Plan Review Details - Permit 13030119
Plan Review Stops For Permit 13030119
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-04-01 Cont ID  
Sent By wjolin Date 2013-04-01 Time 10:56 Rev Time 0.00
Received By wjolin Date 2013-04-01 Time 10:22 Sent To M
Notes
2013-04-01 10:58:125720 PREMIER PARK DRIVE
 PERMIT #13030119
 MASTER #12120739
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VAULT ROOM WALLS SHALL BE FULL HEIGHT TO THE UNDERSIDE
 OF THE ROOF DECK TO CREATE NON-COMBUSTIBLE CONCEALED
 SPACE OTHERWISE SPRINKLER PROTECTION WILL BE NEEDED TO
 PROTECT/COOL THE ROOF STRUCTURE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-11 Cont ID  
Sent By wjolin Date 2013-03-11 Time 10:59 Rev Time 0.00
Received By wjolin Date 2013-03-11 Time 09:36 Sent To M
Notes
2013-03-11 10:59:415720 PREMIER PARK DRIVE
 PERMIT #13030119
 MASTER #12120739
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO PREACTION SYSTEM EQUIPMENT INFORMATION SUBMITTED AND
 NEITHER THE SPRINKLER SHOP DRAWINGS NOR FIRE ALARM SHOP
 DRAWINGS (PERMIT #13030226) SHOW THE DETECTION DEVICES
 TO BE USED WITH THE DOUBLE-INTERLOCK PREACTION SYSTEM
 PROTECTING THE VAULT AND SERVER ROOM.
  
 ESFR SPRINKLERS HAVE BEEN DELETED ABOVE THE NORTH
 PORTION OF OPEN AREA #112. THERE ALSO 5 BRANCHLINES
 THAT ARE NOT CONNECTED TO THE GRID SYSTEM AT EITHER THE
 NORTH OR SOUTH END.
  
 DESIGN AREA #4 INDICATES A REDUCED HYDRAULIC AREA FOR
 UTILIZING QUICK-RESPONSE SPRINKLERS; HOWEVER, THE 155F
 (TEMPERATURE) TYCO EC-8 RECESSED PENDENT SPRINKLER IS
 STANDARD RESPONSE ACCORDING TO TABLE B IN THE CUT
 SHEETS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM
 NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS
 PERMITTED IN THE LISTING DATA.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-01 Cont ID  
Sent By hmoser Date 2013-04-01 Time 14:20 Rev Time 0.00
Received By hmoser Date 2013-03-22 Time 17:37 Sent To  
Notes
2013-03-22 17:38:09TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-15 Cont ID  
Sent By shill Date 2013-03-15 Time 13:55 Rev Time 0.00
Received By shill Date 2013-03-05 Time 13:34 Sent To  
Notes
2013-03-05 13:34:16TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-01 Cont ID  
Sent By hmoser Date 2013-04-01 Time 14:19 Rev Time 0.00
Received By hmoser Date 2013-04-01 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-15 Cont ID  
Sent By hmoser Date 2013-03-15 Time 07:36 Rev Time 0.00
Received By hmoser Date 2013-03-15 Time 07:36 Sent To  
Notes
2013-03-15 13:55:30****CORRECTIONS****
  
 1. FBC 107.2.1.4 QUALITY OF BUILDING PLANS: BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. PLANS
 SUBMITTED ARE DIFFICULT TO READ.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  