Plan Review Details - Permit 13030391
Plan Review Stops For Permit 13030391
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-20 Cont ID  
Sent By shill Date 2013-03-20 Time 09:25 Rev Time 0.00
Received By shill Date 2013-03-20 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-19 Cont ID  
Sent By shill Date 2013-03-19 Time 15:45 Rev Time 0.00
Received By shill Date 2013-03-19 Time 15:45 Sent To  
Notes
2013-03-19 15:52:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE ENGINEERING SUBMITTED VIA EMAIL IS FOR THE
 ASSEMBLY ON PAGE 34, BUT THE ASSEMBLY SUBMITTED IS ON
 PAGE 33. CONFIRM WHICH ASSEMBLY IS PROPOSED AND, IF YOU
 WISH TO USE THE ASSEMBLY ON PAGE 34, PLEASE SUBMIT. IF
 YOU WISH TO USE THE ASSEMBLY ON PAGE 33, PLEASE HAVE
 THE ENGINEERING REVISED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-15 Cont ID  
Sent By shill Date 2013-03-15 Time 17:20 Rev Time 0.00
Received By shill Date 2013-03-15 Time 17:20 Sent To  
Notes
2013-03-15 17:21:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE GENERAL LIMITATION #7 ON THE LAST PAGE OF THE
 FLAT ROOF PRODUCT APPROVAL. ENHANCED FASTENING TO BE
 SPECIFIED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT. FBC R 301.
  