Plan Review Stops For Permit 13020218 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2013-06-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-06-28 |
Time |
07:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-06-28 |
Time |
07:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2013-02-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-26 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-26 |
Time |
16:34 |
Sent To |
M |
|
Notes |
2013-02-26 16:34:56 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: | | | | 1. SEE FBC 107.2.1: | | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED | | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | NO PLAN SUBMITTED. | | | | 2. OK | | | | 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR | | THE ROOF SHINGLES. PROVIDE ROOF HEIGHT AND SLOPE. A | | SEPARATE ROOF SUB PERMIT IS REQUIRED. | | | | 4. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR | | LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR | | SIZE. | | | | 5. SHOW LOCATION OF PROPOSED NEW DOORS ON THE FLOOR | | PLAN, FBC 107. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-02-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-21 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-21 |
Time |
13:24 |
Sent To |
M |
|
Notes |
2013-02-21 13:34:50 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE FBC 107.2.1: | | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED | | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | NO PLAN SUBMITTED. | | | | 2. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR | | THE DOORS AND WINDOWS, FAC9N-3. | | | | 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR | | THE ROOF SHINGLES. PROVIDE ROOF HEIGHT AND SLOPE. A | | SEPARATE ROOF SUB PERMIT IS REQUIRED. | | | | 4. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR | | LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR | | SIZE. | | | | 5. SHOW LOCATION OF PROPOSED NEW DOORS ON THE FLOOR | | PLAN, FBC 107. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2013-06-12 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-06-12 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-06-12 |
Time |
15:11 |
Sent To |
|
|
Notes |
2013-06-12 15:12:08 | 6-12-13 | | CORRECTIONS MADE. | | VB |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2013-03-06 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-03-06 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-03-06 |
Time |
13:45 |
Sent To |
|
|
Notes |
2013-03-06 13:45:57 | 13020218 | | 920 15TH UNITS A AND B | | RESIDENTIAL REPAIR | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL | | RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING, | | FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION | | AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL | | PANEL WITH REQUIRED SAFE WORKING CLEARANCES. | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING | | OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC | | 215.5, 210.50, 110.26 | | | | SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES, | | PANEL BOARDS, METERS ETC. FBC 107.2.1 | | | | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI | | PROTECTED. NEC 210.8 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-02-25 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-02-25 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-02-25 |
Time |
14:59 |
Sent To |
|
|
Notes |
2013-02-25 15:15:06 | 13020218 | | 920 15TH UNITS A AND B | | RESIDENTIAL REPAIR | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL | | RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING, | | FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION | | AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL | | PANEL WITH REQUIRED SAFE WORKING CLEARANCES. | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING | | OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC | | 215.5, 210.50, 110.26 | | | | SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES, | | PANEL BOARDS, METERS ETC. FBC 107.2.1 | | | | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI | | PROTECTED. NEC 210.8 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2013-07-11 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-07-11 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-07-11 |
Time |
11:35 |
Sent To |
|
|
Notes |
2013-07-11 11:36:31 | WINDOWS SHALL HAVE WHITE FRAMES, CLEAR GLASS AND BE | | 1/1/ SINGLE HUNG PER HCD HISTORIC REVIEW DATED 3/3/13. | | QUESTIONS CONTACT FRIEDERIKE MITTNER CITY, HISTORIC | | PRESERVATION PLANNER AT 822-1457. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2013-02-20 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-02-20 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-02-13 |
Time |
17:43 |
Sent To |
|
|
Notes |
2013-02-13 17:44:10 | NOT SURE IF HISTORIC IS NEEDED OR NOT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2013-07-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-07-11 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-06-06 |
Time |
11:53 |
Sent To |
|
|
Notes |
2013-06-08 11:57:09 | *HCD EXPEDITED* | | R--2 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-06-08 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2013-03-06 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2013-02-26 |
Time |
10:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-02-25 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-02-25 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-02-08 |
Time |
10:23 |
Sent To |
|
|
Notes |
2013-02-21 13:43:40 | 2/21 TO MECHANICAL | | | 2013-02-11 10:25:46 | SENT TO MISC 1 BOX PER L MARTINEZ. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-07-10 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-07-10 |
Time |
14:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2013-03-05 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-03-05 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-03-05 |
Time |
13:26 |
Sent To |
E |
|
Notes |
2013-03-05 13:47:29 | PLANS DENIED | | SAME AS LAST REVIEW . NEED PLANS, ENERGY CALCULATIONS | | AND | | HEAT LOADS. PER SECTION 107 FBC 2010 | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2013-02-25 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-02-25 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-02-25 |
Time |
13:30 |
Sent To |
|
|
Notes |
2013-02-25 13:36:24 | DENIED | | 1) ANY NEW MECHANICAL WORK REQUIRES MECHANICAL PLANS. | | PER SECTION 107.3.5.3 (10) AND (13) 2010 FBC. | | 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS.2010 FBC. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2013-07-08 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-07-08 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-07-08 |
Time |
11:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2013-06-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-06-27 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-06-27 |
Time |
07:15 |
Sent To |
|
|
Notes |
2013-06-27 07:15:29 | GAF ROYAL SOVEREIGN SHINGLE | | 12-0313.11 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2013-02-11 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2013-02-11 |
Time |
|
Rev Time |
|
Received By |
mdekle |
Date |
2013-02-11 |
Time |
|
Sent To |
|
|
Notes |
|
|