Plan Review Details - Permit 13020218
Plan Review Stops For Permit 13020218
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-28 Cont ID  
Sent By shill Date 2013-06-28 Time 07:32 Rev Time 0.00
Received By shill Date 2013-06-28 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 16:34 Rev Time 0.00
Received By shill Date 2013-02-26 Time 16:34 Sent To M
Notes
2013-02-26 16:34:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. SEE FBC 107.2.1:
  
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 NO PLAN SUBMITTED.
  
 2. OK
  
 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE ROOF SHINGLES. PROVIDE ROOF HEIGHT AND SLOPE. A
 SEPARATE ROOF SUB PERMIT IS REQUIRED.
  
 4. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR
 LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR
 SIZE.
  
 5. SHOW LOCATION OF PROPOSED NEW DOORS ON THE FLOOR
 PLAN, FBC 107.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-21 Cont ID  
Sent By shill Date 2013-02-21 Time 13:25 Rev Time 0.00
Received By shill Date 2013-02-21 Time 13:24 Sent To M
Notes
2013-02-21 13:34:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. SEE FBC 107.2.1:
  
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 NO PLAN SUBMITTED.
  
 2. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE DOORS AND WINDOWS, FAC9N-3.
  
 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE ROOF SHINGLES. PROVIDE ROOF HEIGHT AND SLOPE. A
 SEPARATE ROOF SUB PERMIT IS REQUIRED.
  
 4. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR
 LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR
 SIZE.
  
 5. SHOW LOCATION OF PROPOSED NEW DOORS ON THE FLOOR
 PLAN, FBC 107.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-06-12 Cont ID  
Sent By dharvey Date 2013-06-12 Time 15:11 Rev Time 0.00
Received By dharvey Date 2013-06-12 Time 15:11 Sent To  
Notes
2013-06-12 15:12:086-12-13
 CORRECTIONS MADE.
 VB

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-03-06 Cont ID  
Sent By rlecky Date 2013-03-06 Time 13:45 Rev Time 0.00
Received By rlecky Date 2013-03-06 Time 13:45 Sent To  
Notes
2013-03-06 13:45:5713020218
 920 15TH UNITS A AND B
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By rlecky Date 2013-02-25 Time 15:15 Rev Time 0.00
Received By rlecky Date 2013-02-25 Time 14:59 Sent To  
Notes
2013-02-25 15:15:0613020218
 920 15TH UNITS A AND B
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-07-11 Cont ID  
Sent By fmittner Date 2013-07-11 Time 11:35 Rev Time 0.00
Received By fmittner Date 2013-07-11 Time 11:35 Sent To  
Notes
2013-07-11 11:36:31WINDOWS SHALL HAVE WHITE FRAMES, CLEAR GLASS AND BE
 1/1/ SINGLE HUNG PER HCD HISTORIC REVIEW DATED 3/3/13.
 QUESTIONS CONTACT FRIEDERIKE MITTNER CITY, HISTORIC
 PRESERVATION PLANNER AT 822-1457.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-02-20 Cont ID  
Sent By fmittner Date 2013-02-20 Time 17:01 Rev Time 0.00
Received By fmittner Date 2013-02-13 Time 17:43 Sent To  
Notes
2013-02-13 17:44:10NOT SURE IF HISTORIC IS NEEDED OR NOT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-11 Cont ID  
Sent By shill Date 2013-07-11 Time 14:26 Rev Time 0.00
Received By shill Date 2013-06-06 Time 11:53 Sent To  
Notes
2013-06-08 11:57:09*HCD EXPEDITED*
 R--2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-08 Cont ID  
Sent By lmartine Date 2013-03-06 Time 11:52 Rev Time 0.00
Received By lmartine Date 2013-02-26 Time 10:12 Sent To  
Notes
2013-02-26 10:13:06TO SH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:36 Rev Time 0.00
Received By hmoser Date 2013-02-08 Time 10:23 Sent To  
Notes
2013-02-21 13:43:402/21 TO MECHANICAL
  
2013-02-11 10:25:46SENT TO MISC 1 BOX PER L MARTINEZ.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By hmoser Date 2013-07-10 Time 14:48 Rev Time 0.00
Received By hmoser Date 2013-07-10 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-03-05 Cont ID  
Sent By hmoser Date 2013-03-05 Time 13:26 Rev Time 0.00
Received By hmoser Date 2013-03-05 Time 13:26 Sent To E
Notes
2013-03-05 13:47:29PLANS DENIED
 SAME AS LAST REVIEW . NEED PLANS, ENERGY CALCULATIONS
 AND
 HEAT LOADS. PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:30 Rev Time 0.00
Received By hmoser Date 2013-02-25 Time 13:30 Sent To  
Notes
2013-02-25 13:36:24DENIED
 1) ANY NEW MECHANICAL WORK REQUIRES MECHANICAL PLANS.
 PER SECTION 107.3.5.3 (10) AND (13) 2010 FBC.
 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-07-08 Cont ID  
Sent By lwagner Date 2013-07-08 Time 11:14 Rev Time 0.00
Received By lwagner Date 2013-07-08 Time 11:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By shill Date 2013-06-27 Time 07:15 Rev Time 0.00
Received By shill Date 2013-06-27 Time 07:15 Sent To  
Notes
2013-06-27 07:15:29GAF ROYAL SOVEREIGN SHINGLE
 12-0313.11
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By mdekle Date 2013-02-11 Time   Rev Time  
Received By mdekle Date 2013-02-11 Time   Sent To  
Notes
***NONE***