Plan Review Details - Permit 13020245
Plan Review Stops For Permit 13020245
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-09 Cont ID  
Sent By hmoser Date 2013-05-09 Time 13:48 Rev Time 0.00
Received By hmoser Date 2013-05-08 Time 12:34 Sent To  
Notes
2013-05-08 12:34:28TO MECHANICAL
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-19 Cont ID  
Sent By hmoser Date 2013-02-19 Time 12:35 Rev Time 0.00
Received By hmoser Date 2013-02-12 Time 09:27 Sent To  
Notes
2013-02-12 09:27:56MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-09 Cont ID  
Sent By hmoser Date 2013-05-09 Time 13:48 Rev Time 0.00
Received By hmoser Date 2013-05-09 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-19 Cont ID  
Sent By hmoser Date 2013-02-19 Time 12:35 Rev Time 0.00
Received By hmoser Date 2013-02-19 Time 12:07 Sent To  
Notes
2013-02-19 12:35:07PLANS DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 PER SECTION 107 FBC 1210
 2) PROVIDE TWO COPIES OF ENERGY CALCULATIONS
 AND HEAT LOADS WITH THE PLANS. PER SECTION
 107 FBC 2010
 3) PROVIDE RETURN AIR DUCT SIZE OFF A/H 4
 ON THE PLANS.PER SECTION 107 FBC.
 4) PROVIDE A DETAIL FROM THE ENGINEER ON
 THE CONDENSER TIE DOWN. PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]