Plan Review Details - Permit 13040039
Plan Review Stops For Permit 13040039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-29 Cont ID  
Sent By jwitmer Date 2013-04-29 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2013-04-29 Time 10:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By jwitmer Date 2013-04-12 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2013-04-12 Time 11:33 Sent To  
Notes
2013-04-12 11:57:23BUILDING PLAN REVIEW
 PERMIT: 113040039
 ADD: 13040039
 CONT: ROBB CONSTRUCTION
 TEL: (561)346-9509
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/12/2013
 ACTION: DENIED
  
 1) THE VALUE ON THE PERMIT IS LISTED AS $2,400 DOLLARS,
 THIS WOULD NOT EVEN COVER THE COST FOR THE INTERIOR
 DEMOLITION SHOWN ON D 1.1.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE SHOW THE FURNATURE LAYOUT ON THE LS PLAN, IT
 IS UNCLEAR AS TO THE USAGE OF THIS SPACE. PLEASE ALSO
 NOTE MISSING EMERGENCY LIGHTS IN THE CORRIDOR ADJACENT
 TO THE SERVER ROOM, 2010 FBC-B 1006.1.2.
  
 3) MISSING THE EXIT DIRECTIONAL LIGHT THAT LEADS INTO
 THE CORRIDOR FROM THE SUPERVISORY AREA. 1006.3.1 EXIT
 SIGNS.
  
 4) MISSING THE QUALIFIERS SIGNATURE ON THE PERMIT
 APPLICATION, A HOLD IS ON THE PERMIT TO NOT ISSUE UNTIL
 WE RECEIVE THE QUALIFIERS SIGNATURE.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 14:49 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 14:49 Sent To  
Notes
2013-04-02 14:50:28AN ELECTRICAL PERMIT IS REQUIRED FOR THE MINOR INTERIOR
 ELECTRICAL WORK PROPOSED. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-04-26 Cont ID  
Sent By ddaniels Date 2013-04-26 Time 09:44 Rev Time 0.00
Received By ddaniels Date 2013-04-26 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-08 Cont ID  
Sent By wjolin Date 2013-04-08 Time 12:59 Rev Time 0.00
Received By wjolin Date 2013-04-08 Time 12:27 Sent To  
Notes
2013-04-08 12:58:582000 PALM BEACH LAKES BOULEVARD - SUITE #901
 PERMIT #13040039
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT APPLICATION: THE JOB VALUE OF $2,400 IS
 EXTREMELY LOW AND UNDERVALUED. THE TOTAL PERMIT JOB
 VALUE NEEDS TO INCLUDE MATERIALS AND LABOR.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY.?
  
 SHEET LS1.1: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET LS1.1: NO EMERGENCY LIGHTING PROVIDED IN SMALL
 CORRIDOR CREATED NORTH OF BREAKROOM.
  
 SHEET LS1.1: NO EXIT SIGN PROVIDED AT DOOR #108 LEADING
 TO EXIT ACCESS DOOR IN SMALL CORRIDOR CREATED NORTH OF
 BREAKROOM.
  
 SHEET A1.1: PROVIDE AN OFFICE/FURNITURE LAYOUT OF WHAT
 WILL BE INSTALLED IN THE LARGE OPEN AREA DESIGNATED AS
 "SUPERVISOR'S AREA #107" AND "OPEN FLOOR AREA #108."
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 NO FIRE SPRINKLER SCOPE INDICATED ON PLANS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-29 Cont ID  
Sent By jwitmer Date 2013-04-29 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2013-04-25 Time 10:50 Sent To  
Notes
2013-04-25 10:51:58TO FIRE BOX
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-12 Cont ID  
Sent By jwitmer Date 2013-04-12 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2013-04-01 Time 11:25 Sent To  
Notes
2013-04-02 11:40:25B07

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-03 Cont ID  
Sent By lwagner Date 2013-04-03 Time 12:46 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 12:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By ajones Date 2013-04-03 Time 10:10 Rev Time 0.00
Received By ajones Date 2013-04-03 Time 10:10 Sent To  
Notes
***NONE***