Plan Review Details - Permit 13020613
Plan Review Stops For Permit 13020613
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 12:38 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-05-20 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2013-05-20 Time 07:02 Sent To  
Notes
2013-05-20 07:39:28BUILDING PLAN REVIEW
 PERMIT: 13020613
 ADD: 6300 S DIXIE HWY
 CONT: ATLANTIDA
 TEL: (561)313-8126
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: 04/20/2013
 ACTION: DENIED
  
 ***** NOTE*****FLORIDA STATUTE 553.80(2)(B)
 DESIGN PROFESSIONAL DOCUMENTS.
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY,LIGHTING, VENTILATION, MECHANICAL,
 PLUMBING, AND GAS SYSTEMS, OR OTHER REQUIREMENTS
 IDENTIFIED BY RULE OF THE FLORIDA BUILDING COMMISSION
 ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL GOVERNMENT
 SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH REVIEW THE
 PLANS ARE REJECTED FOR THAT CODE VIOLATION A FEE OF
 FOUR TIMES THE AMOUNT OF THE PORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLAN REVIEW.
  
 1-2) COMPLIED.
  
  
 3) 3RD REQUEST, SEMI-COMPLIED. SHEET A-1 NOTE # 4
 INDICATES A BUSINESS OCCUPANCY AND THE REFERENECE TO
 CODE SECTION 306 WHICH IS FACTORY? THEN UNDER THE
 HEADING NOTES OCCUPANCY TYPE ; ASSEMBLY, THIS IS A YOGA
 STUDIO, THIS TRUELY APPEARS TO BE A EXERCISE ROOM
 WITHOUT EQUIPMENT AND THE 15 SQ FT PER PERSON SHOULD BE
 USED PROVIDE WHAT AREA WILL BE USED FOR YOGA PROVIDE
 THE SQ FT PER AREA AND OCCUPANT LOADS FOR EACH AREA.
 THE YOGA AREA AREA IS 490 SQ FT / 15 SQ FT PER OCCUPANT
 = 33 OCCUPANTS. . PLEASE PROVIDE WHAT METHOD YOU USED
 TO PROVIDE AN OCCUPANT LOAD OF 15. 2010 FBC-B TABLE
 1004.1.1. THE BUILDING OFFICIAL AND FIRE MARSHALL BOTH
 AGREE THAT YOGA MATS DO NOT CONSTITUTE GYM EQUIPMENT
 AND THE 50 SQ FT CAN NOT BE TAKEN FOR ALLOWABLE SQUARE
 FEET PER OCCUPANT FOR GYM EQUIPMENT.
  
 4)3RD REQUEST. SHEET 1-A UNDER NOTES CLASSIFIES THIS
 BUILDING AS A TYPE 5 BUILDING. UNDER THE 2010 FBC-B
 TABLE 503.1 & TABLE 601 THE TABLES LIST 5A OR 5B.
  
 5-7) COMPLIED.
 NEW COMMENTS:
  
 8)COMPLIED.
  
 9) 2ND REQUEST. THE PLANS ALSO SHOW FOR THE SECOND TIME
 A EXIT FROM THE SECOND STORY BUT THE DETAIL A -A-1
 INDICATES A ROOF ABOVE, PLEASE CLARIFY WHAT TYPE
 CONDITION IS LOCATED ABOVE THIS UNIT? IS THERE ANOTHER
 OCCUPANCY TYPE ABOVE AND HOW ARE YOU OBTAINING
 OCCUPANCY SEPERATION FROM THE UNIT ABOVE? 2010 FBC-B
 TABLE 508.4.
  
 10) 2ND REQUEST. SHEET A1 WITH THE STAIRWELL FROM THE
 SECOND FLOOR, IT APPEARS THAT YOU CAN ENTER THE TENANT
 SPACE THROUGH A BUILDING UTILITY CLOSET, WHERE IS THE
 TENANT SEPERATION LINE, AND WHY CAN YOU ENTER THE
 UTILITY CLOSET FROM THE VERTICAL EXIT. THE 2010 FBC-B
 1022.4 OPENINGS THROUGH AN EXIT ENCLOSURE ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS.1022.3
 OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED
 EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY
 FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED
 SPACES AND FOR EGRESS FROM THE ENCLOSURE.
  
 11)2ND REQUEST. BOTH THE NEW A1 SHEET AS WELL AS THE LS
 SHEET INDICATE A WATER HEATER IN THE VERTICAL EXIT
 ENCLOSURE. 2010 FBC-B 1022.4 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-04 Cont ID  
Sent By jwitmer Date 2013-04-04 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2013-04-04 Time 07:32 Sent To  
Notes
2013-04-04 08:35:31BUILDING PLAN REVIEW
 PERMIT: 13020613
 ADD: 6300 S DIXIE HWY
 CONT: ATLANTIDA
 TEL: (561)313-8126
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 04/04/2013
 ACTION: DENIED
  
 1-2) COMPLIED.
  
  
 3) 2ND REQUEST, SEMI-COMPLIED. SHEET A-1 NOTE # 4
 INDICATES A BUSINESS OCCUPANCY AND THE REFERENECE TO
 CODE SECTION 306 WHICH IS FACTORY? THEN UNDER THE
 HEADING NOTES OCCUPANCY TYPE ; ASSEMBLY, THIS IS A YOGA
 STUDIO, THIS TRUELY APPEARS TO BE A EXERCISE ROOM
 WITHOUT EQUIPMENT AND THE 15 SQ FT PER PERSON SHOULD BE
 USED PROVIDE WHAT AREA WILL BE USED FOR YOGA PROVIDE
 THE SQ FT PER AREA AND OCCUPANT LOADS FOR EACH AREA.
 THE YOGA AREA AREA IS 490 SQ FT / 15 SQ FT PER OCCUPANT
 = 33 OCCUPANTS. IF YOU LOOK AT THE SAME AREA 490 SQ FT
 WITH THE MATS BEING EQUIPMENT, 490/15= 10 OCCUPANTS.
 PLEASE PROVIDE WHAT METHOD YOU USED TO PROVIDE AN
 OCCUPANT LOAD OF 15. 2010 FBC-B TABLE 1004.1.1.
  
 4)2ND SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS
 A TYPE 5 BUILDING. UNDER THE 2010 FBC-B TABLE 503.1 &
 TABLE 601 THE TABLES LIST 5A OR 5B.
  
 5-7) COMPLIED.
 NEW COMMENTS:
  
 8) THE NEW SET OF PLANS HAVE ELIMINATED THE FRONT
 DOORS, ON THE A-1 SHEET BUT STILL SHOW THEM ON THE LIFE
 SAFETY PLAN, IS THIS AN OVER SITE, ARE THE DOORS TILL
 THERE? EXIT DISCHARGE 1027.
  
 9) THE PLANS ALSO SHOW FOR THE FIRST TIME A EXIT FROM
 THE SECOND STORY BUT THE DETAIL A A-1 INDICATES A ROOF
 ABOVE, PLEASE CLARIFY WHAT TYPE CONDITION IS LOCATED
 ABOVE THIS UNIT? IS THERE ANOTHER OCCUPANCY TYPE ABOVE
 AND HOW ARE YOU OBTAINING OCCUPANCY SEPERATION FROM THE
 UNIT ABOVE? 2010 FBC-B TABLE 508.4.
  
 10) SHEET A1 WITH THE STAIRWELL FROM THE SECOND FLOOR,
 IT APPEARS THAT YOU CAN ENTER THE TENANT SPACE THROUGH
 A BUILDING UTILITY CLOSET, WHERE IS THE TENANT
 SEPERATION LINE, AND WHY CAN YOU ENTER THE UTILITY
 CLOSET FROM THE VERTICAL EXIT. THE 2010 FBC-B 1022.4
 OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS.1022.3 OPENINGS IN EXIT
 ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO
 THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 11) BOTH THE NEW A1 SHEET AS WELL AS THE LS SHEET
 INDICATE A WATER HEATER IN THE VERTICAL EXIT ENCLOSURE.
 2010 FBC-B 1022.4 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-01 Cont ID  
Sent By jwitmer Date 2013-03-01 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2013-02-28 Time 16:45 Sent To  
Notes
2013-03-01 09:41:48BUILDING PLAN REVIEW
 PERMIT: 13020613
 ADD: 6300 S DIXIE HWY
 CONT: ATLANTIDA
 TEL: (561)313-8126
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 03/01/2013
 ACTION: DENIED
  
 1) SHEET A1 NOTE # 2, UNDER THE HEADING INDICATES THE
 USE OF TABLE 302.1.1AND 2 HOUR FIRE WALL RATINGS, IN
 THE 2010 FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE
 PLANS TO THE 2010 FBC-B. FIRE WALLS IS THE WRONG
 TERM,THEY ARE WALLS THAT SPLIT BUILDINGS INTO 2
 BUILDINGS BECAUSE OF BEING TO LARGE FOR THE BUILDING
 TYPE DECLARED SEE 706. THE WALLS ARE TENAN SEPERATION
 WALLS ( FIRE PARTITIONS 709) OR OCCUPANCY SEPERATION
 WALLS.
  
 2) SHEET A-1 NOTE # 3 UNDER THE HEADING INDICATES THE
 USE OF TABLE 302.1.1 AND 1 HOUR FIRE WALLS, IN THE 2010
 FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE PLANS TO THE
 2010 FBC-B.
  
 3) SHEET A-1 NOTE # 4 INDICATES A BUSINESS OCCUPANCY
 AND THE REFERENECE TO CODE SECTION 306 WHICH IS
 FACTORY? THEN UNDER THE HEADING NOTES OCCUPANCY TYPE ;
 MERCANTILE, THIS IS A YOGA SSTUDIO, PROVIDE THE AREA ON
 THE PLAN WHERE THE MERCANTILE AREA IS LOCATED. THIS
 TRUELY APPEARS TO BE A EXERCISE ROOM WITHOUT EQUIPMENT
 AND THE 15 SQ FT PER PERSON SHOULD BE USED PROVIDE WHAT
 AREA WILL BE USED FOR YOGA AND WHAT AREA WILL BE USED
 AS MERCANTILE FOR THE SALE OF GOODS, PROVIDE THE SQ FT
 PER AREA AND OCCUPANT LOADS FOR EACH AREA. DEPENDING ON
 THE SQ FOOTAGE THIS MAY BE A MIXED USE WILL THERE BE
 SEPERATION BETWEEN OCCUPANCIES OR NON SEPERATED USE OR
 ACCESSORY OCCUPANCIE? 508.4, 508.3 OR 508.2.
  
 4) SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS A
 TYPE III BUILDING UNDER THE 2001 AND EARLIER CODE A
 TYPE III BUILDING IDENTIFICATION WAS USED FOR A HEAVY
 TIMBER BUILDING, PLEASE USE THE NOMENCLATURE UNDER THE
 2010 FBC-B TABLE 503.1 & TABLE 601.
  
 5) THE WIND DESIGN CRITERIA IS NOT STATED TO THE 2010
 FBC-B AND WIND CRITERIA FOR A CATEGORY II BUILDING V
 ULT 170 MPH, 3 SECOND GUST
  
 6) UNDER THE WIND DESIGN CRITERIA THE EXPOSURE IS
 LISTED AS "M" ? 2010 FBC-B 1609. 4.2 SURFACE ROUGHNESS
 "C".
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-21 Cont ID  
Sent By dharvey Date 2013-06-21 Time 10:56 Rev Time 0.00
Received By dharvey Date 2013-06-21 Time 10:38 Sent To  
Notes
2013-06-21 10:56:42BY RL
2013-06-17 14:32:29NEW SHEETS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-02-25 Cont ID  
Sent By rlecky Date 2013-02-25 Time 15:59 Rev Time 0.00
Received By rlecky Date 2013-02-25 Time 15:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-06-14 Cont ID  
Sent By lphilmor Date 2013-06-14 Time 14:37 Rev Time 0.00
Received By lphilmor Date 2013-06-14 Time 14:08 Sent To  
Notes
2013-06-14 14:35:396300 S DIXIE HWY, SUITE 102
 PERMIT # 13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 1. PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 2.EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-05-20 Cont ID  
Sent By wjolin Date 2013-05-20 Time 09:55 Rev Time 0.00
Received By wjolin Date 2013-05-20 Time 09:45 Sent To P
Notes
2013-05-20 09:55:136300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT (X2): PROVIDE TACTILE SIGNAGE AT ALL
 REQUIRED EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT (X2): DOORS SERVING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS SHALL SWING IN THE DIRECTION OF
 EGRESS.
  
 REPEAT COMMENT (X1): SHEET A-1 INDICATES AN EXERCISE
 AREA OF 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT
 INDICATES AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.).
 USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON
 (EXERCISE ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA
 101) RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS.THE FIRE
 CODE DEFINES AN ASSEMBLY OCCUPANCY AS AN OCCUPANCY USED
 FOR THE GATHERING OF 50 OR MORE PERSONS FOR
 DELIBERATION, WORSHIP, ENTERTAINMENT, EATING, DRINKING
 OR SIMILAR USAGE.
  
 REPEAT COMMENT (X1): EVERY ASSEMBLY OCCUPANCY ROOM NOT
 HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE
 ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT
 FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 REPEAT COMMENT (X1): SHEET A-1, A 1-HOUR FIRE-RATED
 CEILING BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER
 AREA LOCATED BENEATH THE CONCRETE STAIRS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-06 Cont ID  
Sent By wjolin Date 2013-04-06 Time 13:21 Rev Time 0.00
Received By wjolin Date 2013-04-06 Time 12:35 Sent To  
Notes
2013-04-06 13:21:056300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: THE LOCK/LATCH RELEASING MECHANISM ON
 ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE
 RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE
 AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 REPEAT COMMENT: DOORS SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS SHALL SWING IN THE DIRECTION OF EGRESS.
  
 REPEAT COMMENT: THE CORRECT OCCUPANCY TYPE NEEDS TO BE
 DETERMINED BEFORE A THOROUGH AND COMPLETE PLAN REVIEW
 CAN BE PERFORMED. THE PLANS INDICATE A BUSINESS
 OCCUPANCY; HOWEVER, AN ASSEMBLY OCCUPANCY IS MORE
 APPROPRIATE. THE FIRE CODE DEFINES AN ASSEMBLY
 OCCUPANCY AS AN OCCUPANCY USED FOR THE GATHERING OF 50
 OR MORE PERSONS FOR DELIBERATION, WORSHIP,
 ENTERTAINMENT, EATING, DRINKING OR SIMILAR USAGE.
  
 NEW COMMENT: SHEET A-1 INDICATES AN EXERCISE AREA OF
 490 SQ.FT.; HOWEVER, THE SCALED MEASUREMENT INDICATES
 AN AREA OF 800 SQ.FT. (25 FT. X 32 FT.). USING AN
 OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON (EXERCISE
 ROOM WITHOUT EQUIPMENT PER TABLE 7.3.1.2 NFPA 101)
 RESULTS IN AN OCCUPANT LOAD OF 54 PERSONS.
  
 NEW COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 NEW COMMENT: SHEET A-1, THE "HALL AREA" APPEARS TO BE A
 LARGE OPEN AREA THAT IS NOT DESIGNATED AS ANY
 PARTICULAR USE OR OCCUPANT LOAD. MORE INFORMATION (USE,
 FURNITURE, ETC.) NEEDS TO BE PROVIDED.
  
 NEW COMMENT: SHEET A-1, A 1-HOUR FIRE-RATED CEILING
 BARRIER IS NEEDED FOR THE STORAGE/WATER HEATER AREA
 LOCATED BENEATH THE CONCRETE STAIRS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-02 Cont ID  
Sent By wjolin Date 2013-03-02 Time 19:30 Rev Time 0.00
Received By wjolin Date 2013-03-02 Time 19:15 Sent To  
Notes
2013-03-02 19:30:106300 SOUTH DIXIE HIGHWAY - SUITES 101 & 102
 PERMIT #13020613
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLAN ADDRESS DOES NOT INDICATE IF IT IS NORTH DIXIE
 OR SOUTH DIXIE HIGHWAY.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXITS, OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 SHEET A-1: THE BUILDING SITE LOCATION IS INCORRECTLY
 SHOWN AS "S. MILITARY TRAIL."
  
 PROVIDE AN EXERCISE EQUIPMENT LAYOUT, YOGA MAT LAYOUT,
 ETC.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 SHALL SWING IN THE DIRECTION OF EGRESS.
  
 THE CORRECT OCCUPANCY TYPE NEEDS TO BE DETERMINED
 BEFORE A THOROUGH AND COMPLETE PLAN REVIEW CAN BE
 PERFORMED. THE PLANS INDICATE BOTH A BUSINESS OCCUPANCY
 AND "M" GROUP (MERCANTILE?); HOWEVER, AN ASSEMBLY
 OCCUPANCY APPEARS TO BE MORE APPROPRIATE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 17:00 Rev Time 0.00
Received By hmoser Date 2013-06-05 Time 10:00 Sent To  
Notes
2013-06-25 08:44:406/25 ROUTED TO HM DESK
  
2013-06-08 10:24:56*EXPEDITED*
 B--1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-24 Cont ID  
Sent By jwitmer Date 2013-05-24 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2013-05-17 Time 16:53 Sent To  
Notes
2013-05-17 16:54:02EXPEDITED
 GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 08:40 Rev Time 0.00
Received By hmoser Date 2013-04-02 Time 14:53 Sent To  
Notes
2013-04-02 15:02:25EXPEDITED
 B--11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-18 Cont ID  
Sent By hmoser Date 2013-03-18 Time 12:09 Rev Time 0.00
Received By hmoser Date 2013-02-21 Time 13:28 Sent To  
Notes
2013-02-22 13:29:25SENT TO B11 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-05-20 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2013-05-20 Time 07:11 Sent To  
Notes
2013-05-20 07:12:00IMPACT FEE STAMP ZERO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-04-10 Cont ID  
Sent By jwitmer Date 2013-04-10 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2013-04-10 Time 07:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-01 Cont ID  
Sent By jwitmer Date 2013-03-01 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2013-03-01 Time 09:55 Sent To  
Notes
2013-03-01 09:55:31BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 16:59 Rev Time 0.00
Received By hmoser Date 2013-06-25 Time 16:39 Sent To  
Notes
2013-06-25 16:59:39PASS PROVISO
 PAGE M1.1 SHOW NEW CONDENSER STAND.
 DETAIL # 2 PAGE M2.1 SHOW EXISTING
 CONDENSER STAND. IF STAND IS NEW PROVIDE A DETAIL FROM
 THE ENGINEER
 SHOWING TIE DOWN TO THE ROOF AT FIRST INSPECTION.
 PER SECTION 301.12 WIND RESISTANCE.2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 08:40 Rev Time 0.00
Received By hmoser Date 2013-04-10 Time 08:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-18 Cont ID  
Sent By hmoser Date 2013-03-18 Time 12:09 Rev Time 0.00
Received By hmoser Date 2013-03-18 Time 11:48 Sent To  
Notes
2013-03-18 12:09:34PLANS DENIED
 PROVIDE THE DUCT AND GRILL SIZE OF THE SUPPLY AND
 RETURN
 AND THE SUPPLY CFM .PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2013-06-17 Cont ID  
Sent By lwagner Date 2013-06-17 Time 14:55 Rev Time 0.00
Received By lwagner Date 2013-06-17 Time 13:30 Sent To  
Notes
2013-06-17 14:36:11***PROVISO***
  
 PER ACCESSIBILITY 2010 HI/LO DRINKING FOUNTAINS ARE
 REQUIRED.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2013-05-24 Cont ID  
Sent By jwitmer Date 2013-05-24 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2013-05-24 Time 10:27 Sent To  
Notes
2013-05-24 11:07:50PLUMBING PLAN REVIEW
 PERMIT: 13020613
 ADD: 6300 S DIXIE HWY # 101 & 102
 CONT: ATANTIDA
 TEL: (561) 290-1472
  
 2010 FLORIDA BUILDING CODE- PLUMBING W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RDREVIEW
 DATE: MAY 24/ 2013
 ACTION: DENIED
  
 NOTE: IT HS BEEN DETERMINED BY BUILDING & FIRE THAT
 THIS OCCUPANCY CLASSIFICATION IS A A3 ASSEMBLY
 OCCUPANCY, GYM WITHOUT SPECTATOR SEATING. OCCUPANT LOAD
 490 SQ FT/ 15= 33 OCCUPANTS.
 2010 FBC-EXISTING BUILDING 901.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 912 SHALL APPLY.
 2010 EXST BLDG CODE 910.1 INCREASED DEMAND. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING
 FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, PLUMBING, THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
 1) THE 2010 FBC-P TABLE 403.1(1) MINIMUM REQUIRED
 FIXTURES WILL REQUIRE A HANDICAPPED RESTROOM FOR EACH
 SEX, A SERVICE SINK AND DRINKING FOUNTAIN, NOTE THE
 2010 ACCESSIBILITY CODE REQUIRES A HIGH -LOW TYPE
 DRINKING FOUNTAIN TO MEET THE REQUIREMENTS OF :
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 PLUMBING:
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-04-09 Cont ID  
Sent By lwagner Date 2013-04-09 Time 08:51 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 13:13 Sent To  
Notes
2013-04-09 08:51:08FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLUMBING REVIEW IS PENDING THE OUTCOME FOR THE
 OCCUPANCY TYPE AND
 OCCUPANT LOAD. PLEASE SEE BUILDING REVIEW COMMENTS.
  
 A BUSINESS OCCUPANCY WITH LESS THAN 3000 SQUARE FEET
 WOULD ONLY REQUIRE ONE RESTROOM, AND WITH 15 OR LESS
 OCCUPANTS WOULD NOT REQUIRE A HI/LOW DRINKING FOUNTAIN
 (FBC
 ACCESSIBILITY CODE 211.2)
 FBC PLUMBING TABLE 403.1
  
 ALSO, A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY.
 THEN
 SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW
 DRINKING FOUNTAIN (IF OCCUPANT LOAD IS OVER 15), AND A
 SERVICE SINK.
 FBC PLUMBING TABLE 403.1 AND 403.2 SEPARATE FACILITIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805?6692
 EMAIL [email protected]
 FAX # 805?6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-27 Cont ID  
Sent By lwagner Date 2013-02-27 Time 15:45 Rev Time 0.00
Received By lwagner Date 2013-02-27 Time 10:58 Sent To  
Notes
2013-02-27 15:45:44FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 MORE INFORMATION IS REQUIRED FOR THE OCCUPANCY TYPE AND
 OCCUPANT LOAD.
 SHEET A-1 SCOPE OF WORK NOTE 4 STATES GROUP B BUISNESS
 UNDER NOTES STATES - GROUP M, WITH 35 OCCUPANTS.
 BUSINESS OCCUPANCY WITH 35 OCCUPANTS WOULD REQUIRE 2
 RESTROOMS AND A HI/LOW DRINKING FOUNTAIN (FBC
 ACCESSIBILITY CODE 211.2) UNLESS THESE ARE PROVIDED IN
 THE BUILDING COMMON AREA.
 FBC PLUMBING TABLE 403.1 WATER CLOSETS 1 PER 25 FOR THE
 FIRST 50 OCCUPANTS. DRINKING FOUNTAIN REQUIRED FOR OVER
 15 OCCUPANTS.
  
 ALSO A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY. THEN
 SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW
 DRINKING FOUNTAIN, AND A SERVICE SINK.
 FBC PLUMBING 403.2
  
 THIS OCCUPANCY DOES NOT APPEAR TO BE MERCANTILE AS
 GROUP M IS FOR THE DISPLAY AND SALE OF MERCHANDISE AND
 INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE
 INCIDENTAL TO SUCH PURPOSES...
 FBC 309.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-26 Cont ID  
Sent By ajones Date 2013-02-26 Time 14:47 Rev Time 0.00
Received By ajones Date 2013-02-26 Time 14:47 Sent To  
Notes
***NONE***