Plan Review Details - Permit 13020220
Plan Review Stops For Permit 13020220
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By shill Date 2013-05-16 Time 16:57 Rev Time 0.00
Received By shill Date 2013-05-16 Time 16:57 Sent To  
Notes
2013-05-16 16:58:54****PROVISO****
  
 REVISION REQUIRED
  
 SUBMIT A FLOOR PLAN SHOWING WINDOW LOCATIONS, SIZES,
 AND LOCATION/SCOPE OF DRYWALL REPLACEMENT.
  
 SUBMIT FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 COMPONENTS AND CLADDING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-12 Cont ID  
Sent By shill Date 2013-02-12 Time 11:19 Rev Time 0.00
Received By shill Date 2013-02-12 Time 11:19 Sent To  
Notes
2013-02-12 11:23:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. SEE FBC 107.2.1:
  
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 NO PLAN SUBMITTED.
  
 2. SHOW LOCATION AND SCOPE OF DRYWALL REPLACEMENT ON A
 PLAN, FBC 107.
  
 3. PROVIDE A STRUCTURAL DETAIL FOR ROOF JOIST REPAIR.
 SHOW LOCATION AND SCOPE ON A PLAN, AND INCLUDE WIND
 DESIGN CRITERIA AND NAME AND SIGNATURE OF PERSON TAKING
 RESPONSIBILITY FOR THE DESIGN FBC 107.2, FBC R 301.
  
 4. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE DOORS AND WINDOWS, FAC9N-3.
  
 5. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR
 LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR
 SIZE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-21 Cont ID  
Sent By rlecky Date 2013-02-21 Time 12:09 Rev Time 0.00
Received By rlecky Date 2013-02-21 Time 12:06 Sent To  
Notes
2013-02-21 12:09:5913020220
 2003 N. TAMARIND AVE
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-16 Cont ID  
Sent By wjolin Date 2013-02-16 Time 12:12 Rev Time 0.00
Received By wjolin Date 2013-02-16 Time 12:10 Sent To  
Notes
2013-02-16 12:12:342003 TAMARIND AVENUE
 PERMIT #13020220
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A BUILDING FLOOR PLAN DETAILING THE WORK TO BE
 PERFORMED AT THIS LOCATION.
  
 A THOROUGH PLAN REVIEW CANNOT BE PERFORMED AT THIS TIME
 DUE TO LACK OF INFORMATION SUBMITTED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 09:41 Rev Time 0.00
Received By hmoser Date 2013-02-11 Time 10:12 Sent To  
Notes
2013-02-14 14:54:27B-10
 CHANGED PERMIT TYPE FROM RES. TO COMM.
2013-02-11 10:13:39SENT TO MISC 1 BOX PER LUIS MARTINEZ.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 09:38 Rev Time 0.00
Received By hmoser Date 2013-02-25 Time 09:37 Sent To  
Notes
2013-02-25 09:41:04DENIED
 NEED MORE INFORMATION FOR MECHANICAL REVIEW.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-15 Cont ID  
Sent By lwagner Date 2013-02-15 Time 13:13 Rev Time 0.00
Received By lwagner Date 2013-02-15 Time 13:09 Sent To  
Notes
2013-02-15 13:13:39FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 IF THE NEW SINK REQUIRES PLUMBING PIPEING, A PLUMBING
 ISOMETRIC WILL BE REQUIRED.
 FBC 107.3.5.1.3
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By mdekle Date 2013-02-11 Time   Rev Time  
Received By mdekle Date 2013-02-11 Time   Sent To  
Notes
***NONE***