Plan Review Stops For Permit 13020210
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-05-23 Cont ID  
Sent By JWITMER Date 2013-05-23 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 07:04 Sent To  
Notes
2013-05-23 07:46:55BUILDING PLAN REVIEW
 PERMIT:13020210
 ADD: 701 S ROSEMARY AVE. SUITE # NOT PROVIDED
 CONT: LAKEVIEW CONSTRUCTION
 TEL: (561)635-6935
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 CITY PLACE MANAGEMENT
 CARLOS BERNEL
 561-820-0074
  
 WIND DESIGN: FACTORY MUTUAL PRESSURES OK!
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-26 Cont ID  
Sent By jwitmer Date 2013-04-26 Time 12:52 Rev Time 0.00
Received By jwitmer Date 2013-04-26 Time 12:08 Sent To  
Notes
2013-04-26 12:15:15BUILDING PLAN REVIEW
 PERMIT:13020210
 ADD: 701 S ROSEMARY AVE. SUITE # NOT PROVIDED
 CONT: LAKEVIEW CONSTRUCTION
 TEL: (561)635-6935
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 CITY PLACE MANAGEMENT
 CARLOS BERNEL
 561-820-0074
  
 2ND REVIEW
 DATE: 04/26/2013
 ACTION: DENIED
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. NO
 TRANSMITTAL LETTER WAS SUBMITTED
 FOR BUILDINGS FIRST ROUND OF COMMENTS.
  
 ADDRESS: THIS PERMIT HAS NOT BEEN PROVIDED WITH THE
 TENANT SUITE NUMBER. ON THE PERMIT APPLICATION AS WELL
 AS PLANS H & M'S OWN STORE NUMBER US 316 HAS BEEN
 MISTAKEN AS THE SUITE NUMBER. PLEASE CORRECT THE PERMIT
 APPLICATION AND PLANS AND PROVIDE THE TENANT SUITE
 NUMBER.
  
 1) 2ND REQUEST. THE COVER SHEET INDICATES ALL
 STOREFRONT TO BE FILED UNDER SEPERATE PERMIT. PLEASE
 REMOVE THE MENTION OF STOREFRONT FROM THESE PLANS SINCE
 IT IS NOT PART OF THIS PERMIT. TODATE NO SUCH PERMIT
 HAS BEEN APPLIED FOR.
 2010 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED... EXAMPLES ARE A200.00
 NOTE # 1 & A-600.00 ELEVATIONS.
  
 2) 2ND REQUEST. SHEET A-200.00 THE TENANT SEPERATION
 WALLS:
 2A) SHEETS 700.00 - 703.00 PROVIDE THE WALL TYPES THAT
 WERE IDENTIFIIED ON A-200.00. A COMMON NOTE ON WALL
 SECTION TYPES ALIGN STUD KNOCK OUTS. ARE THESE DETAILS
 INDICATING NEW WALLS NEXT TO THE EXISTING TENANT
 SEPERATION WALLS WHERE THE STUD KNOK OUTS CAN BE
 ALIGNED OR IS THE 5/8 INCH FIRE RATED DRYWALL BEING
 REMOVED TO PUNCH NEW HOLES IN WHERE THEY DO NOT ALIGN?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2B) THE WALL TAGS FOR THE TENAT SEPERATION WALLS ARE TO
 BE 1 HOUR PER 2010 FBC-B 709.6.1. ON THE SHEETS 700.00-
 702.00 THEY DO NOT INDICATE THEY ARE ONE HOUR FIRE
 RATED. WALL TYPES L & P ARE INDICATED AS ONE HOUR
 WALLS, WHY ARE THE OTHER WALL TAGS FOUND ON THE TENANT
 SEPERATION DESIGNATED AS ONE HOUR?
  
 2C) VARIOUS WALLS INDICATE BEING FURRED OUT WITH FIRE
 RETARDANT TREATED 3/4 INCH PLYWOOD, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 803.11.1 PLEASE PROVIDE
 WHICH OF THE THREE OPTIONS WILL BE INSTALLED AT THE
 SITE.
  
 3) 2ND REQUEST. SHEET S010.00 DO PROVIDE THE WIND
 DESIGN CRITERIA IF THE WINDOWS ARE TO BE PART OF THIS
 PERMIT. IF THE WINDOWS ARE TO BE INSTALLED AS PART OF
 THIS PERMIT THEN THE PRESSURES WILL NEED TO BE PROVIDED
 FOR THESE OPENINGS AND TTHE HEIGHT FACTOR FOR A THREE
 STORY BUILDING.
 THE PLANS INDICATE THE BUILDING TO BE 15 FEET TALL WITH
 ASSOCIATED PRESSURES. 2010 FBC-B TABLE 1609.7(2).
  
 4) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-28 Cont ID  
Sent By jwitmer Date 2013-02-28 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2013-02-28 Time 08:05 Sent To  
Notes
2013-02-28 11:24:47BUILDING PLAN REVIEW
 PERMIT:13020210
 ADD: 701 S ROSEMARY AVE. SUITE # 316
 CONT: LAKEVIEW CONSTRUCTION
 TEL: (561)635-6935
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 02/28/2013
 ACTION: DENIED
  
 1) THE COVER SHEET INDICATES ALL STOREFRONT TO BE FILED
 UNDER SEPERATE PERMIT. PLEASE REMOVE THE MENTION OF
 STOREFRONT FROM THESE PLANS SINCE IT IS NOT PART OF
 THIS PERMIT.
 2010 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED... EXAMPLES ARE A200.00
 NOTE # 1 & A-600.00 ELEVATIONS.
  
 2) SHEET A-200.00 THE TENANT SEPERATION WALLS:
 2A) SHEETS 700.00 - 703.00 PROVIDE THE WALL TYPES THAT
 WERE IDENTIFIIED ON A-200.00. A COMMON NOTE ON WALL
 SECTION TYPES ALIGN STUD KNOCK OUTS. ARE THESE DETAILS
 INDICATING NEW WALLS NEXT TO THE EXISTING TENANT
 SEPERATION WALLS WHERE THE STUD KNOK OUTS CAN BE
 ALIGNED OR IS THE 5/8 INCH FIRE RATED DRYWALL BEING
 REMOVED TO PUNCH NEW HOLES IN WHERE THEY DO NOT ALIGN?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2B) THE WALL TAGS FOR THE TENAT SEPERATION WALLS ARE TO
 BE 1 HOUR PER 2010 FBC-B 709.6.1. ON THE SHEETS 700.00-
 702.00 THEY DO NOT INDICATE THEY ARE ONE HOUR FIRE
 RATED. WALL TYPES L & P ARE INDICATED AS ONE HOUR
 WALLS, WHY ARE THE OTHER WALL TAGS FOUND ON THE TENANT
 SEPERATION DESIGNATED AS ONE HOUR?
  
 2C) VARIOUS WALLS INDICATE BEING FURRED OUT WITH FIRE
 RETARDANT TREATED 3/4 INCH PLYWOOD, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 803.11.1 PLEASE PROVIDE
 WHICH OF THE THREE OPTIONS WILL BE INSTALLED AT THE
 SITE.
  
 3) SHEET S010.00 DO PROVIDE THE WIND DESIGN CRITERIA IF
 THE WINDOWS ARE TO BE PART OF THIS PERMIT. IF THE
 WINDOWS ARE TO BE INSTALLED AS PART OF THIS PERMIT THEN
 THE PRESSURES WILL NEED TO BE PROVIDED FOR THESE
 OPENINGS AND TTHE HEIGHT FACTOR FOR A THREE STORY
 BUILDING. 2010 FBC-B TABLE 1609.7(2).
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) SHEET SHEET S110.00 IS FOR BAR JOIST ROOF FRAMING
 AND DETAILS FOR TYPICAL ROOFTOP MECHANICAL UNITS AND
 OPENINGS THAT ARE NEW AND BEING CUT INTO THE ROOF DECK.
 WHY IS THIS SHEET INCLUDED IN THESE PLANS, THERE IS TWO
 STORIES OF R-2 AND BUSINESS OCCUPANCIES BETWEEN THE
 FIRST FLOOR AND THE ROOF? IF ADDITIONAL AC UNITS ARE TO
 BE ADDED THEY WOULD PROBABBLY BE SPLIT UNITS WITH THE
 CONDENSORS ON THE ROOF. IN THAT CASE THE PRE-ENGINEERED
 A/C STANDS WOULD NEED PRODUCT APPROVALS FOR THE WIND
 SPEED AND EXPOSURE CATEGORY PLUS THE DETAILS FOR
 FASTENING OF THE UNIT TO THE ROOF DECK AND OR BAR
 JOIST. PLEASE BE AWARE OF 1609.8 ROOF TOP STRUCTURES
 AND EQUIPMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 16:20 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 16:20 Sent To  
Notes
2013-05-03 16:20:49ALL CORECTIONS HAVE BEEN MADE.....

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By rlecky Date 2013-03-07 Time 13:57 Rev Time 0.00
Received By rlecky Date 2013-03-06 Time 14:41 Sent To  
Notes
2013-03-07 13:59:0713020210
 701 S. ROSEMARY AVENUE #316
 H&M BUILDING RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR
 FLASH PROTECTION, HIGH-LEG MARKING, PANEL BOARDS AND
 THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION T505.3
  
 INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED
 TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE MDP. NEC
 314.28
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE SYSTEMS,
 AUDIO , SECURITY, FIRE ALARM, DATA, POS, ETC.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-05-22 Cont ID  
Sent By WJOLIN Date 2013-05-22 Time 11:48 Rev Time 0.00
Received By wjolin Date 2013-05-22 Time 11:17 Sent To  
Notes
2013-05-22 11:31:34701 SOUTH ROSEMARY AVENUE - SUITE #151
 PERMIT #13020210
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 H&M WILL BE RESPONSIBLE FOR ESTABLISHING AND
 IMPLEMENTING WRITTEN PROCEDURES FOR MAINTAINING 36"
 WIDE UNOBSTRUCTED EGRESS AISLES AT ALL TIMES. A COPY OF
 THIS WRITTEN PROCEDURE SHALL BE PROVIDED TO THE FIRE
 INSPECTOR PRIOR TO ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY. IF FIRE INSPECTORS OBSERVE THAT THESE
 PROCEDURES ARE NOT BEING FOLLOWED, THE TENANT WILL BE
 REQUIRED TO PROVIDE FLOOR MARKINGS, BOLLARDS, OR
 DIFFERENT FLOORING MATERIAL SO EGRESS AISLES WILL
 ALWAYS BE READILY IDENTIFIABLE NO MATTER HOW THE
 MERCHANDISE AND DISPLAYS CHANGE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-22 Cont ID  
Sent By wjolin Date 2013-04-22 Time 14:10 Rev Time 0.00
Received By wjolin Date 2013-04-22 Time 13:32 Sent To  
Notes
2013-04-22 14:10:50701 SOUTH ROSEMARY AVENUE - SUITE #316
 PERMIT #13020210
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: RELIANCE ON THE TENANT TO MAINTAIN
 CLEAR AISLES HAS NOT BEEN SUCCESSFUL. PLEASE PROVIDE
 FLOOR MARKINGS, BOLLARDS, OR DIFFERENT FLOORING
 MATERIAL SO EGRESS AISLES WILL ALWAYS BE READILY
 IDENTIFIABLE NO MATTER HOW THE MERCHANDISE AND DISPLAYS
 CHANGE.
 ORIGINAL COMMENT: SHEET A-100: PLANS STATE THAT A CLEAR
 WIDTH OF 3'-0" AND 3'-8" IS TO BE MAINTAINED FOR
 EXITING; PLEASE INDICATE HOW THIS WILL BE ACCOMPLISHED
 AND MAINTAINED.
  
 RESPONSE COMMENT: THE FIRE PROTECTION INFORMATION FROM
 THE ORIGINAL COMMENT NEEDS TO BE SUBMITTED EVEN IF THE
 DESIGN IS A PERFORMANCE SPECIFICATION. FOR ISSUANCE OF
 A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SPRINKLER
 CONTRACTOR CAN THEN SUBMIT SHOP DRAWINGS (CONFORMING TO
 THE ENGINEERED CONSTRUCTION DOCUMENTS) FOR A
 SUB-PERMIT.
 ORIGINAL COMMENT: SHEET FP-210: PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By wjolin Date 2013-02-25 Time 12:49 Rev Time 0.00
Received By wjolin Date 2013-02-25 Time 10:29 Sent To  
Notes
2013-02-25 11:12:03701 SOUTH ROSEMARY AVENUE - SUITE #316
 PERMIT #13020210
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS OR SUITE NUMBERS PROVIDED IN THE PLAN
 TITLEBLOCK INFORMATION.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SHEET A-100: PLANS STATE THAT A CLEAR WIDTH OF 3'-0"
 AND 3'-8" IS TO BE MAINTAINED FOR EXITING; PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED AND MAINTAINED.
  
 SHEET A-800: THUMB-TURN STYLE DOOR LOCKS TO BE EQUIPPED
 WITH A LOCK/UNLOCK INDICATOR.
  
 SHEET FP-210: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-31 Cont ID  
Sent By lmartine Date 2013-05-30 Time 17:04 Rev Time 0.00
Received By lmartine Date 2013-05-20 Time 13:59 Sent To  
Notes
2013-05-20 14:07:17C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-03 Cont ID  
Sent By shill Date 2013-05-03 Time 16:45 Rev Time 0.00
Received By shill Date 2013-04-09 Time 17:04 Sent To  
Notes
2013-04-11 17:05:14SENT TO C5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-12 Cont ID  
Sent By shill Date 2013-03-12 Time 14:41 Rev Time 0.00
Received By shill Date 2013-02-08 Time 14:45 Sent To  
Notes
2013-02-11 14:45:23C04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-05-30 Cont ID  
Sent By MOSER Date 2013-05-30 Time 10:31 Rev Time 0.00
Received By hmoser Date 2013-05-30 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-04-24 Cont ID  
Sent By hmoser Date 2013-04-24 Time 11:36 Rev Time 0.00
Received By hmoser Date 2013-04-23 Time 14:08 Sent To  
Notes
2013-04-24 11:35:53PLANS DENIED
 1) ROOF TOP UNITS ARE NOT EXISTING. PLEASE WRIGHT ON
 PLANS SUPPLY BY OTHERS.
 2) REFER TO SECTION 607.1.5 FIRE WALLS FBC (M) 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By hmoser Date 2013-03-12 Time 14:24 Rev Time 0.00
Received By hmoser Date 2013-03-12 Time 14:24 Sent To  
Notes
2013-03-12 14:41:28****CORRECTIONS****
  
 1. REVISE PLAN TO SHOW HOW DUCTWORK WILL BE ROUTED
 THROUGH TWO STORIES OF EXISTING APARTMENTS TO THE
 PROPOSED NEW RTUS.
  
 2. REVISE THE CURB DETAIL ON SHEET 301.12 TO SPECIFY
 FASTENERS, FBC MECHANICAL 301.12.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-18 Cont ID  
Sent By lwagner Date 2013-04-18 Time 11:11 Rev Time 0.00
Received By lwagner Date 2013-04-18 Time 10:49 Sent To  
Notes
2013-04-18 11:11:52RE-STAMPED
2013-04-11 16:40:06NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-27 Cont ID  
Sent By lwagner Date 2013-02-27 Time 10:57 Rev Time 0.00
Received By lwagner Date 2013-02-26 Time 13:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-30 Cont ID  
Sent By ESCHNEID Date 2013-05-30 Time 15:31 Rev Time 0.50
Received By eschneid Date 2013-05-30 Time 15:31 Sent To  
Notes
2013-05-30 15:32:45PER THE PLANS, SEPARATE PERMITS WILL BE SUPPLIED FOR:
  
 A. SIGNS
 B. EXTERIOR ARCADE STOREFRONT
  
 SEE PERMIT NO. 13020353 FOR ROOFTOP SIGHT LINES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-04-25 Cont ID  
Sent By eschneid Date 2013-04-25 Time 09:27 Rev Time 0.75
Received By eschneid Date 2013-04-24 Time 17:10 Sent To  
Notes
2013-04-25 09:34:55FAILED
  
 1) REPEAT COMMENT: THERE IS NEW EQUIPMENT BEING
 INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE
 DRI, ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT
 NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY
 SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR
 CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND
 EQUIPMENT LOCATION. PLEASE PROVIDE PLANS OR OTHER
 EVIDENCE THAT THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL
 BE SCREENED FROM PUBLIC VIEW. THIS IS REQUIRED EVEN
 THOUGH THE PLANS STATE THAT THE LANDLORD WILL BE
 SUBMITTING SEPARATE PLANS FOR THE ROOFTOP MECHANICAL
 EQUIPMENT. STAFF NEEDS TO VERIFY THAT THE ROOF
 PENETRATIONS, CURBS, ETC. ARE NOT PLACED IN A LOCATION
 THAT WILL CREATE ISSUES FOR THE FUTURE A/C UNITS.
  
 2) PER THE PLANS, SEPARATE PERMITS WILL BE SUPPLIED
 FOR:
  
 A. SIGNS
 B. STOREFRONT
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-03-05 Cont ID  
Sent By escheide Date 2013-03-05 Time 13:47 Rev Time 1.00
Received By eschneid Date 2013-03-05 Time 13:47 Sent To  
Notes
2013-03-05 13:48:05FAILED
  
 1) THERE IS NEW EQUIPMENT BEING INSTALLED ON THE ROOF.
 IN ACCORDANCE WITH THE CITYPLACE DRI, ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT
 THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED
 FROM PUBLIC VIEW.
  
 2) SIGNS REQUIRE SEPARATE PERMIT(S).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 2/21/13
2013-02-26 14:42:372/26/13