Plan Review Details - Permit 13020649
Plan Review Stops For Permit 13020649 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2013-04-22 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-04-22 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-04-22 |
Time |
12:48 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2013-02-26 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-02-26 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-02-26 |
Time |
15:33 |
Sent To |
M |
|
Notes |
2013-02-26 15:47:18 | 425 24TH STREET | | PERMIT #13020649 | | MASTER #12030294 | | REVIEW COMMENTS - FIRE DEPARTMENT | | **RENEWAL OF EXPIRED SPRINKLER PERMIT** | | | | PROVIDE AN UPDATED FLOOR/CEILING PLAN TO MATCH THE | | CURRENT ARCHITECTURAL DESIGN. | | | | INDICATE THE EDITION OF NFPA 13 THAT THESE PLANS ARE IN | | COMPLIANCE WITH. | | | | CONFIRM NEW FIRE DEPARTMENT CONNECTION IS LOCATED | | WITHIN 150 FEET OF A FIRE HYDRANT. | | | | NO HAZARD INFORMATION (LIGHT, ORDINARY, ETC.) PROVIDED | | ON THE PLANS. | | | | FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) | | INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR | | UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM | | SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF | | DECK (IF OBSTRUCTED CONSTRUCTION). | | | | NEW SPRINKLERS INSTALLED SHOULD BE QUICK-RESPONSE | | UNLESS THERE IS JUSTIFICATION TO INSTALL STANDARD | | RESPONSE SPRINKLERS. | | | | THE PLAN INDICATES AN INACCURATE SCALE OF 1/8"=1'-0". | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-04-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-04-30 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-04-17 |
Time |
07:52 |
Sent To |
|
|
Notes |
2013-04-17 07:52:38 | TO FIRE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-03-05 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-03-05 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-03-05 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2013-04-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-04-30 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-04-30 |
Time |
09:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2013-03-05 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-03-05 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-03-05 |
Time |
10:08 |
Sent To |
|
|
Notes |
2013-03-05 10:14:16 | PLANS DENIED | | CAN NOT READ SOME OF THE PIPE SIZE | | AND THE ARMOVERS DO NOT HAVE SIZE | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | |
|
|
|