Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-04-22 Cont ID  
Sent By wjolin Date 2013-04-22 Time 12:52 Rev Time 0.00
Received By wjolin Date 2013-04-22 Time 12:48 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-26 Cont ID  
Sent By wjolin Date 2013-02-26 Time 15:48 Rev Time 0.00
Received By wjolin Date 2013-02-26 Time 15:33 Sent To M
Notes
2013-02-26 15:47:18425 24TH STREET
 PERMIT #13020649
 MASTER #12030294
 REVIEW COMMENTS - FIRE DEPARTMENT
 **RENEWAL OF EXPIRED SPRINKLER PERMIT**
  
 PROVIDE AN UPDATED FLOOR/CEILING PLAN TO MATCH THE
 CURRENT ARCHITECTURAL DESIGN.
  
 INDICATE THE EDITION OF NFPA 13 THAT THESE PLANS ARE IN
 COMPLIANCE WITH.
  
 CONFIRM NEW FIRE DEPARTMENT CONNECTION IS LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT.
  
 NO HAZARD INFORMATION (LIGHT, ORDINARY, ETC.) PROVIDED
 ON THE PLANS.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF
 DECK (IF OBSTRUCTED CONSTRUCTION).
  
 NEW SPRINKLERS INSTALLED SHOULD BE QUICK-RESPONSE
 UNLESS THERE IS JUSTIFICATION TO INSTALL STANDARD
 RESPONSE SPRINKLERS.
  
 THE PLAN INDICATES AN INACCURATE SCALE OF 1/8"=1'-0".
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-30 Cont ID  
Sent By hmoser Date 2013-04-30 Time 09:46 Rev Time 0.00
Received By hmoser Date 2013-04-17 Time 07:52 Sent To  
Notes
2013-04-17 07:52:38TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-05 Cont ID  
Sent By hmoser Date 2013-03-05 Time 10:14 Rev Time 0.00
Received By hmoser Date 2013-03-05 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-30 Cont ID  
Sent By hmoser Date 2013-04-30 Time 09:46 Rev Time 0.00
Received By hmoser Date 2013-04-30 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-05 Cont ID  
Sent By hmoser Date 2013-03-05 Time 10:14 Rev Time 0.00
Received By hmoser Date 2013-03-05 Time 10:08 Sent To  
Notes
2013-03-05 10:14:16PLANS DENIED
 CAN NOT READ SOME OF THE PIPE SIZE
 AND THE ARMOVERS DO NOT HAVE SIZE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  