Plan Review Details - Permit 13030510
Plan Review Stops For Permit 13030510
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-05-02 Cont ID  
Sent By jgomez Date 2013-05-02 Time 14:15 Rev Time 0.00
Received By jgomez Date 2013-05-02 Time 14:15 Sent To  
Notes
2013-05-02 14:24:07BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS FOR THE MAIN HOUSE. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
 A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS
 TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM
 #15 (CF, CV).
 B) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON
 SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS
 AND ELEVATIONS AND REVISE AS REQUIRED.
 C) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT
 OFFICE, JURISDICTION, ETC.
  
 2- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN
 THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA
 STATUTE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-05-02 Cont ID  
Sent By jgomez Date 2013-05-01 Time 15:04 Rev Time 0.00
Received By jgomez Date 2013-05-01 Time 14:12 Sent To  
Notes
2013-05-01 15:05:241- REVISE ENERGY CALCULATIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
 A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS
 TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM
 #15 (CF, CV) AS REQUIRED BY SEC. 405.6 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE: THIS APPLIES TO THE MAIN HOUSE (CV)
  
 B) REVISE DOOR TYPE SHOWN ON SHEET 3 OF 5. WHERE IS THE
 WOOD DOOR. SEE PRODUCT APPROVALS SUBMITTED.
 ***NOTE: THIS APPLIES TO THE MAIN HOUSE. (20S.F NOT
 .1S.F) NOT REVISED.
  
 C) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON
 SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS
 AND ELEVATIONS AND REVISE AS REQUIRED.
 *** NOTE: THIS APPLIES TO THE MAIN HOUSE. NOT REVISED
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT
 OFFICE, JURISDICTION, ETC.
  
 2- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN
 THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA
 STATUTE.
 SEC. 107.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-25 Cont ID  
Sent By jgomez Date 2013-03-25 Time 10:45 Rev Time 0.00
Received By jgomez Date 2013-03-25 Time 10:45 Sent To  
Notes
2013-03-25 11:28:24RESIDENTIAL (R3) ALTERATIONS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". ENGINEER OF RECORD TO REVISE DESIGN
 CRITERIA AND DESIGN PRESSURES ON SHEET S-1.
  
 2- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD) TO VERIFY IF IMPACT FEES ARE DUE FOR THE
 PROPOSED STUDIO. BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- SPECIFY SIZE OF MIDDLE BEDROOM WINDOWS TO VERIFY
 COMPLIANCE WITH EGRESS SEC. R310.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. NOA 10-0819.05 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON SHEET
 S-1. PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE
 CONNECTOR.
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 6- REVISE ENERGY CALCULATIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
 A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS
 TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM
 #15 (CF, CV) AS REQUIRED BY SEC. 405.6 OF 2010
 FBC-ENERGY CONSERVATION.
 B) REVISE DOOR TYPE SHOWN ON SHEET 3 OF 5. WHERE IS THE
 WOOD DOOR. SEE PRODUCT APPROVALS SUBMITTED.
 C) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON
 SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS
 AND ELEVATIONS AND REVISE AS REQUIRED.
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT
 OFFICE, JURISDICTION, ETC.
  
 7- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN
 THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA
 STATUTE.
 SEC. 107.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-30 Cont ID  
Sent By dharvey Date 2013-04-30 Time 14:19 Rev Time 0.00
Received By dharvey Date 2013-04-30 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-27 Cont ID  
Sent By rlecky Date 2013-03-27 Time 14:52 Rev Time 0.00
Received By rlecky Date 2013-03-27 Time 14:23 Sent To  
Notes
2013-03-27 14:54:1213030510
 213 SEVILLE ROAD
 SFD INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL
 WORK PROPOSED IS NOT EXACTLY CLEAR.
  
 IS THE ELECTRICAL SERVICE NEW OR EXISTING?
  
 SHOW LOCATION OF ELECTRICAL PANEL BOARDS AND
 DISCONNECTS WITH SAFETY CLEARANCES. NEC 110.26, 215.5
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
 GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLES LOCATED
 IN THE STUDIO/CABANA. NEC 210.8
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE
 FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE
 OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC
 210.52
  
 PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE
 STUDIO/CABANA ELECTRIC PANEL BOARD. NEC 250.32
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-02 Cont ID  
Sent By jgomez Date 2013-05-02 Time 14:14 Rev Time 0.00
Received By jgomez Date 2013-05-02 Time 14:14 Sent To  
Notes
2013-05-02 14:14:53MET WITH ROGGER THOMAS. HE SAID OK TO ISSUE PERMIT WITH
 PROVISO. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-01 Cont ID  
Sent By jgomez Date 2013-05-01 Time 15:20 Rev Time 0.00
Received By jgomez Date 2013-04-19 Time 11:50 Sent To  
Notes
2013-04-26 17:21:28EXPEDITE REQUESTED 4/26/13
2013-04-19 11:50:43SENT TO R10 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By mdekle Date 2013-04-03 Time   Rev Time 0.00
Received By mdekle Date 2013-03-18 Time 09:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-05-01 Cont ID  
Sent By jgomez Date 2013-05-01 Time 15:19 Rev Time 0.00
Received By jgomez Date 2013-05-01 Time 15:19 Sent To  
Notes
2013-05-01 15:20:33NO FEES DUE. SEE SHEET A2.1 FOR COUNTY STAMP DATED
 4/18/13. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-25 Cont ID  
Sent By jgomez Date 2013-03-25 Time 08:41 Rev Time 0.00
Received By jgomez Date 2013-03-25 Time 08:41 Sent To  
Notes
2013-03-25 08:42:26BRING PLANS TO PALM BEACH COUNTY BLDG TO CHECK IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-26 Cont ID  
Sent By jgomez Date 2013-03-26 Time 10:23 Rev Time 0.00
Received By jgomez Date 2013-03-26 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-01 Cont ID  
Sent By jgomez Date 2013-05-01 Time 14:40 Rev Time 0.00
Received By jgomez Date 2013-05-01 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By jgomez Date 2013-03-25 Time 10:19 Rev Time 0.00
Received By jgomez Date 2013-03-25 Time 10:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-04-29 Cont ID  
Sent By mdekle Date 2013-04-29 Time   Rev Time 0.00
Received By mdekle Date 2013-04-29 Time   Sent To  
Notes
2013-04-29 16:25:58GAVE TO L.M. - MD
2013-04-23 10:46:204/23/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-03 Cont ID  
Sent By mdekle Date 2013-04-03 Time   Rev Time 0.00
Received By mdekle Date 2013-04-03 Time   Sent To  
Notes
2013-04-03 09:51:48ZONING PLAN REVIEW
 REVIEW STATUS: FAILED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER