Plan Review Details - Permit 13030309
Plan Review Stops For Permit 13030309
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 18:28 Rev Time 0.00
Received By shill Date 2013-03-18 Time 18:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By shill Date 2013-03-12 Time 18:49 Rev Time 0.00
Received By shill Date 2013-03-12 Time 18:49 Sent To  
Notes
2013-03-12 18:50:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC R 301, INDICATE WHICH APPROVED ASSEMBLY IS
 PROPOSED.
  
 2. SEE GENERAL LIMITATION #7, RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING TO BE DONE BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT (CONTRACTOR
 CANNOT USE LETTER WITH THIS PRODUCT APPROVAL).
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 18:28 Rev Time 0.00
Received By shill Date 2013-03-14 Time 10:50 Sent To  
Notes
2013-03-15 10:50:26GAVE TO SAMANTHA