Plan Review Details - Permit 13030376
Plan Review Stops For Permit 13030376
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-05-21 Cont ID  
Sent By JWITMER Date 2013-05-21 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2013-05-21 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-22 Cont ID  
Sent By jwitmer Date 2013-03-22 Time 12:23 Rev Time 0.00
Received By jwitmer Date 2013-03-22 Time 11:30 Sent To  
Notes
2013-03-22 12:23:52BUILDING PLAN REVIEW
 PERMIT: 13030376
 ADD: ONE HARVARD CIRCLE 2ND FLOOR EXPANSION
 CONT: SUFFOLK CONSTRUCTION
 TEL: (561)832-1616
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MARCH 22/ 2013
 ACTION: DENIED
  
 1A) SHEET A2.0 THE PLANS REFLECT A NEW LARGE TRAINING
 ROOM (1256 SQ. FT.) ROOM NUMBER 116. THERE ARE TWO CODE
 SECTIONS THAT PUT THIS ISZE TRAINING ROOM INTO THE
 OCCUPANCY TYPE A "A3" OCCUPANCY . THE 2010 FBC-B 303.1
 EXCEEPTION 1 & 3, SEE BELOW:
 EXCEPTION # 1 A BUILDING OR TENANT SPACE USED FOR
 ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50
 PERSONS SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.
 EXCEPTION # 3 A ROOM OR SPACE USED FOR ASSEMBLY
 PURPOSES THAT IS LESS THAN 750 SQUARE FEET (70 M2) IN
 AREA AND ACCESSORY TO ANOTHER OCCUPANCY SHALL BE
 CLASSIFIED AS A GROUP B OCCUPANCY OR AS PART OF THAT
 OCCUPANCY.
  
 1B) WITH THE TRAINING ROOM BEING AN A3 OCCUPANCY WITH
 THE BUILDING BEING EQUIPED WITH FIRE SPRINKLERS TABLE
 508.4 WILL REQUIRE THE SURROUNDING WALLS TO HAVE A 1
 HOUR OCCUPANCY SEPERATION IF THE DESIGNER WISHES TO USE
 SECTION 508.4 SEPERATED OCCUPANCIES IT IS NOT DECLARED.
  
 1C) THE DOORS AND WINDOWS WITHIN THE OCCUPANCY
 SEPERATION WALL WILL NEED TO COMPLY WITH OPENING
 PROTECTIVES TABLE 715.4.
  
 1D) THE DOORS THAT LEAD OUT OF THE LARGE TRAINING ROOM
 # 116, DOOR # D116A & D116B WILL NEED TO SWING IN THE
 OPPOSITE DIRECTION. 2010 FBC-B 1008.1.2. DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING
 AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A GROUP H
 OCCUPANCY.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-03-14 Cont ID  
Sent By ajones Date 2013-03-14 Time 14:27 Rev Time 0.00
Received By ajones Date 2013-03-14 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 16:01 Rev Time 0.00
Received By rlecky Date 2013-03-22 Time 15:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-18 Cont ID  
Sent By WJOLIN Date 2013-05-18 Time 17:04 Rev Time 0.00
Received By wjolin Date 2013-05-18 Time 16:39 Sent To  
Notes
2013-05-18 17:04:311 HARVARD CIRCLE - SECOND FLOOR
 PERMIT #13030376
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 RESPONSE: PER NFPA 101 SECTION 6.1.14.1.2, WHERE EXIT
 ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER OCCUPANCY,
 THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A MIXED
 OCCUPANCY. FOR MIXED USE OCCUPANCIES, THE MOST
 STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH
 OCCUPANCY SHALL APPLY. BECAUSE THE ASSEMBLY SPACES MUST
 USE THE BUSINESS OCCUPANCY EGRESS ROUTES AND ENTIRE
 TENANT SPACE HAS AN OCCUPANT LOAD EXCEEDING 100 PERSONS
 SO DOOR #100A AND #100B REQUIRE PANIC HARDWARE.
  
 ORIGINAL COMMENT: FOR ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-20 Cont ID  
Sent By wjolin Date 2013-03-20 Time 14:36 Rev Time 0.00
Received By wjolin Date 2013-03-20 Time 14:16 Sent To  
Notes
2013-03-20 14:36:171 HARVARD CIRCLE - SECOND FLOOR
 PERMIT #13030376
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE A BUSINESS OCCUPANCY ON THE COVER
 SHEET; HOWEVER, THE LARGE TRAINING ROOM #116 IS AN
 ASSEMBLY OCCUPANCY. PROVIDE OCCUPANT LOAD BREAKDOWNS
 FOR EACH AREA.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 THE DOORS IN THE LARGE TRAINING ROOM #116 ARE SWINGING
 AGAINST THE FLOW OF TRAFFIC. DOOR IS REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD
 OF 50 OR GREATER PERSONS PER SECTION 7.2.1.4.2 OF THE
 FLORIDA FIRE PREVENTION CODE: NFPA 101 - LIFE SAFETY
 CODE.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE
 MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 DOOR #111: SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA
 EDITION 2009 ALLOWS ACCESS CONTROLLED EGRESS DOORS
 PROVIDED THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE
 MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 INDICATE IF THE EXISTING STAIR LOCATED AT THE SOUTWEST
 CORNER OF THE SUITE IS AN EXIT STAIR OR JUST A
 MONUMENTAL STAIR. NO STAIRWELL ENTRY DOOR COULD BE
 LOCATED ON THE PLANS.
  
 NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-21 Cont ID  
Sent By jwitmer Date 2013-05-21 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2013-05-09 Time 10:56 Sent To  
Notes
2013-05-10 10:59:07B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 14:50 Rev Time 0.00
Received By hmoser Date 2013-03-14 Time 09:56 Sent To  
Notes
2013-03-14 09:56:32B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-21 Cont ID  
Sent By HMOSER Date 2013-05-21 Time 15:56 Rev Time 0.00
Received By jwitmer Date 2013-05-21 Time 15:56 Sent To  
Notes
2013-05-21 16:00:25MECHANICAL PROVISO:
 2010 FBC-ENERGY CONSERVATION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH DAMPERS
 THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES
 SERVED ARE NOT IN USE.
 VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF
 AUTOMATICALLY SHUTTING OFF
 DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND
 SETBACK, EXCEPT WHEN
 VENTILATION REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR
 WHEN VENTILATION MUST
 BE SUPPLIED TO MEET CODE REQUIREMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-28 Cont ID  
Sent By hmoser Date 2013-03-28 Time 14:50 Rev Time 0.00
Received By hmoser Date 2013-03-28 Time 14:33 Sent To  
Notes
2013-03-28 14:50:15PLANS DENIED
 SHOW ON THE PLANS THE SIZE AND LOCATION OF THE FRESH
 AIR DUCT
 GOING TO THE VAV BOX.PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 OFFICE 561-805-6732
 FAX 561-805-6676
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-21 Cont ID  
Sent By lwagner Date 2013-03-21 Time 09:03 Rev Time 0.00
Received By lwagner Date 2013-03-20 Time 15:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-03-19 Cont ID  
Sent By ajones Date 2013-03-19 Time 17:28 Rev Time 0.00
Received By ajones Date 2013-03-19 Time 17:28 Sent To  
Notes
***NONE***