Plan Review Details - Permit 13030468
Plan Review Stops For Permit 13030468
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-17 Cont ID  
Sent By jwitmer Date 2013-04-16 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2013-04-16 Time 16:26 Sent To  
Notes
2013-04-16 16:48:45BUILDING PLAN REVIEW
 PERMIT: 13030468
 ADD: 501 FERN ST
 CONT: TBD
 TEL: (561)670-0411
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 4/16/2013
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) MIAMI-DADE NOA 09-0115.04 GAF EVERGUARDTPO SINGLE
 PLY ROOFING SYSTEM OVER STEEL DECK. CONTRACTOR HAS NOT
 IDENTIFIED WHICH SUB-SYSTEM IS TO BE INSTALLED, WILL
 NEED TO IDENTIFY WHICH SUB-SYSTEM WILL BE INSTALLED.
 PLEASE REVIEW THE MAXIMUM DESIGN PRESSURE AND
 LIMITATION FOR EACH SUB-SYSTEM. IF LIMITATION # 7 IS
 INDICATED, THEN ENHANCED FASTENING WILL BE REQUIRED BY
 A DESIGN PROFESSIONAL, RAS 117 CALCULATIONS REQUIRED.
 THIS REVIEW WILL REQUIRE A REVISION, WITH ASSOCAITED
 FEES.
  
 1B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2A ) THE ONLY PRODUCT APPROVAL SUBMITTED FOR WALL
 OPENINGS WAS EURO-WALL +70/-70 PSF LARGE MISSILE
 IMPACT.
 ALL OTHER OPENING APPROVALS WILL REQUIRE A REVISION
 WITH ASSOCIATED FEES.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-28 Cont ID  
Sent By jwitmer Date 2013-03-28 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2013-03-28 Time 13:28 Sent To  
Notes
2013-03-28 14:33:11BUILDING PLAN REVIEW
 PERMIT: 13030468
 ADD: 501 FERN ST
 CONT: TBD
 TEL: (561)670-0411
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 3/28/2013
 ACTION: DENIED
  
 1) THE DESCRIPTION OF WORK FOR THIS PERMIT INDICATES A
 SHELL PERMIT THE ASSUMED SCOPE OF WORK SINCE ROOFING
 APPROVALS, AND GLAZING IS TO INCLUDE THESE IN THE VALUE
 OF WORK AS WELL AS THE DEMOLITION WORK SINCE PERMIT #
 12070649 HAD NEVER BEEN ISSUED. THE VALUE OF THAT
 PERMIT WAS $40,000.00 WHERE AS THE SAID VALUE OF THIS
 SCOPE OF WORK IS VALUED AT
 $9,600 DOLLARS AND THE BUILDING OF A STEEL MEZZANINE.
 PLEASE PROVIDE A MORE ACCURATE VALUE FOR THE WORK TO BE
 ACCCOMPLISHED UNDER THE SCOPE OF THE PERMIT.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE UPDATE YOUR PERMIT APPLICATION AS TO WHERE
 THE WORK IS GOING TO BE COMPLETED. SUITE "C" IS LOCATED
 UNDER THE ADDRESS 515 FERN, PCN
 74-43-43-21-01-022-0080.
 NOTE IF ANY OPENINGS ARE GOING TO BE CREATED BETWEEN
 THIS PROPERTY AND THE PROPERTY TO THE EAST AT 501 FERN
 THEN A UNITY OF TITLE WILL NEED TO BE RECORDED AT THE
 CLERK OF THE COURT.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. A EURO-WALL, EURO-C3 BIFOLD
 ALUMINUN REPORT WAS SUBMITTED, IT DOES NOT INDICATE IF
 IT IS A MIAMI-DADE NOA OR A FLORIDA APPROVAL, OR IT IS
 CURRENT TO THE 2010
 FBC-B. THE OTHER DOOR OPENINGS NO REPORT WAS SUBMITTED.
 (B) WINDOWS- NO REPORT WAS SUBMITTED.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOA 09-0115.04 GAF
 TPO ROOFING SYSTEMS, NO SUB-SYSTEM WAS CIRCLED
 INDICATING WHICH SYSTEM WAS TO BE INSTALLED, PLEASE
 NOTE THAT
 THE ENERGY CALCULATIONS INDICATE A R-23.2 ROOFING
 INSULATION VALUE.
  
 5) PLEASE PROVIDE HOW THE STAIR DESIGN LOCATED ON SHEET
 S-2, WHERE THEY WILL ATTACH TO THE MEZZANINE, PROVIDE
 FLOOR PLAN INDICATING LOCATION OF STAIRS. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-04-19 Cont ID  
Sent By dharvey Date 2013-04-19 Time 14:20 Rev Time 0.00
Received By dharvey Date 2013-04-19 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 14:09 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 12:56 Sent To  
Notes
2013-04-02 14:09:5113030468
 501 FERN ST #C
 SHELL CONSTRUCTION FOR FUTURE TENANTS
  
 THE RESPONSE SUBMITTED FOR 2ND REVIEW IS NOT AS EARLIER
 DISCUSSED. THE SUGGESTION WAS TO PROVIDE A TEMPORARY
 ELECTRIC SERVICE TO BEGIN CONSTRUCTION PENDING A FOLLOW
 UP SUBMITTAL WHICH ADDRESSES THE NEC CODE REQUIREMENT
 FOR A SINGLE POINT OF SERVICE. THE PLANS STILL SHOW
 MULTIPLE ELECTRICAL SERVICES.
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE
 LOCATION. YOUR REQUEST FOR MULTIPLE SERVICE POINTS HAS
 BEEN DENIED. THIS STRUCTURE IS NOT SUFFICIENTLY LARGE
 NOR DOES IT EXHIBIT ANY SPECIAL CONDITIONS WHICH WOULD
 WARRANT THE SPECIAL PERMISSION REQUESTED FOR MULTIPLE
 ELECTRICAL SERVICES. THE PRINCIPAL SAFETY RULE FOR
 ELECTRICAL SERVICES REQUIRES A BUILDING OR STRUCTURE TO
 HAVE ONE POINT OF SERVICE. NEC 230.2, 230.71, 230.72
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-26 Cont ID  
Sent By rlecky Date 2013-03-26 Time 16:04 Rev Time 0.00
Received By rlecky Date 2013-03-26 Time 14:14 Sent To  
Notes
2013-03-26 16:03:5913030468
 501 FERN ST #C
 SHELL CONSTRUCTION FOR FUTURE TENANTS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE
 LOCATION. YOUR REQUEST FOR MULTIPLE SERVICE POINTS HAS
 BEEN DENIED. THIS STRUCTURE IS NOT SUFFICIENTLY LARGE
 NOR DOES IT EXHIBIT ANY SPECIAL CONDITIONS WHICH WOULD
 WARRANT THE SPECIAL PERMISSION REQUESTED FOR MULTIPLE
 ELECTRICAL SERVICES. THE PRINCIPAL SAFETY RULE FOR
 ELECTRICAL SERVICES REQUIRES A BUILDING OR STRUCTURE TO
 HAVE ONE POINT OF SERVICE. NEC 230.2, 230.71, 230.72
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By wjolin Date 2013-03-25 Time 13:05 Rev Time 0.00
Received By wjolin Date 2013-03-25 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2013-04-02 Time 11:30 Sent To  
Notes
2013-04-02 11:30:55INCOMING SENT TO C-7. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-12 Cont ID  
Sent By shill Date 2013-04-03 Time 17:44 Rev Time 0.00
Received By shill Date 2013-03-15 Time 16:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-03-28 Cont ID  
Sent By jwitmer Date 2013-03-28 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2013-03-28 Time 14:59 Sent To  
Notes
2013-03-28 15:00:23SHELL PERMIT ONLY, WILL BE REVIEWED UNDER THE BUILD-
 OUT PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By hmoser Date 2013-04-19 Time 08:55 Rev Time 0.00
Received By hmoser Date 2013-04-19 Time 08:44 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-29 Cont ID  
Sent By hmoser Date 2013-03-29 Time 10:54 Rev Time 0.00
Received By hmoser Date 2013-03-29 Time 09:13 Sent To  
Notes
2013-03-29 10:54:02PLANS DENIED
 1) PROVIDE A DETAIL ON THE PLANS ON HOW RTU 1,2,3 AND 4
 ARE TIED DOWN TO THE CURB. PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 2) SHOW DUCT DETECTORS ON THE ALARM AND MECHANICAL
 PLANS
 FOR RTU 1,2,3 AND 4. PER SECTION 606.2.1 SUPPLY AIR
 SYSTEMS
 AND 606.4.1 SUPERVISION.
 3) PROVIDE WELDERS CERTIFICATION TO THE CITY BEFOR
 WELDING STARTS ON THE JOB
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By lwagner Date 2013-03-25 Time 10:07 Rev Time 0.00
Received By lwagner Date 2013-03-25 Time 09:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By aaponte Date 2013-04-03 Time 08:39 Rev Time 0.00
Received By aaponte Date 2013-04-03 Time 08:39 Sent To  
Notes
2013-04-03 08:39:27SHELL ONLY, NO ZONING RELATED ITEMS.