Plan Review Details - Permit 13020828
Plan Review Stops For Permit 13020828
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 10:23 Rev Time 0.00
Received By jgomez Date 2013-05-16 Time 10:02 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By jgomez Date 2013-03-22 Time 14:15 Rev Time 0.00
Received By jgomez Date 2013-03-22 Time 12:37 Sent To  
Notes
2013-03-22 14:27:22RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- CURRENT BUILDING CODE IS 2010 FBC NOT 2007 FBC.
 REVISE ALL THE DESIGN CRITERIA AND ALL THE NOTES AND
 INFORMATION ON SHEET SP-1 TO REFLECT THE CURRENT CODES
 AND THE CURRENT CODE SECTIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 13:40 Rev Time 0.00
Received By dharvey Date 2013-07-05 Time 12:55 Sent To  
Notes
2013-07-05 13:40:51BY RL

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2013-05-16 Cont ID  
Sent By dharvey Date 2013-05-16 Time 11:36 Rev Time 0.00
Received By dharvey Date 2013-05-16 Time 11:36 Sent To  
Notes
2013-05-16 11:37:075-16-13
  
 ALL CORRECTIONS HAVE BEEN MADE....
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-18 Cont ID  
Sent By rlecky Date 2013-03-18 Time 16:22 Rev Time 0.00
Received By rlecky Date 2013-03-18 Time 16:00 Sent To  
Notes
2013-03-18 16:23:2613020828
 317 PALMETTO STREET
 INTERIOR REMODEL
  
 THE ELECTRICAL PLAN IS INSUFFICIENTLY DETAILED TO
 APPROVE. PLEASE PROVIDE THE FOLLOWING.
  
 SHOW SIZE AND LOCATION OF THE ELECTRICAL SERVICE AND
 PANEL. PROVIDE A PANEL SCHEDULE SHOWING NEW AND
 EXISTING LOADS. SHOW EXISTING AND NEW OUTLETS. NEC
 215.5
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 PROVIDE GFCI PROTECTED OUTLETS IN THE BATHROOMS. NEC
 210.52
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE IN
 FRONT AND AT THE BACK OF THE RESIDENCE. NEC 210.70
  
 ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
  
 SHOW KITCHEN CIRCUITS WITH GFCI PROTECTION NEC 210.8,
 210.52
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 PROVIDE ONE 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2)
  
 PROVIDE A MINIMUM OF TWO 20 AMP KITCHEN CIRCUITS. NEC
 210.11 (C)(1)
  
 PROVIDE A BRANCH CIRCUIT TO THE BATHROOMS. NEC 210.11
 (C)(3)
  
 PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC
 SERVICE. NEC 250.94
  
 AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70
  
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A) (2)
  
 ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE
 MORE THAN 2 FEET IN WIDTH. NEC 10.52 (A) (2)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By rmcdouga Date 2013-07-10 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2013-07-10 Time 10:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2013-05-10 Cont ID  
Sent By rmcdouga Date 2013-05-10 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2013-05-10 Time 16:09 Sent To  
Notes
2013-05-10 16:39:222010 FBC
  
 DENIED
  
 1) THE PLANS SPECIFY THE LONGEST LENGTH AS 80 FEET WITH
 A TOTAL DEMAND OF 320,000 BTUS AND 3/4" DIAMETER
 SCHEDULE 40 PIPE METALLIC PIPE. FBC FUEL GAS TABLE
 402.4(2) FOR 12" WC AND 0.5" PRESSURE DROP SHOWS THAT
 80 FEET OF 3/4" PIPE HAS A CAPACITY OF 117,000 BTU
 WHICH IS NOT ENOUGH. PLEASE REVISE THE GAS PLAN.
  
 2) THE GAS ISOMETRIC DRAWING APPEARS TO SHOW A 1/2"
 PIPE COMING FROM THE GAS METER AND THEN CHANGING TO
 3/4" PIPE. SEE GAS PIPE SIZING TABLE 402.4(2).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By rmcdouga Date 2013-03-22 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2013-03-22 Time 15:04 Sent To  
Notes
2013-03-22 16:46:522010 FBC
  
 FUEL GAS DENIED
  
 1) THE GAS INPUT IN BTUS SHOWN ON THE GAS PLAN ARE
 INCORRECT. THE SPECIFICATIONS THAT WERE SUBMITTED FOR
 THE TANKLESS WATER-HEATER REQUIRES A GAS INPUT OF
 180,000 BTUS. ACCORDING TO FBCR TABLE G2413.2 (402),
 THE RANGE IS 65,000 BTUS, THE CLOTHES DRYER IS 35,000
 BTUS AND THE TOTAL BTUS SHOULD BE 320,000 BTUS. PLEASE
 CORRECT.
  
 2) THE 1/2" PIPE SIZE IS TOO SMALL FOR THE GAS LOAD FOR
 SCHEDULE 40 METALLIC PIPE WITH A 11" W.C. AND 0.5 P.D.
 AND A LENGTH OF 80'. SEE TABLE G2413.4(1) [402.4(2)]
 AND G2413.4.1 (402.4.1).
  
 3) UPDATE THE REFERENCED CODE TO THE 2010 FUEL GAS
 CODE. FBCR CHAPTER 43
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By rmcdouga Date 2013-07-10 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2013-06-06 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 14:21 Rev Time 0.00
Received By jgomez Date 2013-05-09 Time 11:22 Sent To  
Notes
2013-05-10 11:23:15SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-22 Cont ID  
Sent By rmcdouga Date 2013-03-22 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2013-02-28 Time 16:58 Sent To  
Notes
2013-02-28 16:58:20R--8

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By rmcdouga Date 2013-07-10 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2013-07-10 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-10 Cont ID  
Sent By rmcdouga Date 2013-05-10 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2013-05-10 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-18 Cont ID  
Sent By hmoser Date 2013-03-18 Time 09:27 Rev Time 0.00
Received By hmoser Date 2013-03-18 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By rmcdouga Date 2013-07-10 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2013-07-10 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-10 Cont ID  
Sent By rmcdouga Date 2013-05-10 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2013-05-10 Time 16:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-22 Cont ID  
Sent By rmcdouga Date 2013-03-22 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2013-03-22 Time 15:04 Sent To  
Notes
***NONE***