Plan Review Details - Permit 13020353
Plan Review Stops For Permit 13020353
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2013-02-21 Time 07:45 Sent To  
Notes
2013-02-13 13:21:50COMBINING SPACES A15, A16, & A17 INTO 1 SPACE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 07:43 Rev Time 0.00
Received By jwitmer Date 2013-04-19 Time 07:43 Sent To  
Notes
2013-04-19 07:45:11NEW A2.1, MP 101 & MP 102. PULL OLD SHEETS COLATE PLANS
 STAMP PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-02-21 Cont ID  
Sent By jwitmer Date 2013-02-21 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2013-02-21 Time 07:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-02-25 Cont ID  
Sent By rlecky Date 2013-02-25 Time 14:25 Rev Time 0.00
Received By rlecky Date 2013-02-25 Time 13:00 Sent To  
Notes
2013-02-25 14:26:23SEE REDLINED NOTE FOR NEC 110.9 (INTERRUPTING RATING)
 ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-02-16 Cont ID  
Sent By wjolin Date 2013-02-16 Time 11:58 Rev Time 0.00
Received By wjolin Date 2013-02-16 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2013-04-01 Time 10:21 Sent To  
Notes
2013-04-02 10:22:00B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-11 Cont ID  
Sent By hmoser Date 2013-03-11 Time 15:15 Rev Time 0.00
Received By hmoser Date 2013-02-13 Time 13:30 Sent To  
Notes
2013-02-14 13:30:59SENT TO B6 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-10 Cont ID  
Sent By hmoser Date 2013-04-10 Time 13:20 Rev Time 0.00
Received By hmoser Date 2013-04-10 Time 13:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-11 Cont ID  
Sent By hmoser Date 2013-03-11 Time 15:15 Rev Time 0.00
Received By hmoser Date 2013-03-11 Time 14:25 Sent To  
Notes
2013-03-11 15:15:13PLANS DENIED
 1) REFER TO SECTION 307.2.2 DRAIN PIPE MATERIALS
 AND SIZE. 2010 FBC (M)
 2) PROVIDE EQUIPMENT SCHEDULE ON THE
 PLANS FOR THE NEW AIRCONDITIONING EQUIPMENT
 PER SECTION 107 FBC
 3) PLEASE REVISE THE VALUE OF THE JOB ON THE
 APPLICATION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-25 Cont ID  
Sent By lwagner Date 2013-02-25 Time 15:55 Rev Time 0.00
Received By lwagner Date 2013-02-25 Time 15:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-04-18 Cont ID  
Sent By eschneid Date 2013-04-18 Time 15:41 Rev Time 0.50
Received By eschneid Date 2013-04-18 Time 15:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-03-05 Cont ID  
Sent By eschendi Date 2013-03-05 Time 08:49 Rev Time 0.50
Received By eschneid Date 2013-03-05 Time 08:49 Sent To  
Notes
2013-03-05 13:10:45FAILED
  
 1) THERE IS NEW EQUIPMENT BEING INSTALLED ON THE ROOF.
 IN ACCORDANCE WITH THE CITYPLACE DRI, ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT
 THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED
 FROM PUBLIC VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
2013-02-21 14:21:522/21/13