Plan Review Details - Permit 13030378
Plan Review Stops For Permit 13030378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2013-04-19 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By jwitmer Date 2013-03-22 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2013-03-22 Time 10:46 Sent To  
Notes
2013-03-22 11:25:59BUILDING PLAN REVIEW
 PERMIT: 13030378
 ADD: 770 NORTHPOINT PKWY # 200
 CONT: LEIGHTON MCGINN
 TEL: (561)863-4455
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MARCH 22/ 2013
 ACTION: DENIED
  
 1) SHEET A-1.1 PLEASE SEE DOOR INTO EXAM ROOM # 2 ROOM
 # 239, THE DOOR DOES NOT HAVE THE REQUIRED 18" ON THE
 INTERIOR SWING SIDE OF THE DOOR. 2010 ACCESSIBILITY
 CODE
 SECTION 404.2.4 & TABLE 404.2.4.
  
 2) SHEET A-1.2 PLEASE SEE DOOR INTO EXAM ROOM # 9 ROOM
 # 274, THE DOOR DOES NOT HAVE THE REQUIRED 18" ON THE
 INTERIOR SWING SIDE OF THE DOOR. 2010 ACCESSIBILITY
 CODE
 SECTION 404.2.4 & TABLE 404.2.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By dharvey Date 2013-04-19 Time 11:36 Rev Time 0.00
Received By dharvey Date 2013-04-19 Time 11:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-15 Cont ID  
Sent By rlecky Date 2013-03-15 Time 12:40 Rev Time 0.00
Received By rlecky Date 2013-03-15 Time 12:08 Sent To  
Notes
2013-03-15 12:41:3013030378
 770 NORTH POINT PKWY #200
 MEDICAL OFFICE INTERIOR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By ddaniels Date 2013-04-19 Time 14:47 Rev Time 0.00
Received By ddaniels Date 2013-04-19 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-20 Cont ID  
Sent By wjolin Date 2013-03-20 Time 15:38 Rev Time 0.00
Received By wjolin Date 2013-03-20 Time 14:38 Sent To  
Notes
2013-03-20 15:38:03770 NORTHPOINT PARKWAY - SUITE #200
 PERMIT #13030378
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 SHEET A-1.-0: CORRIDOR #208 HAS A DOOR THAT WILL SWING
 AGAINST THE DIRECTION OF EGRESS NO MATTER WHICH WAY THE
 SWING IS ORIENTED. ALSO THIS DOOR IS EQUIPPED WITH A
 KEYPAD THAT WILL PREVENT OCCUPANTS FROM FREELY
 ACCESSING EXIT STAIR #210. DOORS SHALL BE ARRANGED TO
 BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE
 BUILDING IS OCCUPIED. LOCKS, IF PROVIDED, SHALL NOT
 REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR
 EFFORT FOR OPERATION FROM THE EGRESS SIDE.
  
 SHEET E4.1: NOTE #8 INDICATES A KEYPAD TO BE INSTALLED
 AT THE FLOOR EXTERIOR DOOR. HOW WILL THE ELECTRICAL BE
 ROUTED TO THIS DEVICE? NOTE: THE STAIRWELL CANNOT BE
 USED.
  
 NO FIRE ALARM DESIGN SHOW. PER FBC SECTION907.1.1,
 "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE
 FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2013-04-10 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 13:18 Rev Time 0.00
Received By hmoser Date 2013-03-14 Time 09:49 Sent To  
Notes
2013-03-14 09:51:40B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By hmoser Date 2013-04-19 Time 13:59 Rev Time 0.00
Received By hmoser Date 2013-04-19 Time 13:40 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 13:17 Rev Time 0.00
Received By hmoser Date 2013-03-28 Time 12:21 Sent To  
Notes
2013-03-28 13:17:48PLANS DENIED
 DUCT THAT PENETRATE ELECTRICAL ROOM
 # 225 REQUIRE FIRE DAMPERS. PER SECTION 607.5.1 FIRE
 WALLS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-18 Cont ID  
Sent By lwagner Date 2013-04-18 Time 13:09 Rev Time 0.00
Received By lwagner Date 2013-04-18 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-03-21 Cont ID  
Sent By lwagner Date 2013-03-21 Time 11:32 Rev Time 0.00
Received By lwagner Date 2013-03-21 Time 09:04 Sent To  
Notes
2013-03-21 11:32:26FBC 2010 PLUMBING REVIEW #1
  
 1. THE WATER CLOSETS IN ROOMS # 220, 223, 224, & 257
 ARE NOT VENTED PER P-909 WET VENTING.
 A. ROOM 257 & 220 THE SINKS ARE REQUIRED TO CONNECT
 DOWNSTREAM OF THE RESTROOM WET VENT.
 B. ROOM 224 THE WATER CLOSET IS NOT VENTED.
 C. ROOM 223 THE MOP SINK IS REQUIRED TO CONNECT
 DOWNSTREAM OF THE RESTROOM WET VENT.
  
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-03-14 Cont ID  
Sent By ajones Date 2013-03-14 Time 14:35 Rev Time 0.00
Received By ajones Date 2013-03-14 Time 14:35 Sent To  
Notes
***NONE***