Plan Review Details - Permit 13030826
Plan Review Stops For Permit 13030826
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 10:40 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 09:46 Rev Time 0.00
Received By rlecky Date 2013-04-01 Time 09:38 Sent To  
Notes
2013-04-01 09:46:40ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 PROVIDE AN ELECTRICAL RISER PLAN. NEC 215.5
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 10:40 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 09:47 Sent To  
Notes
2013-04-02 09:48:12SENT TO ELECTRICAL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 09:46 Rev Time 0.00
Received By rlecky Date 2013-03-28 Time 16:21 Sent To  
Notes
2013-03-28 16:22:00SENT TO ELECTRICAL SHELF FOR REVIEW. JG.