Plan Review Details - Permit 13010915
Plan Review Stops For Permit 13010915
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-02-20 Cont ID  
Sent By shill Date 2013-02-20 Time 11:26 Rev Time 0.00
Received By shill Date 2013-02-20 Time 11:26 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-07 Cont ID  
Sent By shill Date 2013-02-07 Time 19:21 Rev Time 0.00
Received By shill Date 2013-02-07 Time 19:21 Sent To FIRE
Notes
2013-02-07 19:31:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE SHEET 6 OF THE PRODUCT APPROVAL. PROVIDE THE
 PRODUCT APPROVAL FOR THE DOOR AS THIS IS NOT INCLUDED
 IN THE PRODUCT APPROVAL SUBMITTED, FAC9N-3, FBC 1609.
  
 2. PROVIDE THE DIMENSIONS (APPROXIMATE) OF THE SIDE
 LITES. THEY MUST BE WITHIN THE LIMITATIONS OF THE
 PRODUCT APPROVAL, FBC 1609.
  
 3. AS THIS STRUCTURE IS A CHURCH, PANIC DEVICES MAY BE
 REQUIRED FBC1008.1.10.
  
 IF PANIC DEVICES ARE TO BE INSTALLED, THIS IS TO BE
 INCLUDED IN THE PRODUCT APPROVAL. REVISE THE PLAN TO
 INDICATE PANIC HARDWARE FOR THE DOOR.
  
 IF PANIC DEVICES ARE NOT PROPOSED, PROVIDE A LIFE
 SAFETY PLAN FOR ALL AREAS WHICH THIS CORRIDOR SERVES -
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3, OCCUPANT LOAD
 FBC 1004, SIZE OF EACH AREA FBC 1004, AND ANY OTHER
 INFORMATION REQUIRED TO SHOW CODE COMPLIANCE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-02-23 Cont ID  
Sent By wjolin Date 2013-02-23 Time 10:52 Rev Time 0.00
Received By wjolin Date 2013-02-23 Time 10:50 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 10:12 Rev Time 0.00
Received By wjolin Date 2013-02-12 Time 10:06 Sent To B
Notes
2013-02-12 10:12:201400 PALM BEACH LAKES BOULEVARD
 PERMIT #13010915
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR ASSEMBLY OCCUPANCIES (CHURCH) WITH AN OCCUPANT LOAD
 OF 100 OR MORE PERSONS, PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-25 Cont ID  
Sent By shill Date 2013-02-25 Time 10:35 Rev Time 0.00
Received By shill Date 2013-02-13 Time 09:41 Sent To  
Notes
2013-02-20 11:26:532/20 TO FIRE BOX
  
2013-02-14 09:42:42SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-12 Cont ID  
Sent By shill Date 2013-02-12 Time 11:25 Rev Time 0.00
Received By shill Date 2013-01-30 Time 08:57 Sent To  
Notes
2013-01-31 08:57:38SENT TO MISCELLANEOUS SHELF #1 FOR REVIEW. JG.