Plan Review Details - Permit 13030120
Plan Review Stops For Permit 13030120
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-11 Cont ID  
Sent By wjolin Date 2013-03-11 Time 09:11 Rev Time 0.00
Received By wjolin Date 2013-03-07 Time 12:30 Sent To M
Notes
2013-03-11 09:11:552015 OKEECHOBEE BOULEVARD
 PERMIT #13030120
 MASTER #12120635
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THERE SHALL BE NO SHUTOFF VALVE DOWNSTREAM OF THE FIRE
 DEPARTMENT CONNECTION. CONNECT FDC ABOVE RISER
 BUTTERFLY VALVE OR ELIMINATE RISER CONTROL VALVE AND
 PROVIDE PERMANENT WEATHERPROOF SIGNAGE INDICATING THE
 BACKFLOW PREVENTER IS THE SHUTOFF FOR THE SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  