Plan Review Details - Permit 13040038
Plan Review Stops For Permit 13040038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-25 Cont ID  
Sent By J WITMER Date 2013-04-25 Time 11:03 Rev Time 0.00
Received By jwitmer Date 2013-04-25 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-04 Cont ID  
Sent By jwitmer Date 2013-04-04 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2013-04-04 Time 09:38 Sent To  
Notes
2013-04-04 09:49:27BUILDING PLAN REVIEW
 PERMIT: 13040038
 ADD: 2465 MERCER AVE. SUITE 101
 CONT: CROSSROADS CONSTRUCTION
 TEL: (561)346-6160
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 04/04/2013
 ACTION: DENIED
  
 1) THE UNITS LOCATED AT 2465 MERCER ARE COMMERCIAL
 CONDOMINIUMS . THE SAME OWNER WOULD LIKE TO COMBINE
 SUITES 101-103. PLEASE PROVIDE A UNITY OF TITLE FOR
 THESE UNITS.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 2) THE UNITS LOCATED AT 2465 MERCER ARE COMMERCIAL
 CONDOMINIUMS AND TWO DIFFERENT TENANTS BETWEEN 101 &
 104. THE PLANS INDICATE THE EXISTANCE OF A ONE HOUR
 TENANT SEPERATION WALL WITH A ONE HOUR FIRE RATED DOOR.
 THE PLANS DO NOT PROVIDE HARDWARE INFORMATION SHOWING
 COMPLIANCE WITH 715.4.8 FOR FIRE RATED DOORS. TO BE
 SELF CLOSING OR AUTOMATIC-CLOSING IN ACCORDANCE WITH
 THIS SECTION. PLEASE PROVIDE HOW CODE COMPLIANCE WITLL
 BE ACHIEVED. PLEASE PROVIDE CODE COMPLIANCE FOR IF
 THEERE IS EITHER A FIRE OR SMOKE FROM EITHER TENANT
 SPACE THE DOOR WILL AUTOMATICALLY CLOSE. THIS COMMENT
 IS DUPLICATED UNDER 13040040.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 16:15 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 15:43 Sent To  
Notes
2013-04-02 16:10:07SEE NOTE ON PLAN REGARDING UNDERSIZED FEEDER TO NEW
 PANEL 'D' WHICH NEEDS TO BE INCREASED TO # 1 NEC
 T310.16
  
 RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-04-18 Cont ID  
Sent By wjolin Date 2013-04-18 Time 08:42 Rev Time 0.00
Received By wjolin Date 2013-04-18 Time 08:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-08 Cont ID  
Sent By wjolin Date 2013-04-08 Time 12:05 Rev Time 0.00
Received By wjolin Date 2013-04-08 Time 09:08 Sent To  
Notes
2013-04-08 12:05:502465 MERCER AVENUE - SUITE #101
 PERMIT #13040038
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE WORK TO BE PERFORMED IN SUITE
 #104 WHEREAS THE PERMIT APPLICATION INDICATES SUITE
 #101.
  
 PROVIDE A DOOR AND DOOR HARDWARE SCHEDULE FOR OFFICE
 DOOR #12, OFFICE DOOR #14 AND FIRE RATED CORRIDOR DOOR
 ADJACENT TO OFFICE #15. NOTE: THE OFFICE DOORS NEED
 UNLOCKABLE PASSAGEWAY HARDWARE AS THESE DOORS ARE
 INDICATED AS EXIT ACCESS DOORS. FIRE-RATED DOORS SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING AND POSITIVE
 LATCHING.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-01 Cont ID  
Sent By hmoser Date 2013-05-01 Time 15:10 Rev Time 0.00
Received By hmoser Date 2013-04-17 Time 16:24 Sent To  
Notes
2013-04-17 16:30:18B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 09:10 Rev Time 0.00
Received By hmoser Date 2013-04-01 Time 10:41 Sent To  
Notes
2013-04-02 10:41:47B04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-01 Cont ID  
Sent By hmoser Date 2013-05-01 Time 15:09 Rev Time 0.00
Received By hmoser Date 2013-05-01 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 09:09 Rev Time 0.00
Received By hmoser Date 2013-04-10 Time 08:51 Sent To  
Notes
2013-04-10 09:09:52PLANS DENIED
 1) REFER TO SECTION 501.2 EXHAUST DISCHARGE # 2
 2010 FBC (M)
 2) APPLICATION IS FOR SUITE 101,104 PLANS SAY
 101,102 AND 103
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By lwagner Date 2013-04-03 Time 12:36 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 12:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By ajones Date 2013-04-03 Time 10:05 Rev Time 0.00
Received By ajones Date 2013-04-03 Time 10:05 Sent To  
Notes
***NONE***