Plan Review Details - Permit 13020348
Plan Review Stops For Permit 13020348
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-22 Cont ID  
Sent By jwitmer Date 2013-02-22 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2013-02-22 Time 08:25 Sent To  
Notes
2013-02-22 08:50:49BUILDING PLAN REVIEW
 PERMIT: 13020348
 ADD: 1616 N FLORIDA MANGO
 CONT: BADER'S GROUP
 TEL: (561)294-4070
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE: 02/22/2013
 ACTION: DENIED
  
 1) PLEASE SHOW CODE COMPLIANCE WITH 2010 FBC-B:
  
 1A) [F] 416.2 SPRAY ROOMS. SPRAY ROOMS SHALL BE
 ENCLOSED WITH NOT LESS THAN 1-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED AND
 DRAINED IN AN APPROVED MANNER.
  
 1B) [F] 416.2.1 SURFACES. THE INTERIOR SURFACES OF
 SPRAY ROOMS SHALL BE SMOOTH AND SHALL BE SO CONSTRUCTED
 TO PERMIT THE FREE PASSAGE OF EXHAUST AIR FROM ALL
 PARTS OF THE INTERIOR AND TO FACILITATE WASHING AND
 CLEANING, AND SHALL BE SO DESIGNED TO CONFINE RESIDUES
 WITHIN THE ROOM. ALUMINUM SHALL NOT BE USED.
  
 1C) [F] 416.3 SPRAYING SPACES. SPRAYING SPACES SHALL BE
 VENTILATED WITH AN EXHAUST SYSTEM TO PREVENT THE
 ACCUMULATION OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL. WHERE SUCH
 SPACES ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE
 SPRAY CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD
 OF FLAMMABLE VAPORS.
  
 1D) [F] 416.3.1 SURFACES. THE INTERIOR SURFACES OF
 SPRAYING SPACES SHALL BE SMOOTH AND CONTINUOUS WITHOUT
 EDGES; SHALL BE SO CONSTRUCTED TO PERMIT THE FREE
 PASSAGE OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR
 AND TO FACILITATE WASHING AND CLEANING; AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE SPRAYING SPACE.
 ALUMINUM SHALL NOT BE USED.
  
 1E) [F] 416.4 SPRAY BOOTHS. SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE.
  
 1F) [F] 416.5 FIRE PROTECTION. AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL
 SPRAY, DIP AND IMMERSING SPACES AND STORAGE ROOMS AND
 SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 9.
  
 2A) PLEASE PROVIDE AMOUNTS OF FLAMABLE OR COMBUSTILE
 LIQUIDS THAT ARE GOING TO BE USED, DISPENSED OR MIXED
 IN OPEN CONTAINERS WITHIN THE MIXING ROOM, THIS WILL
 CLASSIFY TYPE OF OCCUPANCY. SECTION 415, AND TABLE
 307.1(1) MAXIMUM ALLOWABLE QUANITIES PER CONTROL AREA
 OF HAZARDOUS MATERIALS, CLASS I, II AND III FLAMMABLE
 OR COMBUSTIBLE LIQUIDS.
  
 2B) 414.2.1 FIRE-RESISTANCE-RATING REQUIREMENTS.
 CONSTRUCTION REQUIREMENTS. CONTROL AREAS SHALL BE
 SEPARATED FROM EACH OTHER BY FIRE BARRIERS CONSTRUCTED
 IN ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 712, OR BOTH.
  
 2C) [F] 414.2.3 NUMBER. THE MAXIMUM NUMBER OF CONTROL
 AREAS WITHIN A BUILDING SHALL BE IN ACCORDANCE WITH
 TABLE 414.2.2.
  
 3) SHEET A1 INDICATES VENTING THROUGH THE ROOF,
 APPROXIMATELY 4'-0" & 7'-0" , HOW ARE THESE ROOF VENTS
 BE HELD IN PLACE IN THE EVENT OF A HIGH WIND EVENT?
 1609. COMPONENTS & CLADDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-26 Cont ID  
Sent By rlecky Date 2013-02-26 Time 09:25 Rev Time 0.00
Received By rlecky Date 2013-02-26 Time 08:23 Sent To  
Notes
2013-02-26 09:25:5213020348
 1616 N. FLORIDA MANGO ROAD #C8
 PAINT SPRAY BOOTH
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE SPRAY BOOTH, MIXING ROOMS AND ALL AREAS WITHIN 3
 FEET MUST BE CLASSIFIED FOR THE HAZARD. INDICATE ON THE
 PLANS THE APPROPRIATE CLASSIFICATION AND ELECTRICAL
 WIRING METHOD.
 NEC 516.3(C)(2)
  
 PROVIDE A LISTING FROM A NATIONALLY REGISTERED TESTING
 LABORATORY FOR THE SPRAY BOOTH AND PAINT MIXING ROOM.
 NEC 110.3
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By wjolin Date 2013-02-25 Time 14:52 Rev Time 0.00
Received By wjolin Date 2013-02-25 Time 14:19 Sent To  
Notes
2013-02-25 14:50:561616 NORTH FLORIDA MANGO ROAD
 PERMIT #13020348
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 OPERATIONS INVOLVING THE SPRAY APPLICATION OF FLAMMABLE
 AND COMBUSTIBLE MATERIALS SHALL COMPLY WITH NFPA 33
 (2007 EDITION).
  
 MIXING ROOMS AND SPRAY AREAS (WHICH INCLUDE EXHAUST
 PLENUMS, EXHAUST DUCTWORK, FILTERS, ETC.) SHALL BE
 PROTECTED WITH AN APPROVED AUTOMATIC FIRE PROTECTION
 SYSTEM.
  
 MIXING ROOMS AND SPRAY BOOTHS SHALL BE CONSTRUCTED OF
 AND SEPARATED FROM SURROUNDING AREAS OF THE BUILDING BY
 CONSTRUCTION ASSEMBLIES THAT HAVE A FIRE RESISTANCE
 RATING OF 1-HOUR.
  
 MIXING ROOM SHALL BE DESIGNED TO CONTAIN A SPILL OF THE
 CONTENTS IN THE ROOM.
  
 AREAS ADJACENT TO THE MIXING ROOM AND SPRAY BOOTH SHALL
 HAVE PERMANENT SIGNS INDICATING, "NO SMOKING OR OPEN
 FLAMES PERMITTED."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-02-20 Cont ID  
Sent By lwagner Date 2013-02-20 Time 15:48 Rev Time 0.00
Received By lwagner Date 2013-02-20 Time 15:32 Sent To  
Notes
2013-02-20 15:48:37FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 PLEASE SUBMIT THE FOLLOWING FOR A FUEL GAS REVIEW::
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-13 Cont ID  
Sent By lwagner Date 2013-03-13 Time 14:48 Rev Time 0.00
Received By lwagner Date 2013-02-13 Time 09:52 Sent To  
Notes
2013-02-14 09:53:18SENT TO B3 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-13 Cont ID  
Sent By hmoser Date 2013-03-13 Time 11:17 Rev Time 0.00
Received By hmoser Date 2013-03-11 Time 15:25 Sent To  
Notes
2013-03-13 11:17:28PLANS DENIED
 1) PROVIDE VENTILATION SEQUENCE ON THE PLANS.
 REFER TO SECTION 502.7.3.1 THROUGH 502.7.3.6
 2010 FBC (M)
 2) SEPARATE APPLICATION , PLANS AND PERMIT REQUIRED
 FOR AUTOMATIC SPRINKLER PROTECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-02-20 Cont ID  
Sent By lwagner Date 2013-02-20 Time 15:31 Rev Time 0.00
Received By lwagner Date 2013-02-20 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-21 Cont ID  
Sent By ajones Date 2013-02-21 Time 14:23 Rev Time 0.00
Received By ajones Date 2013-02-21 Time 14:23 Sent To  
Notes
***NONE***