Plan Review Details - Permit 13030722
Plan Review Stops For Permit 13030722
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-28 Cont ID  
Sent By rmcdouga Date 2013-03-28 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2013-03-28 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-27 Cont ID  
Sent By rmcdouga Date 2013-03-27 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2013-03-27 Time 16:42 Sent To  
Notes
2013-03-27 16:53:542010 FBC
  
 DENIED BY BUILDING
  
 1) THE MAXIMUM UPLIFT PRESSURE OF -71 PSF FROM THE
 METAL ROOF PRODUCT APPROVALS ARE TOO LOW FOR THIS
 PROJECT. THIS STRUCTURE IS LOCATED IN A 17O MPH VULT /
 132 MPH VASD WIND SPEED AND EXPOSURE CATEGORY D. PLEASE
 SUBMIT PRODUCT APPROVALS WITH ADEQUATE UPLIFT
 PRESSURES. DCA RULE 9N-3 AND FBC R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW