Plan Review Details - Permit 13030406
Plan Review Stops For Permit 13030406
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-08-12 Cont ID  
Sent By jwitmer Date 2013-08-12 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2013-08-07 Time 09:05 Sent To  
Notes
2013-08-07 11:05:05PROCESSING PLANS, MISSING NEW E2 & E3 SHEETS, OLD
 SHEETS IN PLANS, RESPONCE LETTER INDICATES NEW 2 SETS
 OF E2 & E3.
 I SPOKE WITH DOUG HARVEY AND HE WILL NEED THESE SHEETS
 TO PASS ELECTRICAL. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-07-31 Cont ID  
Sent By jwitmer Date 2013-07-31 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2013-07-31 Time 09:32 Sent To  
Notes
2013-07-31 09:35:21BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD .
  
 1-8) COMPLIED.
  
 9) THREE SETS OF PLANS ARE REQUIRED, THRESHOLD
 BUILDING.
  
 9A) COMPLETE. THRESHOLD PAPER WORK .
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 10:58 Sent To  
Notes
2013-07-10 11:04:38BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 JULY 10/2013
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
 A LETTER FROM THE QUALIFIER OF BOTH THE LANDLORD WORK
 AND TENANT BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE
 TENANT BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT
 BUILD-OUT CONTRACTOR WISHES TO START WORK BEFORE THE
 LANDLORD WORK HAS RECEIVED A CERTIFICATE OF COMPLETION,
 AGREEING THEY WILL WORK TOGETHER TO ACHIEVE CODE
 COMPLIANCE. THESE DOCUMENTS WILL NEED TO BE SIGNED BY
 THE QUALIFIER AND NOTARIZED.
  
 1-8) COMPLIED.
  
  
 9) THREE SETS OF PLANS ARE REQUIRED, THRESHOLD
 BUILDING. PLEASE NOTE 2 SETS OF PLANS WERE SUBMITTED
 ORIGINALLY. THE LAST RESPONCE LETTER INDICATED 3 SETS
 OF REVISIONS ARE BEING SUBMITTED IN RESPONCE TO
 BUILDING COMMENTS, WILL NEED A COMPLETE SET OF PLANS
 FOR THE THRESHOLD INSPECTOR.
  
 9A) COMPLIED. THRESHOLD INSPECTION PLAN.
  
 9B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 9C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
  
 9D) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-05-20 Time 17:00 Rev Time 0.00
Received By jwitmer Date 2013-05-20 Time 16:38 Sent To  
Notes
2013-05-20 17:00:19BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
  
 1) COMPLIED.
  
 2) COMPLIED
  
  
 3) ) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4) COMPLIED, THE MAIN ENTRY / EXIT AND MONUMENTAL STAIR
 MEETS THE REQUIREMENTS OF 1028.2.
  
 5A) 2ND REQUEST. THE LIFE SAFETY PLANS HAVE SERIOUS
 PROBLEMS SINCE THE MONUMETAL STAIRS CAN NOT BE USED FOR
 EXITING AND SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 499
 OCCUPANTS, NEITHER THE STAIRS NOR THE DOORS AT THE BACK
 OF THE BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE
 DESIGNER IS TAKING A 42 INCH DOOR AND STATING 200
 OCCUPANTS CAN EXIT THIS OPENING, WITH THE 2 DOORS MAXED
 OUT AT 400 OCCUPANTS THERE ARE STILL 99 OCCUPANTS NOT
 ACCOUNTED FOR IN EXITING THE 2ND FLOOR. THE BACK OF
 HOUSE STAIR 1 & 2 DO NOT PROVIDE THE WIDTH OF THE STAIR
 AND HOW MANY OCCUPANTS CAN USE THESE STAIRS AS A MENAS
 OF EGRESS.
  
 5B) THE SERVICE CORRIDOR IS ALSO CONSIDERED A EXIT
 PASSAGEWAY SINCE IT IS A CONTINUATION OF THE VERTICAL
 EXIT. MANY OF THE DOORS IN THIS EXIT PASSAGEWAY
 DOORWAYS ARE NOT WIDE ENOUGH FOR THE NEW ASSEMBLY
 OCCUPANCIES THAT NOW EXIST. FOR EXAMPLE TO THE SOUTH
 THE SPACE WAS ORIGINALLY DESIGN FOR MERCANTILE
 OCCUPANCY, THIS IS NOW GOING TO BE A RESTRAUNT WITH
 DOUBLE THE OCCUPANT LOAD OF HOW THE EXIT PASSAGE WAY
 WAS DESIGNED. THE SAME HOLD TRUE JUST TO THE NORTH, A
 SECOND FLOOR NIGHTCLUB AND THE SECONDARY EXIT THAT
 LEADS TO THE EXIT STAIRS. THE PROVIDED 499 FOR THE
 SECOND FLOOR OCCUPANY LOADS THAT SHARE THE EXITING FOR
 THIS COMMON EXIT PASSAGE WAY WILL NOT WORK WITH THE
 CURRENT ARRANGEMENT. PLEASE NOTE PART OF THE EXIT
 DISCHARGE A 4 FOOT WIDE SIDEWALK TO THE PARKING GARAGE
 IS NOT WIDE ENOUGH ALSO FIGURE THE REQUIRED WIDTH OF
 THE EXTERIOR STAIR WITHIN THE WALKWAY. THE OTHER
 SIDEWALK THAT LEADS TO OKEECHOBEE BLVD IS NOT PROVIDED
 IN ITS ENTIREITY NOR THE PROPOSED WIDTH.
 5C) THE CURRENT PLAN INDICATES THE OCCUPANT LOAD FROM
 NV LOUNGE ALONE (340 OCCUPANTS) DOES NOT ALLOW FOR THE
 OCCUPANT LOAD THAT NEEDS TO EXIT THE FIRST FLOOR.
  
 6) ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT
 LOAD ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY
 2010 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON
 THE 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL
 ALSO BE REQUIRED. UNTIL THE TENANT EXITING FROM THE
 TENANT SPACE THE LANDLORD WORK CAN NOT BE APPROVED
 SINCE THEEXITING THROUGH THE EXIT PASSAGEWAY IS UNDER
 THE LANDLORD CONTROL.
  
 7)COMPLIED> SPRINKLERS & SMOKE DRAFT CURTAIN TO BE
 UNDER TENANT IMPROVEMENT PERMIT.
  
 8) COMPLIED, TO BE UNDER TENANT SEPERATE PERMIT . SHEET
 # A-3.0 INDICATES A NEW ROOF CURB PLEASE PROVIDE THE
 MANUFACTURES CUT SHEETS ON THE NEW ROOF CURB FOR THIS
 WIND SPEED, 170 MPH V-ULT.
  
 9) THREE SETS OF PLANS ARE REQUIRED, THRESHOLD
 BUILDING.
  
 9A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 9B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 9C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 9D) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-25 Cont ID  
Sent By jwitmer Date 2013-03-25 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2013-03-25 Time 10:16 Sent To  
Notes
2013-03-25 11:29:59BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
  
 1A) SHEET A-1.0 INDICATES THAT THIS TENANT SPACE IS NOT
 CHANGE OF OCCUPANCY. BARNES & NOBLE OCCUPIED THIS SPACE
 A MERCANTILE OCCUPANCY. LA FITNESS IS PROPOSING TO
 BECOME THE NEW TENANT, A A-3 OCCUPANCY. THE DESIGNER OF
 RECORD WILL NEED TO REVIEW THE 2010 EXISTING BUILDING
 CODE 901.3.1 FOR BUILDINGS THAT ARE UNDER GOING A
 PARTIAL CHANGE OF OCCUPANCY, SECTION 912 WILL APPLY.
  
 1B) SHEET A1-0 NOTE # 16 REFERENCE MINIMUM EXIT AISLES
 OR CORRIDORS AND CODE REFERENCE 1017.2 FOR AISLES FOR
 BUSINESS & MERCANTILE, THIS IS AN A-3 OCCUPANCY. PLEASE
 CORECT.
  
 1C) 1B) SHEET A1-0 NOTE # 17 REFERENCE THE MINIMUM
 NUMBER OF EXITS REQUIRED AND REFERNCES TABLE 1019.1, NO
 SUCH TABLE, SECTION 1019.1 IS FOR EGRESS BALCONIES.
  
 1D) 1B) SHEET A1-0 NOTE # 18 REFERENCES THE NUMBER OF
 EXITS PROVIDED AS THREE ACTUALLY ONLY TWO, THE FRONT
 AND THE BACK, THE TWO VERTICAL EXITS DROP INTO THE SAME
 EXIT PASSAGE WAY.
  
 1E) SHEET A1-0 NOTE # 19 REFERENCES MAXIMUM PATH OF
 TRAVEL, AND SECTION 1025.8 WHICH DEALS WITH HORIZONTAL
 EXITS.
  
 1F) 1B) SHEET A1-0 NOTE # 20 REFERENCES MAXIMUM DEAD
 ENDS AND REFENECES SECTION # 1017 BUT IS AISLES.
  
 2A) THE DESIGNER OF RECORD SHALL ELECT TO DESSIGN THIS
 TENANT SPACE UNDER EITHER SECTION:
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 3) ) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4) THE MONUMENTAL STAIR IS NOW AN ISSUE (A-3 OCCUPANCY)
 WHERE IT WAS NOT UNDER THE MERCANTILE OCCUPANCY. THE
 EXCEPTION FOR MONUMENTAL STAIRS IS FOUND UNDER 708.2
 EXCEPTION # 7, THE MONUMENTAL STAIR NOT REQUIRED TO BE
 PART OF THE MEANS OF EGRESS BECAUSE THERE WERE 2
 VERTICAL EXITS TO THE 2ND FLOOR.
  
 THE 2010 FBC-B SECTION 1028.2 REQUIRES 50 % OF THE
 TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN EXIT. 1028.3
 ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE
 PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO
 ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED
 BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED
 AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH
 EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE
 AISLE. PLEASE PROVIDE CODE COMPLIANCE.
  
 IF THE MONUMENTAL STAIR WAS ENCLOSED ON BOTH FLOORS
 WITH A ONE HOUR RATED ENCLOSURE IT WOULD THEN BECOME A
 CODE COMPLIANT SET OF EXIT STAIRS, THEY WOULD NOT BE
 REQUIRED TO GO TO THE EXTERIOR OF THE BUILDING SINCE
 THE 2 VERTICAL EXITS WOULD MEET THAT REQUIREMENT. DOORS
 COULD BE LEFT IN THE OPEN POSITION IF THEY WERE TIED TO
 MAG LOCKS AND THE FIRE ALARM.
  
 5) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE
 THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND
 SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS,
 NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE
 BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER
 IS TAKING A 36 INCH DOOR AND STATING 180 OCCUPANTS CAN
 EXIT THIS OPENING, WHEREAS THE CLEAR OPENING IS CLOSER
 TO 34 INCHES AND ONLY 170 OCCUPANTS CAN EXIT. FOR A
 PAIR OF DOUBLE DOORS 340 OCCUPANTS. THE BACK OF HOUSE
 SEERVICE CORRIDOR IS ALSO CONSIDERED A EXIT PASSAGEWAY
 SINCE IT IS A CONTINUATION OF THE VERTICAL EXIT. MANY
 OF THE DOORS IN THIS EXIT PASSAGEWAY DOORWAYS ARE NOT
 WIDE ENOUGH FOR THE NEW ASSEMBLY OCCUPANCIES THAT NOW
 EXIST. FOR EXAMPLE TO THE SOUTH THE SPACE WAS
 ORIGINALLY DESIGN FOR MERCANTILE OCCUPANCY, THIS IS NOW
 GOING TO BE A RESTRAUNT WITH DOUBLE THE OCCUPANT LOAD
 OF HOW THE EXIT PASSAGE WAY WAS DESIGNED. THE SAME HOLD
 TRUE JUST TO THE NORTH, A SECOND FLOOR NIGHTCLUB AND
 THE SECONDARY EXIT THAT LEADS TO THE EXIT STAIRS.
 PLEASE PROVIDE THE OCCUPANT LOADS THAT WILL SHARE THE
 EXITING FOR THIS COMMON EXIT PASSAGE WAY. PLEASE NOTE
 PART OF THE EXIT DISCHARGE A 4 FOOT WIDE SIDEWALK
 AND STAIRS., THE STAIRS WILL ONLY ALLOW FOR 160
 OCCUPANTS. PLEASE PROVIDE THE LIFE SAFETY PLANS TO THE
 PUBLIC WAY.
  
 6) ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT
 LOAD ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY
 2010 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON
 THE 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL
 ALSO BE REQUIRED.
  
 7) ) THE PLANS DO NOT PROVIDE A SECTION THROUGH THE
 MONUMENTAL STAIRWAY, PLEASE PROVIDE SUCH SECTION
 PROVIDING DETAILS SUCH AS DRAFT CURTAIN AND SPRINKLER
 LOCATION.
 2010 FBC-B 708.2 EXCEPTION 2.1. WHERE THE AREA OF THE
 FLOOR OPENING BETWEEN STORIES DOES NOT EXCEED TWICE THE
 HORIZONTAL PROJECTED AREA OF THE ESCALATOR OR STAIRWAY
 AND THE OPENING IS PROTECTED BY A DRAFT CURTAIN AND
 CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13.
 IN OTHER THAN GROUPS B AND M, THIS APPLICATION IS
 LIMITED TO OPENINGS THAT DO NOT CONNECT MORE THAN FOUR
 STORIES. PLEASE NOTE THIS EXCEPTION IS ONLY FOR
 BUSINESS & MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE
 PROVIDE HOW THIS CODE VIOLATION WILL BE COMPLIED.
  
 8) SHEET # A-3.0 INDICATES A NEW ROOF CURB PLEASE
 PROVIDE TTHE MANUFACTURES CUT SHEETS ON THE NEW ROOF
 CURB FOR THIS WIND SPEED, 170 MPH V-ULT.
  
 9A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 9B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 9C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 9D) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-08-12 Cont ID  
Sent By dharvey Date 2013-08-12 Time 13:30 Rev Time 0.00
Received By dharvey Date 2013-08-12 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 10:21 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 10:21 Sent To  
Notes
2013-05-07 10:21:545-7-13
 CORRECTIONS MADE......
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-26 Cont ID  
Sent By rlecky Date 2013-03-26 Time 14:06 Rev Time 0.00
Received By rlecky Date 2013-03-26 Time 12:24 Sent To  
Notes
2013-03-26 14:12:1513030406
 700 S. ROSEMARY AVE #104
 L.A. FITNESS (PRELIMINARY PLAN)
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 GROUND FAULT PROTECTION EQUIPMENT (GFPE) IS REQUIRED
 FOR THE NEW ELECTRIC SERVICE. NEC 230.95
  
 INDICATE THE FAULT CURRENT INTERRUPTING RATING REQUIRED
 FOR THE ELECTRICAL SERVICE EQUIPMENT. NEC 110.9
  
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-23 Cont ID  
Sent By wjolin Date 2013-07-23 Time 12:02 Rev Time 0.00
Received By wjolin Date 2013-07-23 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-05-22 Cont ID  
Sent By wjolin Date 2013-05-22 Time 11:02 Rev Time 0.00
Received By wjolin Date 2013-05-09 Time 11:28 Sent To  
Notes
2013-05-22 11:02:23700 SOUTH ROSEMARY AVENUE- SUITE #104
 PERMIT #13030406 (OWNER PERMIT)
 [PERMIT # 13010720 (TENANT PERMIT)]
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE OCCUPANT LOAD CALCULATIONS NEED TO BE ACCURATE AND
 APPROVED FOR THE TENANT IMPROVEMENT PERMIT (#13010720)
 BEFORE AN ACCURATE PLAN REVIEW CAN BE COMPLETED FOR
 THIS PERMIT. REFER TO BUILDING REVIEWER COMMENTS
 CONCERNING INADEQUATE EGRESS WIDTHS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-21 Cont ID  
Sent By wjolin Date 2013-03-21 Time 12:47 Rev Time 0.00
Received By wjolin Date 2013-03-21 Time 12:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-03-27 Cont ID  
Sent By lwagner Date 2013-03-27 Time 09:34 Rev Time 0.00
Received By lwagner Date 2013-03-27 Time 09:28 Sent To  
Notes
2013-03-27 09:35:12SEPARATE GAS PERMMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-08-12 Cont ID  
Sent By jwitmer Date 2013-08-12 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2013-08-09 Time 15:43 Sent To  
Notes
2013-08-09 15:45:58REQUESTED ELECTRICAL SHEETS SENT TO J WITMER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-23 Cont ID  
Sent By wjolin Date 2013-07-23 Time 12:09 Rev Time 0.00
Received By wjolin Date 2013-06-28 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-30 Cont ID  
Sent By eschneid Date 2013-05-30 Time 16:13 Rev Time 0.00
Received By eschneid Date 2013-05-06 Time 11:36 Sent To  
Notes
2013-05-06 11:39:15INCOMING SENT TO C-25 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 14:25 Rev Time 0.00
Received By hmoser Date 2013-03-14 Time 14:21 Sent To  
Notes
2013-03-15 16:38:39C--4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 14:24 Rev Time 0.00
Received By hmoser Date 2013-03-28 Time 13:44 Sent To  
Notes
2013-03-28 14:24:34PASS PROVISO
 PROVIDE WELDING CERTIFICATION AT FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-27 Cont ID  
Sent By lwagner Date 2013-03-27 Time 09:34 Rev Time 0.00
Received By lwagner Date 2013-03-26 Time 15:35 Sent To  
Notes
2013-03-26 16:05:12***PROVISO***
 606.5.5 LOW-PRESSURE CUTOFF REQUIRED ON BOOSTER PUMPS.
 A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL BOOSTER
 PUMPS IN A WATER PRESSURE BOOSTER SYSTEM TO PREVENT
 CREATION OF A VACUUM OR NEGATIVE PRESSURE ON THE
 SUCTION SIDE OF THE PUMP WHEN A POSITIVE PRESSURE OF 10
 PSI (68.94 KPA) OR LESS OCCURS ON THE SUCTION SIDE OF
 THE PUMP.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2013-08-07 Cont ID  
Sent By jwitmer Date 2013-08-07 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2013-08-07 Time 10:43 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 11:09 Sent To  
Notes
2013-07-10 11:09:27BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 JULY 10/2013
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
  
 3 SETS OF PLANS REQUIRED. MISSING ONE SET.
  
 1A)COMPLIED. THRESHOLD INSPECTION PLAN.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) COMPLIED, THRESHOLD BLDG, REQUIRED STATEMENT:
  
 2) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT UNTIL
 THESE ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF
 BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2A) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2B) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 11:05 Sent To  
Notes
2013-07-10 11:08:11BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 JULY 10/2013
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
  
 3 SETS OF PLANS REQUIRED. MISSING ONE SET.
  
 1A)COMPLIED. THRESHOLD INSPECTION PLAN.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) COMPLIED, THRESHOLD BLDG, REQUIRED STATEMENT:
  
 2) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT UNTIL
 THESE ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF
 BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2A) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2B) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2013-03-25 Cont ID  
Sent By jwitmer Date 2013-03-25 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2013-03-25 Time 11:30 Sent To  
Notes
2013-03-25 11:32:33BUILDING PLAN REVIEW
 PERMIT: 13030406
 ADD: 700 S ROSEMARY # 104
 CONT: CHANDLIER CONSTRUCTION
 CONTACT:JOHN CHANDLIER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE
 LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY
 BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD
 OR TENANT WILL TAKE RESPONSIBILITY.
  
 1A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT UNTIL
 THESE ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF
 BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2A) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2B) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2013-07-18 Cont ID  
Sent By eschneid Date 2013-07-18 Time 09:51 Rev Time 0.75
Received By eschneid Date 2013-07-17 Time 16:49 Sent To  
Notes
2013-07-18 10:23:55PASSED W/PROVISO
  
 1) PRIOR TO THE FINAL 104 INSPECTION/ISSUANCE OF A
 CERTIFICATE OF COMPLETION FOR THIS PERMIT, THE
 FOLLOWING INFORMATION SHALL BE SUBMITTED WITH A REVISED
 PERMIT APPLICATION:
  
 A. REVISED PLANS SHOWING THE FULL PEDESTRIAN ACCESS
 FROM LA FITNESS TO THE PARKING GARAGE, INCLUDING THE
 ACCESSIBLE ROUTE MEETING BUILDING DIVISION
 REQUIREMENTS.
 B. REVISED PLANS SHOWING THE PROPERTY LINES IN THE AREA
 OF WORK.
 C. A COPY OF A RECORDED CROSS ACCESS AGREEMENT/EASEMENT
 FOR THE PORTIONS OF THE ACCESS AND EGRESS ROUTES WHICH
 CROSS ONTO THE OFFICE TOWER PARCEL.
  
 2) SEPARATE PERMIT APPLICATIONS WILL BE REQUIRED FOR
 THE WORK ON THE OFFICE TOWER PARCEL, TO INCLUDE
 SIDEWALKS, NEW SCREEN FENCING, ETC. PLEASE NOTE THAT
 FENCES REQUIRE SEPARATE PERMITS AND ARE REQUIRED FOR
 SCREENING.
  
 3) REVISED PLANS SHOWING ALL THE WORK SHALL BE
 SUBMITTED TO THE ZONING DIVISION AS PART OF THE OPEN
 MINOR AMENDMENT APPLICATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-05-30 Cont ID  
Sent By eschneid Date 2013-05-30 Time 16:10 Rev Time 0.50
Received By eschneid Date 2013-05-30 Time 16:10 Sent To  
Notes
2013-05-30 16:10:24FAILED
  
 PLEASE PROVIDE RESPONSES TO THE COMMENTS IN WRITING.
  
 1) REPEAT COMMENT: THERE IS NEW EQUIPMENT BEING
 INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE
 DRI, PLEASE PROVIDE VERIFICATION THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PROVIDE VERIFICATION OF THE SCREENING. ADDING
 THE 7 FEET PLUS IN HEIGHT A/C AND CURB TO THE SECTION
 DRAWINGS DOES NOT SHOW THAT THE EQUIPMENT IS SCREENED
 FROM PUBLIC VIEW, SPECIFICALLY FROM THE OKEECHOBEE
 BOULEVARD RIGHT-OF-WAY.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By eschenid Date 2013-03-22 Time 14:50 Rev Time 0.50
Received By eschneid Date 2013-03-22 Time 14:50 Sent To  
Notes
2013-03-22 14:54:10FAILED
  
 PLEASE PROVIDE RESPONSES TO THE COMMENTS IN WRITING.
  
 1) THERE IS NEW EQUIPMENT BEING INSTALLED ON THE ROOF.
 IN ACCORDANCE WITH THE CITYPLACE DRI, PLEASE PROVIDE
 VERIFICATION THAT ALL ROOFTOP MECHANICAL EQUIPMENT,
 INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND
 PRIVATE UTILITY SERVICE CONNECTIONS; HEATING,
 VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PROVIDE
 VERIFICATION OF THE SCREENING.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-03-19 17:26:143-19-13