Plan Review Details - Permit 13020219
Plan Review Stops For Permit 13020219
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-29 Cont ID  
Sent By shill Date 2013-03-29 Time 10:25 Rev Time 0.00
Received By shill Date 2013-03-29 Time 10:25 Sent To  
Notes
2013-03-29 10:41:15****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SPEC SHEET REFERS TO A NEW CLOSET AND DOOR, NOT
 SHOWN ON PLAN. CONFIRM THAT THIS HAS BEEN REMOVED FROM
 SCOPE OR REVISE PLAN TO SHOW ALL WORK PROPOSED, FBC
 107.
  
 2. ENGINEER TO PROVIDE AN INDEX SHEET USING CURRENT
 SEAL (OLD SEAL USED ON PLANS INADVERTENTLY);
 FAC61G15-23.002.
  
 3. ENGINEER TO PROVIDE LETTERS PRINTED ON ENGINEER'S
 LETTERHEAD RATHER THAN GLADES ROOFING LLC LETTERHEAD
 FAC61G15-23.002.
  
 4. ENERGY CALCS NOT SIGNED AND ARE LACKING THE HEATING
 EQUIPMENT INFORMATION, SUBMIT AS A REVISION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-21 Cont ID  
Sent By shill Date 2013-03-21 Time 07:03 Rev Time 0.00
Received By shill Date 2013-03-21 Time 07:03 Sent To  
Notes
2013-03-21 07:28:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. SPEC SHEET REFERS TO A NEW CLOSET AND DOOR, NOT
 SHOWN ON PLAN. CONFIRM THAT THIS HAS BEEN REMOVED FROM
 SCOPE OR REVISE PLAN TO SHOW ALL WORK PROPOSED, FBC
 107.
  
 4. OK
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE FLAT DECK. PROVIDE ROOF HEIGHT AND SLOPE. FOR THE
 ROOF, INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED AND
 PROVIDE ENGINEERING IF REQUIRED OR OTHERWISE SPECIFY
 ENHANCED FASTENING, SEE LIMITATIONS ON THE PRODUCT
 APPROVAL. A SEPARATE ROOF SUB PERMIT IS REQUIRED.
  
 PLEASE NOTE THAT INSULATION BOARD IS REQUIRED PER
 SPECIFICATION.
  
 ROOF INFORMATION MAY BE PROVIDED UNDER A SEPARATE STAND
 ALONE PERMIT. PLEASE ADVISE IF YOU WISH FOR THIS SCOPE
 TO BE REMOVED FROM THIS PERMIT.
  
 2ND REVIEW, TWO DIFFERENT ASSEMBLIES HIGHLIGHTED
 (SHEETS 8 AND 11), SEE GENERAL LIMITATION #7,
 CALCULATIONS IN ACCORDANCE WITH RAS 117 TO BE
 CALCULATED BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT, FBC R 301.
  
 6-7. OK
  
 NEW COMMENT:
  
 ENGINEER'S SEAL TO BE IN ACCORDANCE WITH FBPE BOARD
 RULES, FS 471, FAC61G-15.23. SEAL TO STATE "LICENSE"
 RATHER THAN "CERTIFICATE" (RULE CHANGED SEVERAL YEARS
 AGO).
  
 IT IS NOT CLEAR WHETHER THE ENGINEER IS WORKING THROUGH
 THE COMPANY GLADES ROOFING LLC. ENGINEER'S LETTER
 APPROVING PRODUCT APPROVALS IS NOT SEALED AND IS ON
 GLADES ROOFING LLC'S LETTERHEAD. IF THE ENGINEER IS
 PRACTICING ENGINEERING THROUGH THIS COMPANY, A
 CERTIFICATE OF AUTHORIZATION IS REQUIRED FS471. IF THE
 ENGINEER IS NOT, EITHER PROVIDE THE LETTER ON THE
 ENGINEER'S LETTERHEAD OR EXPLAIN WHY THE ENGINEER IS
 USING THE CONTRACTOR'S LETTERHEAD FOR BUILDING
 SPECIFICATIONS.
  
 ENERGY CALCS NOT SIGNED AND ARE LACKING THE HEATING
 EQUIPMENT INFORMATION.
  
 NEW COMMENT:
  
 UPON REQUEST, OUTSTANDING ITEMS CAN BE PROVISO ITEMS
 (REVISION REQUIRED PRIOR TO FIRST INSPECTION). PERMIT
 WILL BE ISSUED AT CONTRACTOR'S RISK.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-12 Cont ID  
Sent By shill Date 2013-02-12 Time 11:27 Rev Time 0.00
Received By shill Date 2013-02-12 Time 11:27 Sent To  
Notes
2013-02-12 11:37:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. SEE FBC 107.2.1:
  
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 NO PLAN SUBMITTED.
  
 2. PLEASE DO NOT SUBMIT DOCUMENTS NOT REQUIRED TO SHOW
 CODE COMPLIANCE. FOR INSTANCE, THE DOCUMENT REGARDING
 LEAD BASED PAINT.
  
 3. PROVIDE A STRUCTURAL DETAILS FOR STAIRS, RAILINGS,
 COLUMNS, NEW INTERIOR DOOR FRAMING (AS WELL AS INCLUDE
 LOCATIONS ON A FLOOR PLAN), FBC R 301.
  
 4. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE DOORS AND WINDOWS, FAC9N-3.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE FLAT DECK. PROVIDE ROOF HEIGHT AND SLOPE. FOR THE
 ROOF, INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED AND
 PROVIDE ENGINEERING IF REQUIRED OR OTHERWISE SPECIFY
 ENHANCED FASTENING, SEE LIMITATIONS ON THE PRODUCT
 APPROVAL. A SEPARATE ROOF SUB PERMIT IS REQUIRED.
  
 PLEASE NOTE THAT INSULATION BOARD IS REQUIRED PER
 SPECIFICATION.
  
 ROOF INFORMATION MAY BE PROVIDED UNDER A SEPARATE STAND
 ALONE PERMIT. PLEASE ADVISE IF YOU WISH FOR THIS SCOPE
 TO BE REMOVED FROM THIS PERMIT.
  
 6. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR
 LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR
 SIZE.
  
 7. REAR UNIT REQUIRES ALL INFORMATION AS NOTED ABOVE TO
 BE INCLUDED IN A SEPARATE PERMIT APPLICATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 15:49 Rev Time 0.00
Received By rlecky Date 2013-04-01 Time 11:25 Sent To  
Notes
2013-04-01 12:40:27 
 13020219
 817 21ST STREET
 RESIDENTIAL REPAIR
  
 THE PERMIT WAS APPROVED WITH THE FOLLOWING REQUIREMENTS
 LISTED ON THE PLAN.
  
 PROVISO
  
 KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED.
 NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-20 Cont ID  
Sent By rlecky Date 2013-02-20 Time 16:26 Rev Time 0.00
Received By rlecky Date 2013-02-20 Time 15:55 Sent To P
Notes
2013-02-20 16:27:2813020219
 817 21ST STREET
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-02 Cont ID  
Sent By lwagner Date 2013-04-02 Time 10:36 Rev Time 0.00
Received By lwagner Date 2013-03-18 Time 08:53 Sent To  
Notes
2013-03-20 09:20:56R--1
2013-03-20 09:20:38EXPEDITED
 (CITY HOUSING)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:07 Rev Time 0.00
Received By hmoser Date 2013-02-08 Time 10:14 Sent To  
Notes
2013-02-12 11:38:582/11 TO ZONING
  
2013-02-11 10:23:01SENT TO MISC 1 BOX PER L MARTINEZ.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 08:45 Rev Time 0.00
Received By hmoser Date 2013-03-21 Time 08:45 Sent To  
Notes
2013-03-21 09:03:53PROVISO
  
 ANY CHANGES TO DUCTWORK WILL REQUIRE A PLAN SUBMITTED
 AS A REVISION
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:07 Rev Time 0.00
Received By hmoser Date 2013-02-25 Time 12:49 Sent To  
Notes
2013-02-25 13:07:05DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS
 2010 FBC.
 2) ANY NEW MECHANICAL WORK REQUIRES A MECHANICAL PLAN.
 PER SECTION 107.3.5.3 (10) AND ( 13 ) 2010 FBC
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-02 Cont ID  
Sent By lwagner Date 2013-04-02 Time 10:35 Rev Time 0.00
Received By lwagner Date 2013-04-02 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-22 Cont ID  
Sent By lwagner Date 2013-02-22 Time 15:26 Rev Time 0.00
Received By lwagner Date 2013-02-22 Time 14:31 Sent To  
Notes
2013-02-22 15:00:45FBC 2010 EXISTING BUILDING CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. PLEASE SEE BUILDING REVIEW NOTES FOR FBC 107.2.1:
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ANY NEW PLUMBING PIPEING REQUIRES A PLUMBING
 DRAWING.
 FBC 107.3.5.3 (11)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By mdekle Date 2013-02-11 Time   Rev Time  
Received By mdekle Date 2013-02-11 Time   Sent To E
Notes
***NONE***