Plan Review Details - Permit 13010915
Plan Review Stops For Permit 13010915 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-02-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-20 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-20 |
Time |
11:26 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-02-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-07 |
Time |
19:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-07 |
Time |
19:21 |
Sent To |
FIRE |
|
Notes |
2013-02-07 19:31:18 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. SEE SHEET 6 OF THE PRODUCT APPROVAL. PROVIDE THE | | PRODUCT APPROVAL FOR THE DOOR AS THIS IS NOT INCLUDED | | IN THE PRODUCT APPROVAL SUBMITTED, FAC9N-3, FBC 1609. | | | | 2. PROVIDE THE DIMENSIONS (APPROXIMATE) OF THE SIDE | | LITES. THEY MUST BE WITHIN THE LIMITATIONS OF THE | | PRODUCT APPROVAL, FBC 1609. | | | | 3. AS THIS STRUCTURE IS A CHURCH, PANIC DEVICES MAY BE | | REQUIRED FBC1008.1.10. | | | | IF PANIC DEVICES ARE TO BE INSTALLED, THIS IS TO BE | | INCLUDED IN THE PRODUCT APPROVAL. REVISE THE PLAN TO | | INDICATE PANIC HARDWARE FOR THE DOOR. | | | | IF PANIC DEVICES ARE NOT PROPOSED, PROVIDE A LIFE | | SAFETY PLAN FOR ALL AREAS WHICH THIS CORRIDOR SERVES - | | OCCUPANCY CLASSIFICATION FBC CHAPTER 3, OCCUPANT LOAD | | FBC 1004, SIZE OF EACH AREA FBC 1004, AND ANY OTHER | | INFORMATION REQUIRED TO SHOW CODE COMPLIANCE. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2013-02-23 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-02-23 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-02-23 |
Time |
10:50 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2013-02-12 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-02-12 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-02-12 |
Time |
10:06 |
Sent To |
B |
|
Notes |
2013-02-12 10:12:20 | 1400 PALM BEACH LAKES BOULEVARD | | PERMIT #13010915 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FOR ASSEMBLY OCCUPANCIES (CHURCH) WITH AN OCCUPANT LOAD | | OF 100 OR MORE PERSONS, PANIC HARDWARE SHALL BE | | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER | | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE | | RELEASED BY THE PANIC HARDWARE. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-02-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-25 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-02-13 |
Time |
09:41 |
Sent To |
|
|
Notes |
2013-02-20 11:26:53 | 2/20 TO FIRE BOX | | | 2013-02-14 09:42:42 | SENT TO SAMANTHA'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-02-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-02-12 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-01-30 |
Time |
08:57 |
Sent To |
|
|
Notes |
2013-01-31 08:57:38 | SENT TO MISCELLANEOUS SHELF #1 FOR REVIEW. JG. |
|
|
|