Plan Review Details - Permit 13030449
Plan Review Stops For Permit 13030449
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 13:40 Rev Time 0.00
Received By hmoser Date 2013-03-18 Time 15:59 Sent To  
Notes
2013-03-18 15:59:17TO MECH

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 13:34 Rev Time 0.00
Received By hmoser Date 2013-03-25 Time 13:34 Sent To  
Notes
2013-03-25 13:40:09PASS PROVISO
 PROVIDE A DETAIL STAMPED BY THE ENGINEER ON
 THE CURB TO ROOF TIE DOWN AND FAN TO CURB TIE DOWN
 AT FIRST INSPECTION. PER SECTION 301.12 WIND
 RESISTANCE,
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER