Plan Review Details - Permit 13030651
Plan Review Stops For Permit 13030651
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-04-02 Cont ID  
Sent By jwitmer Date 2013-04-02 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2013-04-02 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-18 Cont ID  
Sent By dharvey Date 2013-04-18 Time 14:48 Rev Time 0.00
Received By dharvey Date 2013-04-18 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-03-27 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2013-03-27 Time 13:30 Sent To  
Notes
2013-03-27 13:46:31PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
 NOTE: SHEET A7 WITH POWER PLAN DOES NOT APPEAR WITH THE
 ELECTRICAL PLANS?
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By wjolin Date 2013-03-25 Time 12:54 Rev Time 0.00
Received By wjolin Date 2013-03-25 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-18 Cont ID  
Sent By dharvey Date 2013-04-18 Time 14:48 Rev Time 0.00
Received By dharvey Date 2013-04-11 Time 13:02 Sent To  
Notes
2013-04-11 13:02:43TO ELEC
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-02 Cont ID  
Sent By jwitmer Date 2013-04-02 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2013-03-22 Time 18:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-29 Cont ID  
Sent By hmoser Date 2013-03-29 Time 14:20 Rev Time 0.00
Received By hmoser Date 2013-03-29 Time 13:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-28 Cont ID  
Sent By lwagner Date 2013-03-28 Time 08:21 Rev Time 0.00
Received By lwagner Date 2013-03-27 Time 14:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved