Plan Review Stops For Permit 13020828 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-05-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-16 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-16 |
Time |
10:02 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-03-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-03-22 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-03-22 |
Time |
12:37 |
Sent To |
|
|
Notes |
2013-03-22 14:27:22 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC | | | | 1- CURRENT BUILDING CODE IS 2010 FBC NOT 2007 FBC. | | REVISE ALL THE DESIGN CRITERIA AND ALL THE NOTES AND | | INFORMATION ON SHEET SP-1 TO REFLECT THE CURRENT CODES | | AND THE CURRENT CODE SECTIONS. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2013-07-05 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-05 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-05 |
Time |
12:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2013-05-16 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-16 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-16 |
Time |
11:36 |
Sent To |
|
|
Notes |
2013-05-16 11:37:07 | 5-16-13 | | | | ALL CORRECTIONS HAVE BEEN MADE.... | | VB |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-03-18 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-03-18 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-03-18 |
Time |
16:00 |
Sent To |
|
|
Notes |
2013-03-18 16:23:26 | 13020828 | | 317 PALMETTO STREET | | INTERIOR REMODEL | | | | THE ELECTRICAL PLAN IS INSUFFICIENTLY DETAILED TO | | APPROVE. PLEASE PROVIDE THE FOLLOWING. | | | | SHOW SIZE AND LOCATION OF THE ELECTRICAL SERVICE AND | | PANEL. PROVIDE A PANEL SCHEDULE SHOWING NEW AND | | EXISTING LOADS. SHOW EXISTING AND NEW OUTLETS. NEC | | 215.5 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | PROVIDE GFCI PROTECTED OUTLETS IN THE BATHROOMS. NEC | | 210.52 | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE IN | | FRONT AND AT THE BACK OF THE RESIDENCE. NEC 210.70 | | | | ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | 210.12 | | | | SHOW KITCHEN CIRCUITS WITH GFCI PROTECTION NEC 210.8, | | 210.52 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | PROVIDE ONE 20 AMP LAUNDRY CIRCUIT. NEC 210.11 (C) (2) | | | | PROVIDE A MINIMUM OF TWO 20 AMP KITCHEN CIRCUITS. NEC | | 210.11 (C)(1) | | | | PROVIDE A BRANCH CIRCUIT TO THE BATHROOMS. NEC 210.11 | | (C)(3) | | | | PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC | | SERVICE. NEC 250.94 | | | | AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET | | SHALL BE INSTALLED IN EVERY HABITABLE ROOM. NEC 210.70 | | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | RECEPTACLE OUTLET. NEC 210.52 (A) (2) | | | | ADDITIONAL RECEPTACLES ARE REQUIRED FOR ANY WALL SPACE | | MORE THAN 2 FEET IN WIDTH. NEC 10.52 (A) (2) | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2013-05-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:09 |
Sent To |
|
|
Notes |
2013-05-10 16:39:22 | 2010 FBC | | | | DENIED | | | | 1) THE PLANS SPECIFY THE LONGEST LENGTH AS 80 FEET WITH | | A TOTAL DEMAND OF 320,000 BTUS AND 3/4" DIAMETER | | SCHEDULE 40 PIPE METALLIC PIPE. FBC FUEL GAS TABLE | | 402.4(2) FOR 12" WC AND 0.5" PRESSURE DROP SHOWS THAT | | 80 FEET OF 3/4" PIPE HAS A CAPACITY OF 117,000 BTU | | WHICH IS NOT ENOUGH. PLEASE REVISE THE GAS PLAN. | | | | 2) THE GAS ISOMETRIC DRAWING APPEARS TO SHOW A 1/2" | | PIPE COMING FROM THE GAS METER AND THEN CHANGING TO | | 3/4" PIPE. SEE GAS PIPE SIZING TABLE 402.4(2). | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2013-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-03-22 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-03-22 |
Time |
15:04 |
Sent To |
|
|
Notes |
2013-03-22 16:46:52 | 2010 FBC | | | | FUEL GAS DENIED | | | | 1) THE GAS INPUT IN BTUS SHOWN ON THE GAS PLAN ARE | | INCORRECT. THE SPECIFICATIONS THAT WERE SUBMITTED FOR | | THE TANKLESS WATER-HEATER REQUIRES A GAS INPUT OF | | 180,000 BTUS. ACCORDING TO FBCR TABLE G2413.2 (402), | | THE RANGE IS 65,000 BTUS, THE CLOTHES DRYER IS 35,000 | | BTUS AND THE TOTAL BTUS SHOULD BE 320,000 BTUS. PLEASE | | CORRECT. | | | | 2) THE 1/2" PIPE SIZE IS TOO SMALL FOR THE GAS LOAD FOR | | SCHEDULE 40 METALLIC PIPE WITH A 11" W.C. AND 0.5 P.D. | | AND A LENGTH OF 80'. SEE TABLE G2413.4(1) [402.4(2)] | | AND G2413.4.1 (402.4.1). | | | | 3) UPDATE THE REFERENCED CODE TO THE 2010 FUEL GAS | | CODE. FBCR CHAPTER 43 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
09:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-05-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-16 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-09 |
Time |
11:22 |
Sent To |
|
|
Notes |
2013-05-10 11:23:15 | SENT TO J GOMEZ |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-03-22 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-02-28 |
Time |
16:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2013-05-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2013-03-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-03-18 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-03-18 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-07-10 |
Time |
10:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2013-05-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-05-10 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2013-03-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-03-22 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-03-22 |
Time |
15:04 |
Sent To |
|
|
Notes |
|
|