2013-04-22 08:32:33BUILDING PLAN REVIEW
 PERMIT: 13020602
 ADD: 2555 PALM BCH LAKES # 100
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 4/22/2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST, PLEASE PROVIDE ADDITIONAL DATA FOR THE
 WATER CURTAIN IN THE MAIN LOBBY, WATER CURTAINS ARE TO
 BE INSTALLED IN AN ATRIUM MEETING ALL THE REQUIEMENTS
 OF AN ATRIUM WITH SMOKE CONTROL PER 2010 FBC-B909.
 EXIST BLDG CODE 704.2.1 FIRE PROTECTION SEE SECTION 403
 OF THE FBC-B. 403.6 SMOKE REMOVAL SHALL BE PROVIDED IN
 ACCORDANCE WITH 909 FBC-B. SHEET A-1 INDICATES THAT THE
 COMMON WALL TO THE ATRIUM IS A GLASS CURTAIN WALL TYPE
 OF CONSTRUCTION WITH SPRINKLER HEADS ABOVE IN THE MAIN
 LOBBY, WE TAKE THE MEANING OF SPRINKLER HEADS IN THE
 MAIN LOBBY TO MEAN AT THE TOP OF THE ATRIUM.
  
 THE EXCEPTION TO THE ONE HOUR RATED FIRE BARRIER IS
 404.6 EXCEPTION # 1. A GLASS WALL FORMING A SMOKE
 PARTITION WHERE AUTOMATIC SPRINKLERS ARE SPACED 6 FEET
 (1829 MM) OR LESS ALONG BOTH SIDES OF THE SEPARATION
 WALL, OR ON THE ROOM SIDE ONLY IF THERE IS NOT A
 WALKWAY ON THE ATRIUM SIDE, AND BETWEEN 4 INCHES AND 12
 INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS AND
 DESIGNED SO THAT THE ENTIRE SURFACE OF THE GLASS IS WET
 UPON ACTIVATION OF THE SPRINKLER SYSTEM WITHOUT
 OBSTRUCTION. THE GLASS SHALL BE INSTALLED IN A GASKETED
 FRAME SO THAT THE FRAMING SYSTEM DEFLECTS WITHOUT
 BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLER
 SYSTEM OPERATES.
  
 IS RAISES THE QUESTION WITH CURTAIN WALL CONSTRUCTION,
 IS THERE INTERMEDIATE HORIZONTAL MULLIONS THAT WOULD
 KEEP THE WATER FROM THE FIRE SPRINLERS FROM STAYING ON
 THE GLASS, OR IF THERE IS ORIZONTAL MULLIONS THEN THE
 FIRE CURTAIN IS IN-EFFECTIVE.
  
 3) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By jwitmer Date 2013-03-12 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2013-03-12 Time 11:46 Sent To  
Notes
2013-03-12 13:59:51BUILDING PLAN REVIEW
 PERMIT: 13020602
 ADD: 2555 PALM BCH LAKES # 100
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 3/12/2013
 ACTION: DENIED
  
 1) BUILDING DATA INDICATES THIS TO BE A TYPE III
 BUILDING, PLEASE REVIEW THE 2010 FBC-B TABLE 503 FOR A
 15 STORY BUILDING IT HAS TO BE BUILDING TYPE IA.
  
 2) PLEASE PROVIDE ADDITIONAL DATA FOR THE WATER CURTAIN
 IN THE MAIN LOBBY, WATER CURTAINS ARE TO BE INSTALLED
 IN AN ATRIUM MEETING ALL THE REQUIEMENTS OF AN ATRIUM
 WITH SMOKE CONTROL PER 2010 FBC-B909. EXIST BLDG CODE
 704.2.1 FIRE PROTECTION SEE SECTION 403 OF THE FBC-B.
 403.6 SMOKE REMOVAL SHALL BE PROVIDED IN ACCORDANCE
 WITH 909 FBC-B.
  
 3) SHEET A-3 INDICATES A FIRE SPRAY PLAN, A NOTE THAT
 INDICATES FIRE SPRAY THE ENTIRE ROOF STRUCTURES AS
 SHOWN , AND THE PLAN IS THE INTERIOR SPACE OF UNIT #
 100. ADDITIONAL INFORMATION REQUIRED, 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 08:55 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 08:54 Sent To  
Notes
2013-05-06 08:55:295-6-13
 CORRECTIONS MADE
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-14 Cont ID  
Sent By rlecky Date 2013-03-14 Time 11:14 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 08:54 Sent To  
Notes
2013-03-14 11:02:41 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-05-11 Cont ID  
Sent By wjolin Date 2013-05-11 Time 15:39 Rev Time 0.00
Received By wjolin Date 2013-05-11 Time 15:00 Sent To B
Notes
2013-05-11 15:39:041555 PALM BEACH LAKES BOULEVARD - SUITE #100
 PERMIT #13020602
 REVIEW #3 COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-1: ENGINEERED FIRE SPRINKLER DRAWINGS THAT
 WERE SUBMITTED ARE NOT SIGNED/SEALED BY A PROFESSIONAL
 ENGINEER. THE DESIGN OR ALTERATION OF 50 OR MORE
 SPRINKLERS REQUIRES SIGNED/SEALED PLANS. PLANS TO BE
 SEALED BEFORE PERMIT IS ISSUED.
  
 AN ON-SITE INSPECTION WAS PERFORMED SATURDAY
 (05/11/13). THE MAIN LOBBY ENTRANCE CONNECTS THE GROUND
 FLOOR WITH TWO OTHER FLOORS. NO SPRINKLER WATER CURTAIN
 (CLOSELY SPACED SPRINKLERS) WERE OBSERVED ON THE LOWER
 LEVEL ON EITHER SIDE OF THE EXISTING GLASS CURTAIN
 WALLS.THE EXISTING LOBBY AREA APPEARS TO BE A
 "COMMUNICATING SPACE" IN LIEU OF AN "ATRIUM." ARCHITECT
 TO PROVIDE LETTER INDICATING IF EXISTING SPACE IS A
 "COMMUNICATING SPACE" OR AN "ATRIUM."
  
 PER NFPA 101:
 8.6.6 COMMUNICATING SPACE. UNENCLOSED FLOOR OPENINGS
 FORMING A COMMUNICATING SPACE BETWEEN FLOOR LEVELS
 SHALL BE PERMITTED, PROVIDED THAT THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE COMMUNICATING SPACE DOES NOT CONNECT MORE THAN
 THREE CONTIGUOUS STORIES.
 (2) THE LOWEST OR NEXT-TO-LOWEST STORY WITHIN THE
 COMMUNICATING SPACE IS A STREET FLOOR.
 (3) THE ENTIRE FLOOR AREA OF THE COMMUNICATING SPACE IS
 OPEN AND UNOBSTRUCTED, SUCH THAT A FIRE IN ANY PART OF
 THE SPACE WILL BE READILY OBVIOUS TO THE OCCUPANTS OF
 THE SPACE PRIOR TO THE TIME IT BECOMES AN OCCUPANT
 HAZARD.
 (4) THE COMMUNICATING SPACE IS SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY FIRE BARRIERS WITH NOT
 LESS THAN A 1-HOUR FIRE RESISTANCE RATING, UNLESS ONE
 OF THE FOLLOWING IS MET:
 (A) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7, A SMOKE BARRIER IN ACCORDANCE WITH SECTION 8.5
 SHALL BE PERMITTED TO SERVE AS THE SEPARATION REQUIRED
 BY 8.6.6(4).
 (B) THE REQUIREMENT OF 8.6.6(4) SHALL NOT APPLY TO
 FULLY SPRINKLERED RESIDENTIAL HOUSING UNITS OF
 DETENTION AND CORRECTIONAL OCCUPANCIES IN ACCORDANCE
 WITH 22.3.1(2) AND 23.3.1.1(2).
 (5) THE COMMUNICATING SPACE HAS ORDINARY HAZARD
 CONTENTS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7 OR HAS
 ONLY LOW HAZARD CONTENTS. (SEE 6.2.2.)
 (6) EGRESS CAPACITY IS SUFFICIENT TO ALLOW ALL THE
 OCCUPANTS OF ALL LEVELS WITHIN THE COMMUNICATING SPACE
 TO SIMULTANEOUSLY EGRESS THE COMMUNICATING SPACE BY
 CONSIDERING IT AS A SINGLE FLOOR AREA IN DETERMINING
 THE REQUIRED EGRESS CAPACITY.
 (7) EACH OCCUPANT WITHIN THE COMMUNICATING SPACE HAS
 ACCESS TO NOT LESS THAN ONE EXIT WITHOUT HAVING TO
 TRAVERSE ANOTHER STORY WITHIN THE COMMUNICATING SPACE.
 (8) EACH OCCUPANT NOT IN THE COMMUNICATING SPACE HAS
 ACCESS TO NOT LESS THAN ONE EXIT WITHOUT HAVING TO
 ENTER THE COMMUNICATING SPACE.
  
 8.6.7 ATRIUMS. AN ATRIUM SHALL BE PERMITTED, PROVIDED
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY
 FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING WITH OPENING PROTECTIVES FOR CORRIDOR
 WALLS, UNLESS ONE OF THE FOLLOWING IS MET:
 (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO
 EXISTING, PREVIOUSLY APPROVED ATRIUMS.
 (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE
 PERMITTED TO OPEN DIRECTLY TO THE ATRIUM WITHOUT
 ENCLOSURE BASED ON THE RESULTS OF THE ENGINEERING
 ANALYSIS REQUIRED IN 8.6.7(5).
 (C)*GLASS WALLS AND INOPERABLE WINDOWS SHALL BE
 PERMITTED IN LIEU OF THE FIRE BARRIERS WHERE ALL THE
 FOLLOWING ARE MET:
 I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES OF
 THE GLASS WALL AND THE INOPERABLE WINDOWS AT INTERVALS
 NOT TO EXCEED 6 FT (1830 MM).
 II. THE AUTOMATIC SPRINKLERS SPECIFIED IN
 8.6.7(1)(C)(I) ARE LOCATED AT A DISTANCE FROM THE GLASS
 WALL NOT TO EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT
 THE ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION
 OF THE SPRINKLERS.
 III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED
 GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS THE
 GLASS FRAMING SYSTEM TO DEFLECT WITHOUT BREAKING
 (LOADING) THE GLASS BEFORE THE SPRINKLERS OPERATE.
 IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(1)(C)(I)
 ARE NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL
 AND THE INOPERABLE WINDOW WHERE THERE IS NO WALKWAY OR
 OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE THE MAIN
 FLOOR LEVEL.
 V. DOORS IN THE GLASS WALLS ARE OF GLASS OR OTHER
 MATERIAL THAT RESISTS THE PASSAGE OF SMOKE.
 VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON DETECTION OF SMOKE.
 VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT
 HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER
 OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING OF
 THE ENTIRE GLASS SURFACE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-20 Cont ID  
Sent By wjolin Date 2013-04-20 Time 12:18 Rev Time 0.00
Received By wjolin Date 2013-04-20 Time 11:50 Sent To  
Notes
2013-04-20 12:15:591555 PALM BEACH LAKES BOULEVARD - SUITE #100
 PERMIT #13020602
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW COMMENT: IN ADDITION TO THE ARCHITECTURAL RESPONSE
 LETTER, PLEASE PROVIDE A NOTE ON THE DRAWING INDICATING
 THERE IS AN EXISTING ATRIUM DESIGNED WITH SMOKE CONTROL
 SYSTEM.
  
 RESPONSE COMMENT: PLAN STILL SEEMS TO INDICATE CLOSELY
 SPACED SPRINKLERS ON THE ATRIUM SIDE ONLY.
 ORIGINAL COMMENT - SHEET A-1: PLAN INDICATES AN
 EXISTING SPRINKLER WATER CURTAIN IN THE LOBBY
 PROTECTING THE GLAZING CURTAIN WALL IN TRAINING ROOM
 #100. CLOSELY SPACED SPRINKLERS ARE REQUIRED TO BE
 LOCATED ON BOTH SIDES OF THE GLASS TO USE A SPRINKLER
 WATER CURTAIN IN LIEU OF FIRE-RATED GLASS. PLAN STILL
 SEEMS TO INDICATE CLOSELY SPACED SPRINKLERS ON THE
 ATRIUM SIDE ONLY.
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. PER FBC
 907.1.1 CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 NOTE: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By wjolin Date 2013-03-07 Time 11:49 Rev Time 0.00
Received By wjolin Date 2013-03-07 Time 10:45 Sent To  
Notes
2013-03-07 11:49:561555 PALM BEACH LAKES BOULEVARD - SUITE #100
 PERMIT #13020602
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A SUITE NUMBER IN THE TITLEBLOCK INFORMATION.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SHEET A-1: PLAN INDICATES AN EXISTING SPRINKLER WATER
 CURTAIN IN THE LOBBY PROTECTING THE GLAZING CURTAIN
 WALL IN TRAINING ROOM #100. CLOSELY SPACED SPRINKLERS
 ARE REQUIRED TO BE LOCATED ON BOTH SIDES OF THE GLASS.
 ALSO, TO USE A SPRINKLER WATER CURTAIN IN LIEU OF
 FIRE-RATED GLASS, THE LOBBY NEEDS TO MEET THE
 DEFINITION OF AN ATRIUM AND BE EQUIPPED WITH A SMOKE
 CONTROL SYSTEM. CONFIRM EXISTING LOBBY COMPLIES WITH
 THESE REQUIRMENTS.
  
 SHEET M-1: NO DUCT SMOKE DETECTORS PROVIDED FOR 2100
 CFM AIR HANDLER UNITS (1 & 2).
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. PER FBC
 907.1.1 CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-15 Cont ID  
Sent By jwitmer Date 2013-05-15 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2013-05-11 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-06 Cont ID  
Sent By lmartine Date 2013-05-06 Time 11:02 Rev Time 0.00
Received By lmartine Date 2013-04-12 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 09:22 Rev Time 0.00
Received By hmoser Date 2013-02-22 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-01 Cont ID  
Sent By hmoser Date 2013-05-01 Time 13:34 Rev Time 0.00
Received By hmoser Date 2013-05-01 Time 13:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 09:21 Rev Time 0.00
Received By hmoser Date 2013-03-20 Time 15:26 Sent To  
Notes
2013-03-21 09:21:53PLANS DENIED
 1) PROVIDE DUCT SMOKE DETECTORS ON AHU 1 & 3
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC (M)
 2) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M)
 3) PROVIDE FRESH AIR DUCT ON AHU # 3
 4) REFER TO SECTION 403.3 OUTDOOR AIR FLOW RATE AND
 TABLE 403.3 MINIMUM VENTILATION RATES 2010 FBC (M)
 5) PROVIDE DUCT SIZE ON ALL DUCT. PER SECTION 107 FBC
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-15 Cont ID  
Sent By lwagner Date 2013-04-15 Time 12:10 Rev Time 0.00
Received By lwagner Date 2013-04-15 Time 12:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-28 Cont ID  
Sent By lwagner Date 2013-02-28 Time 13:35 Rev Time 0.00
Received By lwagner Date 2013-02-28 Time 13:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-26 Cont ID  
Sent By ajones Date 2013-02-26 Time 14:53 Rev Time 0.00
Received By ajones Date 2013-02-26 Time 14:53 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved