2013-02-27 15:10:15 | 4855 FRED GLADSTONE DRIVE |
| PERMIT #13020714 |
| MASTER #12030044 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ADDRESS: THE ADDRESS PROVIDED ON THE PLANS (4847) DOES |
| NOT MATCH THE ADDRESS (4855) PROVIDED ON THE PERMIT |
| APPLICATION. |
| |
| GENERAL: ON CONSTRUCTION DOCUMENT SHEET FP000, THE |
| ENGINEER OF RECORD (NELSON LONG, P.E.) INDICATES A |
| REMOTE AREA OF 1,500 SQ.FT. SHALL BE HYDRAULICALLY |
| CALCULATED FOR LIGHT HAZARD AREAS. ENGINEER IS TO |
| PROVIDE A SIGNED/SEALED LETTER OR REVISED DRAWING |
| INDICATING THAT THE SPRINKLER CONTRACTOR'S PROPOSED |
| ROOM DESIGN METHOD SHOWN AND CALCULATED ON THE |
| SPRINKLER SHOP DRAWINGS IS ACCEPTABLE. TO UTILIZE THE |
| ROOM DESIGN METHOD, ALL ROOMS SHALL BE ENCLOSED WITH |
| WALLS HAVING A FIRE RESISTANCE RATING OF 30 |
| MINUTES..THIS NEEDS TO BE INDICATED ON THE PLANS. FOR |
| AREAS NOT ENCLOSED BY WALLS WITH A FIRE RESISTANCE |
| RATING SUCH AS THE RESIDENTS DIETARY AND DINING AREA |
| NEED TO BE SUPPORTED BY HYDRAULIC CALCULATIONS. |
| |
| GENERAL: (SEE ARCHITECTURAL SHEETS A401 & A402 FOR |
| REFERENCE)THE OVERHEAD LIFT TRACK SYSTEM APPEARS TO BE |
| A SOLID OBSTRUCTION APPROXIMATELY 6"-8" IN DEPTH IN ALL |
| LIVING UNIT TYPES A THROUGH D. LIVING UNIT TYPE E HAS |
| THIS SAME TRACK WHICH APPEARS TO EXTEND INTO THE |
| SHOWER. THIS TRACK APPEARS TO RESULT IN SPRINKLER SPRAY |
| OBSTRUCTIONS. PLEASE EXPLAIN. |
| |
| GENERAL: IT IS UNCLEAR FROM THE PLANS AND SPRINKLER |
| SCHEDULE IF RESIDENTIAL STYLE SPRINKLERS ARE TO BE |
| INSTALLED IN ALL LIVING UNITS ON ALL THREE FLOORS. |
| NOTE: RESIDENTIAL SPRINKLERS WERE NOT HYDRAULICALLY |
| CALCULATED. |
| |
| GENERAL: FOR SYSTEM PRESSURES EXCEEDING 100 PSI, |
| ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS |
| SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL |
| BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE |
| THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING |
| UPWARD MOVEMENT. |
| |
| SHEET FP101: THE RESIDENTIAL STYLE SPRINKLERS WITH A |
| K-FACTOR OF 4.3 COULD NOT BE LOCATED IN ANY OF THE |
| SLEEPING ROOMS. THE PLANS INDICATE A SPRINKLER COUNT OF |
| 84. |
| |
| SHEET FP101: FLEXIBLE DINING ROOM #129 HAS SPRINKLERS |
| LOCATED IN THE 8'-6" CEILING; HOWEVER, THE SPRAY WILL |
| BE OBSTRUCTED BY THE PERIMETER SOFFIT LOCATED AT 8'-3" |
| AFF. |
| |
| SHEET FP101B: THE PRODUCT DATA INDICATES THAT CPVC |
| PIPING WILL BE USED FOR PIPING 2" AND SMALLER; HOWEVER, |
| THE HYDRAULIC CALCULATIONS CORRESPONDING TO THIS SHEET |
| INDICATE A C-FACTOR OF 150 FOR SOME SECTIONS OF 3" |
| PIPING. |
| |
| SHEET FP102: THE SIDEWALL SPRINKLERS PROTECTING THE |
| LIVING UNITS ON THE FIRST FLOOR ARE INDICATED AS |
| RESIDENTIAL SIDEWALL SPRINKLERS (K=4.4); HOWEVER, |
| REGULAR (K=5.6) SIDEWALL SPRINKLERS ARE USED IN THE |
| SECOND AND THIRD FLOOR LIVING UNITS. PLEASE EXPLAIN. |
| |
| SHEET FP102: FLEXIBLE DINING ROOM #229 HAS SPRINKLERS |
| LOCATED IN THE 8'-6" CEILING; HOWEVER, THE SPRAY WILL |
| BE OBSTRUCTED BY THE PERIMETER SOFFIT LOCATED AT 8'-3" |
| AFF. |
| |
| SHEET FP102: SPRINKLER COVERAGE IS ABSENT FROM THE |
| SOUTHWEST CORNER OF CENTRAL STORAGE ROOM #276. |
| |
| SHEET FP103: (SEE ARCHITECTURAL SHEET A153, A401 AND |
| SHEET A591 - DETAIL 16 FOR REFERENCE) INDICATE THE |
| CURRENT CEILING AND SOFFIT ELEVATIONS FOR THE LIVING |
| UNITS AS THE SPRINKLER SHOP DRAWINGS SEEM TO CONFLICT |
| WITH THE ARCHITECTURAL CEILING HEIGHTS. PER NPFA 13, |
| THE MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE THE |
| BOTTOM OF THE OBSTRUCTION IS 14-INCHES FOR STANDARD |
| SPRAY SIDEWALL SPRINKLERS (TABLE 8.7.5.1.3 - NFPA 13, |
| 2010 ED). |
| (NOTE: A RESIDENTIAL SIDEWALL SPRINKLER CANNOT BE USED |
| DUE TO THE CEILING/SOFFIT HEIGHT DIFFERENCES PER NFPA |
| 13). |
| |
| SHEET FP103: FLEXIBLE DINING ROOM #329 HAS SPRINKLERS |
| LOCATED IN THE 8'-6" CEILING; HOWEVER, THE SPRAY WILL |
| BE OBSTRUCTED BY THE PERIMETER SOFFIT LOCATED AT 8'-3" |
| AFF. |
| |
| SHEET FP103: PROVIDE SPRINKLER PROTECTION AT THE TOP OF |
| STAIR #2 AND #3. |
| |
| SHEET FP104: PROVIDE CONTROL VALVES, FLOW SWITCHES AND |
| INSPECTOR'S TEST CONNECTIONS FOR THE SPRINKLERS |
| PROTECTING ROOF AIR HANDLER ROOMS SO A SPRINKLER ALARM |
| IN THESE AREAS IS NOT MISTAKEN AS A THIRD FLOOR ALARM. |
| |
| SHEET FP104: THE RISER AND CROSS MAIN ARE INDICATED AS |
| 3" ON THE PLANS; HOWEVER, THE CROSS MAIN ON THE FLOOR |
| BELOW (SHEET FP103) INDICATES THIS MAIN TO BE 2-1/2". |
| |
| SHEET FP104: THE PLANS INDICATE 1-1/2" BRANCH LINES. |
| THE PLAN REVIEWER WOULD ASSUME THE SPRIG UP OR DROP |
| DOWN IS TO BE 1"; HOWEVER, THE HYDRAULIC CALCULATIONS |
| INDICATE THE USE OF BOTH 1" RUNOUTS/ARMOVERS AND 1-1/4" |
| RUNOUTS/ARMOVERS. CLARIFY ON THE PLANS WHAT IS TO BE |
| INSTALLED. |
| |