Plan Review Details - Permit 13040020
Plan Review Stops For Permit 13040020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-16 Cont ID  
Sent By rmcdouga Date 2013-04-16 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2013-04-16 Time 16:22 Sent To  
Notes
2013-04-16 16:22:54REDLINED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-10 Cont ID  
Sent By rmcdouga Date 2013-04-10 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2013-04-10 Time 10:14 Sent To  
Notes
2013-04-10 14:29:162010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBCR 4101.17 RESIDENTIAL
 SWIMMING POOL BARRIER REQUIREMENT ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-10 Cont ID  
Sent By rmcdouga Date 2013-04-10 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2013-04-10 Time 11:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2013-04-10 Cont ID  
Sent By rmcdouga Date 2013-04-10 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2013-04-10 Time 10:14 Sent To  
Notes
2013-04-10 10:14:53NO GAS INDICATED ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-10 Cont ID  
Sent By rmcdouga Date 2013-04-10 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2013-04-01 Time 15:51 Sent To  
Notes
2013-04-01 15:51:53SENT TO ZONING BOX.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-16 Cont ID  
Sent By rmcdouga Date 2013-04-16 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2013-04-16 Time 16:23 Sent To  
Notes
2013-04-16 16:24:20REDLINED PLANS. SUCTION LINES TO BE 3 INCH.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-04-10 Cont ID  
Sent By rmcdouga Date 2013-04-10 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2013-04-10 Time 11:11 Sent To  
Notes
2013-04-10 13:41:112010 FBC
  
 DENIED BY BUILDING
  
 1) FBCR 4101.6.3 STATES THAT WATER VELOCITY IN POOL
 PIPING SHALL NOT EXCEED 8 FEET PER SECOND IN SUCTION
 PIPING. ANSI/APSP 7 2006 SECTION 4.4 STATES THAT WATER
 VELOCITY IN FIELD FABRICATED PIPING IS BASED ON THE
 MAXIMUM SYSTEM FLOW RATE. THE PUMP PERFORMANCE CURVE
 FOR THE PENTAIR INTELLIFLO VS+SVRS 3050 VARIABLE SPEED
 PUMP HAS A MAXIMUM FLO RATE OF 145 G.P.M. WITH A 50'
 TDH. THE WATER VELOCITY IN 2-1/2 " PIPE AT THE MAXIMUM
 FLOW RATE OF 145 GPM IS 9.48 FT PER SECOND WHICH
 EXCEEDS THE 8 FEET PER SECOND ALLOWED BY CODE. PLEASE
 CORRECT.
  
 2) PLEASE SPECIFY THE PROPOSED PUMP SIZE AND MODEL ON
 THE POOL PLANS. CITY AMENDMENTS 107.2.1
 THIS REVIEWED WAS BASED ON THE POOL PUMP THAT WAS
 INDICATED ON THE PENTAIR TDH CALCULATOR PAGE THAT WAS
 STAPLED TO THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2013-04-09 Cont ID  
Sent By mdekle Date 2013-04-09 Time   Rev Time  
Received By mdekle Date 2013-04-02 Time   Sent To  
Notes
2013-04-09 13:33:23GAVE TO R.M. - MD