Plan Review Details - Permit 13040011
Plan Review Stops For Permit 13040011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By jwitmer Date 2013-06-03 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 15:03 Sent To  
Notes
2013-06-03 15:59:27BUILDING PLAN REVIEW
 PERMIT: 13040011
 ADD: 1002 GREEN PINE BLVD # B1
 CONT: H LAYTON MAINGUY GC
 TEL: (954)249-8500
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 6/03/ 2013
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR THE HORIZONTAL
 SLIDERS DOES NOT INCLUDE MULLIONS WINDOW TYPE D
 INDICATES THERE ARE TWO ADJOINING WINDOWS THAT WILL
 REQUIRE EITHER A MULLION OR A STRUCTURAL FRAMING MEMBER
 TO TRANSFER THE WINDOW LOADS IN TO THE EXTERIOR WALL
 SYSTEM, PART OF THE MWFRS, PLEASE SHOW COMPLIANCE WITH:
 MULLIONS OR MULLED FENESTRATION ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY IN ACCORDANCE
 WITH EITHER AAMA 450, ASTM E 330, OR TAS 202 (HVHZ
 SHALL COMPLY WITH TAS 202), OR SHALL BE ENGINEERED IN
 ACCORDANCE WITH AAMA 450 USING ACCEPTED ENGINEERING
 PRACTICE. MULLIONS TESTED AS STAND-ALONE UNITS OR
 QUALIFIED BY ENGINEERING SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1715.5.5.2, 1715.5.5.3 AND
 1715.5.5.4. MULLIONS QUALIFIED BY AN ACTUAL TEST OF AN
 ENTIRE ASSEMBLY SHALL COMPLY WITH SECTION 1715.5.5.4,
 EXCEPT THAT MULLIONS IN ASSEMBLIES REQUIRING A
 DEFLECTION LIMITATION, AS DEFINED IN AAMA/WDMA/CSA
 101/I.S.2/A440, SHALL MEET 1715.5.5.2 AND 1715.5.5.3.
 PRODUCTS NOT INCLUDED WITHIN THE SCOPE OF SECTION
 1715.5.5.1 SHALL COMPLY WITH SECTIONS 1715.5.5.3 AND
 1715.5.5.4.
 1715.5.5.2 LOAD TRANSFER.
 1715.5.5.3 DEFLECTION.
 1715.5.5.4 STRUCTURAL SAFETY FACTOR.
 1715.5.5.4 STRUCTURAL SAFETY FACTOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By jwitmer Date 2013-04-12 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2013-04-11 Time 14:13 Sent To  
Notes
2013-04-11 14:23:39BUILDING PLAN REVIEW
 PERMIT: 13040011
 ADD: 1002 GREEN PINE BLVD # B1
 CONT: H LAYTON MAINGUY GC
 TEL: (954)249-8500
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/11/ 2013
 ACTION: DENIED
  
 1) THE PLANS IN THE TITLEBLOCK INDICATE "FIRE", IS
 THERE FIRE DAMAGE TO THE INTERIOR OF THIS UNIT? IF SO
 DID THE FIRE BURN THROUGH THE DRYWALL AND REQUIRE FLOOR
 TRUSS REPAIR? IF SO WILL NEED AN EGINEERS' DESIGN FOR
 THE FLOOR TRUSS REPAIR. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) THE PLANS INDICATE EXTERIOR WORK ON THE WINDOWS AND
 DOORS, BUT THE PLANS FAIL TO PROVIDE THE WIND DESIGN
 CRITERIA FROM WHICH THE PRESSURES WERE DESIGNED?
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 HOW MANY STORIES IS THIS UNIT? NEGATIVE PRESSURES ARE
 TAKEN FROM THE MEAN ROOF HEIGTH.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) WITHIN THE PRODUCT APPROVALS FOR THE HORIZONTAL
 SLIDER WINDOWS AND THE SINGLE HUNG WINDOWS PLEASE
 CIRCLE WHICH SERIES WILL BE INSTALLED, THIS IDENTIFIES
 THE PRESSURES FOR THAT PARTICULAR MODEL IF IMPACT OR
 NOT. 1609.1.2.
  
 5) THE WINDOW SCHEDULE INDICATES A TYPE "C" FIXED
 WINDOW, BUT WHEN YOU LOOK AT THE FLOOR PLAN THE TYPE
 "C" OPENING IS THE FRONT DOOR, DISCREPANCY IN THE
 PLANS. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE PRODUCT APPROVAL SUBMITTED FOR THE HORIZONTAL
 SLIDERS DOES NOT INCLUDE MULLIONS, PLEASE SHOW
 COMPLIANCE WITH:
  
  
  
 7A) SHEET A-1.0 NOTE # 6 REFERENECES CODE SECTION
 402.1.6.3 BUT DOES NOT LIST WHICH CODE? BUILDING OR
 RESIDENTIAL, NO SUCH SECTION.
 2010 FBC-B 1715.5.5.1 MULLIONS.
 MULLIONS OR MULLED FENESTRATION ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY IN ACCORDANCE
 WITH EITHER AAMA 450, ASTM E 330, OR TAS 202 (HVHZ
 SHALL COMPLY WITH TAS 202), OR SHALL BE ENGINEERED IN
 ACCORDANCE WITH AAMA 450 USING ACCEPTED ENGINEERING
 PRACTICE. MULLIONS TESTED AS STAND-ALONE UNITS OR
 QUALIFIED BY ENGINEERING SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1715.5.5.2, 1715.5.5.3 AND
 1715.5.5.4. MULLIONS QUALIFIED BY AN ACTUAL TEST OF AN
 ENTIRE ASSEMBLY SHALL COMPLY WITH SECTION 1715.5.5.4,
 EXCEPT THAT MULLIONS IN ASSEMBLIES REQUIRING A
 DEFLECTION LIMITATION, AS DEFINED IN AAMA/WDMA/CSA
 101/I.S.2/A440, SHALL MEET 1715.5.5.2 AND 1715.5.5.3.
 PRODUCTS NOT INCLUDED WITHIN THE SCOPE OF SECTION
 1715.5.5.1 SHALL COMPLY WITH SECTIONS 1715.5.5.3 AND
 1715.5.5.4.
 1715.5.5.2 LOAD TRANSFER.
 1715.5.5.3 DEFLECTION.
 1715.5.5.4 STRUCTURAL SAFETY FACTOR.
 1715.5.5.4 STRUCTURAL SAFETY FACTOR.
  
 7B) SHEET A-1.0 NOTE # 6 ALSO REFERENCES CODE SECTION
 R303 WHICH IS THE ONE & TWO FAMILY RESIDENTIAL CODE,
 THIS IS A CONDOMINIUM (R2) WHICH FALLS UNDER THE 2010
 FBC-B.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-05 Cont ID  
Sent By dharvey Date 2013-06-05 Time 11:35 Rev Time 0.00
Received By dharvey Date 2013-06-05 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-02 Cont ID  
Sent By dharvey Date 2013-05-02 Time 15:16 Rev Time 0.00
Received By dharvey Date 2013-05-02 Time 15:16 Sent To  
Notes
2013-05-02 15:19:031. PROVIDE PANEL SCHEDULE SHOW EXISTING AND NEW
 CIRCUITS
 2. ALL OUTLETS TO BE AFCI PROTECTED PER NEC 210.12B
 3. ALL REQUIRED RECEPTACLES TO BE TAMPER RESISTANT PER
 NEC 406.11
 4. PROVIDE A RECEPTACLE IN HALLWAY IF 10 FT LONG. (NOT
 SHOWN ON PLAN)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-04-08 Cont ID  
Sent By wjolin Date 2013-04-08 Time 13:08 Rev Time 0.00
Received By wjolin Date 2013-04-08 Time 12:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-20 Cont ID  
Sent By jwitmer Date 2013-06-20 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2013-06-20 Time 15:34 Sent To  
Notes
2013-06-20 15:34:46PBC IMPACT FEES STAMPED
 NO FEES DUE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 13:17 Rev Time 0.00
Received By hmoser Date 2013-05-22 Time 14:43 Sent To  
Notes
2013-05-23 14:53:20B--21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-02 Cont ID  
Sent By shill Date 2013-05-02 Time 15:45 Rev Time 0.00
Received By shill Date 2013-04-01 Time 13:37 Sent To  
Notes
2013-04-02 13:38:18B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-06-17 Cont ID  
Sent By jwitmer Date 2013-06-03 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 16:00 Sent To  
Notes
2013-06-24 09:42:45CHGD TO "N" FOR PLAN REVIEW TO PRINT PERMIT CARD (SEE
 INCOMING STOP DATED 6-20-13 PASSED BY J WITMER)
2013-06-03 16:00:25BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By jwitmer Date 2013-04-12 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2013-04-12 Time 10:39 Sent To  
Notes
2013-04-12 10:39:26BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 13:17 Rev Time 0.00
Received By hmoser Date 2013-06-14 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 10:31 Rev Time 0.00
Received By hmoser Date 2013-04-10 Time 10:19 Sent To  
Notes
2013-04-10 10:31:08PLANS DENIED
 APPLICATION IS REQUESTING A/C WORK.
 AIR CONDITIONING PLAN DOES NOT SHOW WHAT
 TYPE OF A/C WORK YOU ARE DOING.
 PLAN REVIEW BY HAROLD MOSER.
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-03 Cont ID  
Sent By lwagner Date 2013-04-03 Time 13:08 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 12:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-04-10 Cont ID  
Sent By ajones Date 2013-04-10 Time 11:45 Rev Time 0.00
Received By ajones Date 2013-04-10 Time 11:45 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved