Plan Review Stops For Permit 13020404 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-02-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-25 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-25 |
Time |
16:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-02-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-21 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-21 |
Time |
14:38 |
Sent To |
|
|
Notes |
2013-02-21 14:41:08 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-02-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-21 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-21 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
|