Plan Review Details - Permit 13010955
Plan Review Stops For Permit 13010955
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-03-16 Cont ID  
Sent By wjolin Date 2013-03-16 Time 16:27 Rev Time 0.00
Received By wjolin Date 2013-03-16 Time 16:19 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-02-23 Cont ID  
Sent By wjolin Date 2013-02-23 Time 11:18 Rev Time 0.00
Received By wjolin Date 2013-02-23 Time 10:55 Sent To M
Notes
2013-02-23 11:18:49477 SOUTH ROSEMARY AVENUE - SUITE #169
 PERMIT #13010955
 MASTER #12100295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ORIGINAL COMMENT:THE FIRE PROTECTION ENGINEER OF RECORD
 (DINO PAPPAS) ON THE CONSTRUCTION DOCUMENTS (SHEET FP1)
 INDICATES THE SYSTEM SHALL BE DESIGNED FOR ORDINARY
 HAZARD GROUP II. THE SPRINKLER SHOP DRAWINGS INDICATE
 THE SYSTEM IS DESIGNED FOR LIGHT HAZARD.
 RESPONSE COMMENT: THE LETTER FROM MR. PAPPAS (P.E.) IS
 NOT SEALED AND THEREFORE CANNOT BE ACCEPTED AS CHANGING
 THE DESIGN CRITERIA PER FLORIDA STATUTES. ADDITIONALLY,
 FIRE PROTECTION NOTE #3 ON SHEET FP1 CLEARLY STATES,
 "THE SYSTEM SHALL BE DESIGNED FOR ORDINARY HAZARD GROUP
 II." A REVISION TO (SHEET FP1) OF THE ENGINEERING
 CONSTRUCTION DOCUMENTS NEEDS TO BE SUBMITTED
 (SIGNED/SEALED) BY THE ENGINEER.
  
 REPEAT COMMENT: NO WATER SUPPLY INFORMATION INDICATED
 ON THE PLANS.
  
 REPEAT COMMENT: NO HORIZONTAL SIDEWALL SPRINKLER
 INFORMATION PROVIDED IN THE SPRINKLER SCHEDULE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-05 Cont ID  
Sent By wjolin Date 2013-02-05 Time 10:29 Rev Time 0.00
Received By wjolin Date 2013-02-05 Time 08:58 Sent To M
Notes
2013-02-05 10:29:16477 SOUTH ROSEMARY AVENUE - SUITE #169
 PERMIT #13010955
 MASTER #12100295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE FIRE PROTECTION ENGINEER OF RECORD (DINO PAPPAS) ON
 THE CONSTRUCTION DOCUMENTS (SHEET FP1) INDICATES THE
 SYSTEM SHALL BE DESIGNED FOR ORDINARY HAZARD GROUP II.
 THE SPRINKLER SHOP DRAWINGS INDICATE THE SYSTEM IS
 DESIGNED FOR LIGHT HAZARD.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE BELOW THE STRUCTURE/ROOF DECK (IF
 OBSTRUCTED CONSTRUCTION).
  
 NO WATER SUPPLY INFORMATION OR HYDRAULIC CALCULATIONS
 SUBMITTED.
  
 NO HORIZONTAL SIDEWALL SPRINKLER INFORMATION PROVIDED
 IN THE SPRINKLER SCHEDULE.
  
 INDICATE THE REASON FOR THE EXPOSED PIPE/DROP NIPPLE IN
 HEAD DETAIL #3.
  
 THE SPRINKLERS IN THE CEILING CLOUDS (8'-6" AFF) ALONG
 COLUMN LINE 8 ARE LOCATED MORE THAN 7'-6" FROM ONE
 EDGE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 10:06 Rev Time 0.00
Received By hmoser Date 2013-03-13 Time 09:17 Sent To  
Notes
2013-03-13 09:18:00SENT TO FIRE BOX.JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-27 Cont ID  
Sent By hmoser Date 2013-02-27 Time 15:39 Rev Time 0.00
Received By hmoser Date 2013-02-22 Time 16:34 Sent To  
Notes
2013-02-22 16:34:30TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 13:04 Rev Time 0.00
Received By hmoser Date 2013-01-31 Time 17:22 Sent To  
Notes
2013-01-31 17:22:54TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 10:06 Rev Time 0.00
Received By hmoser Date 2013-03-25 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-02-27 Cont ID  
Sent By hmoser Date 2013-02-27 Time 15:36 Rev Time 0.00
Received By hmoser Date 2013-02-27 Time 15:36 Sent To  
Notes
2013-02-27 15:39:05PLANS DENIED
 REFER TO COMMENTS FROM FIRE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 13:04 Rev Time 0.00
Received By hmoser Date 2013-02-06 Time 12:58 Sent To  
Notes
2013-02-06 13:04:23PLANS DENIED
 REFER TO NOTES FROM FIRE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]