Plan Review Stops For Permit 13030510 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2013-05-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-02 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-02 |
Time |
14:15 |
Sent To |
|
|
Notes |
2013-05-02 14:24:07 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- REVISE ENERGY CALCULATIONS FOR THE MAIN HOUSE. SEC. | | 107.2.1 CITY AMENDMENTS TO FBC. | | A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS | | TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM | | #15 (CF, CV). | | B) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON | | SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS | | AND ELEVATIONS AND REVISE AS REQUIRED. | | C) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT | | OFFICE, JURISDICTION, ETC. | | | | 2- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN | | THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF | | FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA | | STATUTE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2013-05-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-01 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-01 |
Time |
14:12 |
Sent To |
|
|
Notes |
2013-05-01 15:05:24 | 1- REVISE ENERGY CALCULATIONS. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS | | TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM | | #15 (CF, CV) AS REQUIRED BY SEC. 405.6 OF 2010 | | FBC-ENERGY CONSERVATION. | | ***NOTE: THIS APPLIES TO THE MAIN HOUSE (CV) | | | | B) REVISE DOOR TYPE SHOWN ON SHEET 3 OF 5. WHERE IS THE | | WOOD DOOR. SEE PRODUCT APPROVALS SUBMITTED. | | ***NOTE: THIS APPLIES TO THE MAIN HOUSE. (20S.F NOT | | .1S.F) NOT REVISED. | | | | C) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON | | SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS | | AND ELEVATIONS AND REVISE AS REQUIRED. | | *** NOTE: THIS APPLIES TO THE MAIN HOUSE. NOT REVISED | | | | D) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT | | OFFICE, JURISDICTION, ETC. | | | | 2- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN | | THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF | | FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA | | STATUTE. | | SEC. 107.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. NOT | | ADDRESSED). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-03-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-03-25 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-03-25 |
Time |
10:45 |
Sent To |
|
|
Notes |
2013-03-25 11:28:24 | RESIDENTIAL (R3) ALTERATIONS BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 | | FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE | | "C" NOT "B". ENGINEER OF RECORD TO REVISE DESIGN | | CRITERIA AND DESIGN PRESSURES ON SHEET S-1. | | | | 2- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N. | | JOG RD) TO VERIFY IF IMPACT FEES ARE DUE FOR THE | | PROPOSED STUDIO. BRING BACK STAMPED PLANS AND COPY OF | | PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | CODE. | | | | 3- SPECIFY SIZE OF MIDDLE BEDROOM WINDOWS TO VERIFY | | COMPLIANCE WITH EGRESS SEC. R310. | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) WINDOW MULLIONS. NOA 10-0819.05 SUBMITTED WAS | | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE | | AND DOWNLOAD CURRENT NOA. | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON SHEET | | S-1. PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE | | CONNECTOR. | | C) INSWING ENTRY DOOR AS SHOWN ON PLANS. | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | 6- REVISE ENERGY CALCULATIONS. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS | | TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM | | #15 (CF, CV) AS REQUIRED BY SEC. 405.6 OF 2010 | | FBC-ENERGY CONSERVATION. | | B) REVISE DOOR TYPE SHOWN ON SHEET 3 OF 5. WHERE IS THE | | WOOD DOOR. SEE PRODUCT APPROVALS SUBMITTED. | | C) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON | | SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS | | AND ELEVATIONS AND REVISE AS REQUIRED. | | D) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT | | OFFICE, JURISDICTION, ETC. | | | | 7- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN | | THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF | | FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA | | STATUTE. | | SEC. 107.1 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-04-30 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-04-30 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-04-30 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-03-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-03-27 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-03-27 |
Time |
14:23 |
Sent To |
|
|
Notes |
2013-03-27 14:54:12 | 13030510 | | 213 SEVILLE ROAD | | SFD INTERIOR RENOVATION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL | | WORK PROPOSED IS NOT EXACTLY CLEAR. | | | | IS THE ELECTRICAL SERVICE NEW OR EXISTING? | | | | SHOW LOCATION OF ELECTRICAL PANEL BOARDS AND | | DISCONNECTS WITH SAFETY CLEARANCES. NEC 110.26, 215.5 | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLES LOCATED | | IN THE STUDIO/CABANA. NEC 210.8 | | | | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI | | PROTECTED. NEC 210.8 | | | | RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE | | FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE | | OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC | | 210.52 | | | | PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE | | STUDIO/CABANA ELECTRIC PANEL BOARD. NEC 250.32 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2013-05-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-02 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-02 |
Time |
14:14 |
Sent To |
|
|
Notes |
2013-05-02 14:14:53 | MET WITH ROGGER THOMAS. HE SAID OK TO ISSUE PERMIT WITH | | PROVISO. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-05-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-01 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-04-19 |
Time |
11:50 |
Sent To |
|
|
Notes |
2013-04-26 17:21:28 | EXPEDITE REQUESTED 4/26/13 | 2013-04-19 11:50:43 | SENT TO R10 SHELF FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-04-03 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2013-04-03 |
Time |
|
Rev Time |
0.00 |
Received By |
mdekle |
Date |
2013-03-18 |
Time |
09:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2013-05-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-01 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-01 |
Time |
15:19 |
Sent To |
|
|
Notes |
2013-05-01 15:20:33 | NO FEES DUE. SEE SHEET A2.1 FOR COUNTY STAMP DATED | | 4/18/13. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2013-03-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-03-25 |
Time |
08:41 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-03-25 |
Time |
08:41 |
Sent To |
|
|
Notes |
2013-03-25 08:42:26 | BRING PLANS TO PALM BEACH COUNTY BLDG TO CHECK IF | | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY | | OF PAID RECEIPT IF FEES ARE DUE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2013-03-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-03-26 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-03-26 |
Time |
10:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2013-05-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-01 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-01 |
Time |
14:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2013-03-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-03-25 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-03-25 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2013-04-29 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2013-04-29 |
Time |
|
Rev Time |
0.00 |
Received By |
mdekle |
Date |
2013-04-29 |
Time |
|
Sent To |
|
|
Notes |
2013-04-29 16:25:58 | GAVE TO L.M. - MD | 2013-04-23 10:46:20 | 4/23/13 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2013-04-03 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2013-04-03 |
Time |
|
Rev Time |
0.00 |
Received By |
mdekle |
Date |
2013-04-03 |
Time |
|
Sent To |
|
|
Notes |
2013-04-03 09:51:48 | ZONING PLAN REVIEW | | REVIEW STATUS: FAILED | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | THE ZLDR. | | | | 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | THE ZLDR. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR | | CONSULT THE CITY'S ZONING AND LAND DEVELOPMENT | | REGULATIONS ONLINE @WWW.MUNICODE.COM. | | | | MURRIAH DEKLE, MPA, PLANNER | | PLANNING & ZONING DIVISION | | TEL: (561) 822-1442 | | EMAIL: [email protected] | | |
|
|