Plan Review Details - Permit 13010720
Plan Review Stops For Permit 13010720
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By J WITMER Date 2013-07-10 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 10:06 Sent To  
Notes
2013-07-10 10:08:29TENANT BUILD OUT 2 SETS OF PLANS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-26 Cont ID  
Sent By WITMER Date 2013-04-26 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 09:08 Sent To  
Notes
2013-04-25 16:44:36BUILDING PLAN REVIEW
 PERMIT: 13010720
 ADD: 700 S ROSEMARY # 104
 CONT: TBD
 CONTACT: JORGE BENAVIDES
 TEL: (561)632-1900
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 APRIL 25/ 2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) SHEET A-0.0 & A-2.2 THE OCCUPANT LOAD COUNT IS TAKEN
 AS 50 SQ FT PER PERSON IS WITH EQUIPMENT, BOTH FIRE AND
 THE BUIULDING OFFICIAL CONCUR THAT THE MATS COULD BE
 REMOVED AND A HIGH OCCUPANT LOAD BE ACHIEVED SUCH AS
 LINE DANCING OR SOME SIMILAR ACTIVITY. FOR THE PURPOSE
 OF THIS REVIEW THE 15 SQ FT WILL BE USED FOR THE
 OCCUPANT LOAD COUNT. PLEASE CORRECT THE OCCUPANT LOAD
 AND REQUIRED EGRESS WIDTHS FOR THE SECOND FLOOR.
  
 4)2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4A) THE MONUMENTAL STAIR IS NOW BEING ASKED TO BE A
 PART OF A MEANS OF EGRESS. THE TENANT SPACE IS NOW A
 (A-3 OCCUPANCY) WHERE IT WAS NOT UNDER THE MERCANTILE
 OCCUPANCY. THE EXCEPTION FOR MONUMENTAL STAIRS IS FOUND
 UNDER 708.2 EXCEPTION # 7, THE MONUMENTAL STAIR NOT
 REQUIRED TO BE PART OF THE MEANS OF EGRESS BECAUSE
 THERE WERE 2 VERTICAL EXITS TO THE 2ND FLOOR.
  
 THE 2010 FBC-B SECTION 1028.2 (ASSEMBLY REQUIRES 50 %
 OF THE TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN
 ENTRANCE/ EXIT. ONE QUESTION IS HOW DO YOU GET THE
 OCCUPANTS TO THE SECOND FLOOR? THE ELEVATOR AND THE
 MONUMENTAL STAIR ARE THE ONLY WAY TO THE 2ND FLOOR.
  
 1028.3 ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE
 PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO
 ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED
 BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED
 AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH
 EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE
 AISLE. PLEASE PROVIDE CODE COMPLIANCE.
  
 ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT LOAD
 ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY 2010
 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON THE
 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL ALSO BE
 REQUIRED. FBC-B 708.2 EXCEPTION 7.2 STATES THAT IT "IS
 NOT PART OF A MEANS OF EGRESS SYSTEM.
  
 THE SECOND AREA TO CONSIDER IS IN SECTION FBC-B 1028.2
 THE 50% OF THE TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN
 ENTRANCE/ EXIT. HOW WOULD YOU GET THE 50 % OCCUPANT
 LOAD BACK THROUGH THE MAIN ENTRANCE IF YOU ARE
 CONSIDERING THE BACK ENTRANCE AS ONE OF TWO MAIN
 ENTRANCES. THE SECOND STORY NORTH EXIT TAKES YOU INTO
 AN EXIT PASSAGE WAY THEN YOU TAKE A VERTICAL EXIT AND
 OUT THE EXIT DOORWAY OR THE EXIT DISCHARGE, IT DOES NOT
 TAKE YOU BACK TO THE MAIN ENTRANCE EXIT.
  
 PLEASE REVIEW SECTION FBC-B 1027.1 EXCEPTION# 1, IF THE
 MONUMENTAL STAIR WERE TO BE ENCLOSED, IT DOES NOT NEED
 TO LEAD TO THE EXTERIOR OF THE BUILDING ONLY BE A 1
 HOUR RATED SHAFT WITH OPENING PROTECTIVES 1ST AND 2ND
 FLOOR, THIS WOULD SOLVE YOUR ISSUES WITH HOW YOU ARE
 GETTING OCCUPANTS TO THE 2ND FLOOR AND HOW 50 % OF THE
 OCCUPANTS ARE TRAVELING BACK TO THE MAIN ENTRANCE/
 EXIT, FOR EITHER ENTRANCE.
  
 4B) ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT
 LOAD ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY
 2010 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON
 THE 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL
 ALSO BE REQUIRED. PLEASE REVIEW THE OCCUPANT LOAD FOR
 THE AEROBICS ROOM THE OCCUPANT LOADS ARE TO BE
 CONSIDERED AT 15 NET, FBC-B 1004.1.1.
  
 5) THE PLANS DO PROVIDE A SECTION THROUGH THE
 MONUMENTAL STAIRWAY,INDICATING THE USE OF A DRAFT
 CURTAIN BUT FAIL TO INDICATE THE USE OF THE FIRE
 SPRINKLER LOCATION. NOT FOUND ON THE ARCHITECTURAL NOR
 THE LEVEL 1 FIRE SPRINKLER PLAN. 2010 FBC-B 708.2
 EXCEPTION 2.1. WHERE THE AREA OF THE FLOOR OPENING
 BETWEEN STORIES DOES NOT EXCEED TWICE THE HORIZONTAL
 PROJECTED AREA OF THE ESCALATOR OR STAIRWAY AND THE
 OPENING IS PROTECTED BY A DRAFT CURTAIN AND CLOSELY
 SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. IN OTHER
 THAN GROUPS B AND M, THIS APPLICATION IS LIMITED TO
 OPENINGS THAT DO NOT CONNECT MORE THAN FOUR STORIES.
 PLEASE NOTE THIS EXCEPTION IS ONLY FOR BUSINESS &
 MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE PROVIDE HOW
 THIS CODE VIOLATION WILL BE COMPLIED.
  
 6) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE
 THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND
 SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS,
 NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE
 BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER
 IS TAKING A 42 INCH DOOR AND STATING 200 OCCUPANTS CAN
 EXIT THIS OPENING, WHEREAS THE TWO VERTICAL EXITS BACK
 OF 2ND FLOOR WILL ONLY HANDLE 400 OCCUPANTS. PLEASE
 PROVIDE A LIFE SAFETY PLAN SHOWING THE EGRESS BACK OF
 HOUSE FOR THIS TENANT AND THE ADJACENT TENANTS AND
 PROVIDING A EGRESS PLAN TO THE PUBLIC WAY. PLEASE NOTE
 THE EGRESS PLAN ALSO HANDLES AN ACCESSIBLE RAMP, STAIRS
 OUTSIDE OF THE BUILDING, IT ALSO HAS TO TAKE INTO
 ACCOUNT THE ASSEMBLY OCCUPANCIES ON EITHER SIDE OF THIS
 NEWLY FORMED A3 OCCUPANCY.
  
 THE SAME REQUEST FOR A LIFE SAFETY PLAN FOR THE
 LANDLORD PERMIT FOR THIS SPACE HAS BEEN REQUESTED, THIS
 PERMIT WILL NOT BE ISSUED NOR THE LANDLORD TENANT
 IMPROVEMENT PERMIT UNTIL THIS ISSUE IS CLEARED UP. THE
 BACK OF HOUSE CORRIDORS ARE 1 HOUR EXIT PASSAGEWAYS,
 THAT HAVE TO BE TREATED AS SUCH AND THE EXITING HAS TO
 WORK FOR THE SHARED EXIT PASSAGE WAY.
  
 7-9) COMPLIED.
 10) STRUCTURAL WORK COMMENT # 10 TO BE COMPLETED UNDER
 THE LANDLORD PERMIT# 13030406.
  
 10A) IS THE EXTERIOR STAIR WORK FOUND ON S-1 AND
 EXTERIOR CANOPY WORK FOUND ON S-2 STILL PART OF THIS
 PERMIT OR PART OF THE LANDLORD PERMIT.
  
 11) PLANS ARE REQUIRED TO HAVE CITY PLACE APPROVAL WITH
 THEIR STAMP.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-06 Cont ID  
Sent By jwitmer Date 2013-02-06 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2013-02-05 Time 08:57 Sent To  
Notes
2013-02-06 09:59:30BUILDING PLAN REVIEW
 PERMIT: 13010720
 ADD: 700 S ROSEMARY # 104
 CONT: TBD
 CONTACT: JORGE BENAVIDES
 TEL: (561)632-1900
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-0.0 & A-2.2 BOTH INDICATE THIS TO BE A TYPE
 II BUILDING, UNDER THE 1997 SBC THIS WOULD HAVE BEEN
 CORRECT, IN THE 2004 FBC TYPE VI BUILDINGS WERE
 ELIMINATED AND A RECLASSIFICATION TOOK PLACE, THIS
 BUILDING IS CURRENTLY CLASSIFIED UNDER THE 2010 FBC-B
 AS A BUILDING TYPE IB. PLEASE CORRECT ALL SHEETS.
 FIGURE 600 CONSTRUCTION TYPE COMPARISION 2007 FBC-B
 COMMENTARY. PLEASE UPDATE.
  
 2) NEITHER SHEET A-0.0 NOR A-2.2 INDICATE THAT THIS
 TENANT SPACE IS A CHANGE OF OCCUPANCY. BARNES & NOBLE
 OCCUPIED THIS SPACE A MERCANTILE OCCUPANCY. LA FITNESS
 IS PROPOSING TO BECOME THE NEW TENANT, A A-3 OCCUPANCY.
 THE DESIGNER OF RECORD WILL NEED TO REVIEW THE 2010
 EXISTING BUILDING CODE 901.3.1 FOR BUILDINGS THAT ARE
 UNDER GOING A PARTIAL CHANGE OF OCCUPANCY, SECTION 912
 WILL APPLY.
  
 2A) THE DESIGNER OF RECORD SHALL ELECT TO DESSIGN THIS
 TENANT SPACE UNDER EITHER SECTION:
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
 2B) WHEN THE CONTRACTOR APPLIES FOR THE BUILDING
 PERMIT, UNDER THE HEADING, DESCRIPTION OF WORK, THE
 CONTRACTOR IS TO INCLUDE, "CHANGE OF OCCUPANCY".
  
 3) SHEET A-0.0 & A-2.2 THE OCCUPANT LOAD COUNT IS NOT
 CORRECT, ROOM ID 200 THE AEROBICS ROOM IT APPEARS THE
 USEE OF 50 SQ FT PER PERSON IS WITH EQUIPMENT, THE
 CORRECT USEAGE SHOULD EITHER BE 15 NET OR 7 NET. FOR
 THE PURPOSE OF THIS REVIEW THE 15 SQ FT WILL BE USED
 FOR THE OCCUPANT LOAD COUNT. PLEASE CORRECT THE
 OCCUPANT LOAD AND REQUIRED EGRESS WIDTHS ON BOTH
 SHEETS.
  
 4) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4A) THE MONUMENTAL STAIR IS NOW AN ISSUE (A-3
 OCCUPANCY) WHERE IT WAS NOT UNDER THE MERCANTILE
 OCCUPANCY. THE EXCEPTION FOR MONUMENTAL STAIRS IS FOUND
 UNDER 708.2 EXCEPTION # 7, THE MONUMENTAL STAIR NOT
 REQUIRED TO BE PART OF THE MEANS OF EGRESS BECAUSE
 THERE WERE 2 VERTICAL EXITS TO THE 2ND FLOOR.
  
 THE 2010 FBC-B SECTION 1028.2 REQUIRES 50 % OF THE
 TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN EXIT. 1028.3
 ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE
 PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO
 ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED
 BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED
 AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH
 EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE
 AISLE. PLEASE PROVIDE CODE COMPLIANCE.
  
 ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT LOAD
 ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY 2010
 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON THE
 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL ALSO BE
 REQUIRED.
  
 5) THE PLANS DO NOT PROVIDE A SECTION THROUGH THE
 MONUMENTAL STAIRWAY, PLEASE PROVIDE SUCH SECTION
 PROVIDING DETAILS SUCH AS DRAFT CURTAIN AND SPRINKLER
 LOCATION.
 2010 FBC-B 708.2 EXCEPTION 2.1. WHERE THE AREA OF THE
 FLOOR OPENING BETWEEN STORIES DOES NOT EXCEED TWICE THE
 HORIZONTAL PROJECTED AREA OF THE ESCALATOR OR STAIRWAY
 AND THE OPENING IS PROTECTED BY A DRAFT CURTAIN AND
 CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13.
 IN OTHER THAN GROUPS B AND M, THIS APPLICATION IS
 LIMITED TO OPENINGS THAT DO NOT CONNECT MORE THAN FOUR
 STORIES. PLEASE NOTE THIS EXCEPTION IS ONLY FOR
 BUSINESS & MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE
 PROVIDE HOW THIS CODE VIOLATION WILL BE COMPLIED.
  
 6) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE
 THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND
 SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS,
 NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE
 BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER
 IS TAKING A 36 INCH DOOR AND STATING 180 OCCUPANTS CAN
 EXIT THIS OPENING, WHEREAS THE CLEAR OPENING IS CLOSER
 TO 34 INCHES AND ONLY 170 OCCUPANTS CAN EXIT. FOR A
 PAIR OF DOUBLE DOORS 340 OCCUPANTS. THE BACK OF HOUSE
 SEERVICE CORRIDOR IS ALSO CONSIDERED A EXIT PASSAGEWAY
 SINCE IT IS A CONTINUATION OF THE VERTICAL EXIT. MANY
 OF THE DOORS IN THIS EXIT PASSAGEWAY DOORWAYS ARE NOT
 WIDE ENOUGH FOR THE NEW ASSEMBLY OCCUPANCIES THAT NOW
 EXIST. FOR EXAMPLE TO THE SOUTH THE SPACE WAS
 ORIGINALLY DESIGN FOR MERCANTILE OCCUPANCY, THIS IS NOW
 GOING TO BE A RESTRAUNT WITH DOUBLE THE OCCUPANT LOAD
 OF HOW THE EXIT PASSAGE WAY WAS DESIGNED. THE SAME HOLD
 TRUE JUST TO THE NORTH, A SECOND FLOOR NIGHTCLUB AND
 THE SECONDARY EXIT THAT LEADS TO THE EXIT STAIRS.
 PLEASE PROVIDE THE OCCUPANT LOADS THAT WILL SHARE THE
 EXITING FOR THIS COMMON EXIT PASSAGE WAY. PLEASE NOTE
 PART OF THE EXIT DISCHARGE A 4 FOOT WIDE SIDEWALK
 AND STAIRS., THE STAIRS WILL ONLY ALLOW FOR 160
 OCCUPANTS. PLEASE PROVIDE THE LIFE SAFETY PLANS TO THE
 PUBLIC WAY.
  
 7-9) COMPLIED.
 10) STRUCTURAL WORK COMMENT # 10 TO BE COMPLETED UNDER
 THE LANDLORD PERMIT# 13030406.
  
 11) PLANS ARE REQUIRED TO HAVE CITY PLACE APPROVAL WITH
 THEIR STAMP.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 14:13 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 13:43 Sent To  
Notes
2013-05-06 14:13:30PREVIOUS COMMENTS RESPONDED TO AND VERIFIED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 14:45 Rev Time 0.00
Received By rlecky Date 2013-02-22 Time 10:20 Sent To  
Notes
2013-02-22 14:46:3313010720
 700 S. ROSEMARY AVE #104
 L.A. FITNESS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 PANEL DSA REQUIRES A MAIN BREAKER. NEC 408.36
  
 OVERCURRENT PROTECTION OF TRANSFORMER T-DSA IS LIMITED
 TO 125% OF ITS CURRENT RATING. NEC TABLE 450.3(B)
  
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE TV, POS, AND FIRE ALARM SYSTEMS.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-23 Cont ID  
Sent By W JOLIN Date 2013-07-23 Time 14:05 Rev Time 0.00
Received By wjolin Date 2013-07-17 Time 17:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-11 Cont ID  
Sent By JOLIN Date 2013-04-11 Time 11:06 Rev Time 0.00
Received By wjolin Date 2013-04-08 Time 13:47 Sent To  
Notes
2013-04-08 15:14:46700 SOUTH ROSEMARY AVENUE - #104
 PERMIT #13010720
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THIS NOTE APPLIES TO CONSTRUCTION
 ACTIVITIES, NOT JUST DEMOLITION.
 ORIGINAL COMMENT: SHEET A0.2: ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 RESPONSE COMMENT: PROVIDE NOTE ON DRAWING.
 ORIGINAL COMMENT: SHEET A0.2: FIRE PROTECTION SYSTEMS
 SHALL REMAIN ACTIVE DURING DEMOLITION AND RENOVATION
 ACTIVITIES. IN THE EVENT A FIRE PROTECTION SYSTEM IS
 OUT OF SERVICE FOR MORE THAN 4-HOURS IN A 24-HOUR
 PERIOD, THE BUILDING SHALL BE PLACED UNDER A FIRE
 WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED IN
 WRITING (FAX: 561-804-4774) AND APPROVED BY THE OFFICE
 OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 RESPONSE COMMENT: ROLL-UP AEROBICS MATS ARE TOO EASILY
 REMOVED AND DO NOT CONSTITUTE "EQUIPMENT" IN MY
 OPINION. THIS ROOM SHOULD BE DESIGNED FOR THE WORST
 CASE SCENARIO OF 15 SQ.FT. PER PERSON.
 ORIGINAL COMMENT: SHEET A2.2: AEROBICS ROOM #200 IS
 USING AN OCCUPANT LOAD FACTOR OF 50 SQ.FT. PER PERSON
 WHILE AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON
 WOULD BE MORE APPROPRIATE AS THERE DOES NOT APPEAR TO
 BE ANY EXERCISE EQUIPEMENT IS THIS ROOM.
  
 RESPONSE COMMENT: ROLL-UP AEROBICS MATS ARE TOO EASILY
 REMOVED AND DO NOT CONSTITUTE "EQUIPMENT" IN MY
 OPINION. THIS ROOM SHOULD BE DESIGNED FOR THE WORST
 CASE SCENARIO OF 15 SQ.FT. PER PERSON.
 ORIGINAL COMMENT: SHEET A2.3: IF THE AEROBICS ROOM
 OCCUPANT LOAD IS REFACTORED USING AN OCCUPANT LOAD
 FACTOR OF 15 SQ.FT. PER PERSON, THE OCCUPANT LOAD ON
 THE SECOND FLOOR IS APPROXIMATELY 500 PERSONS AND WOULD
 RESULT IN A NEEDED EGRESS WIDTH OF 100 INCHES. THERE
 APPEARS TO ONLY BE 72 INCHES OF EGRESS WIDTH PROVIDED
 WITH ENTRY INTO TWO EXISTING EXIT STAIR TOWERS.
  
 RESPONSE COMMENT: DURING AN EMERGENCY, MANY OCCUPANTS
 WILL LEAVE THE SAME WAY THEY ENTERED (EMPHASIS
 APPLIED!) AS THIS IS MOST FAMILIAR TO THEM. THE
 PROPOSED EXITING SCHEME IS NOT SUPPORTED BY THE FIRE
 DEPARTMENT AS THE SECOND FLOOR TWO REAR EXIT STAIRS
 WILL BE UNFAMILIAR TO OCCUPANTS AS MOST FITNESS PERSONS
 WILL ACCESS THE SECOND FLOOR VIA MONUMENTAL STAIR. WE
 WOULD SUPPORT CHANGING THE MONUMENTAL STAIR TO A
 FIRE-RATED EXIT STAIR WHEREBY IT IS ENCLOSED AT THE TOP
 AND BOTTOM OR BY PROVIDING ADDITIONAL EXIT STAIR(S) AT
 THE WESTERN AREA OF THE BUILDING.
 ORIGINAL COMMENT: SHEET A2.3: THE MEANS OF EGRESS
 ARRANGEMENT FROM THE SECOND FLOOR IS OF GREAT CONCERN.
 THE OCCUPANTS NEED TO HAVE ACCESS TO THE MAIN
 ENTRANCE/EXIT. IT IS UNCLEAR FROM THE PLANS IF ENTRY
 VESTIBULE #1 OR ENTRY VESTIBULE #2 (OR BOTH) ARE
 INTENDED TO BE THE MAIN ENTRANCE/EXIT. IN EITHER CASE,
 THE MAIN ROUTE OF ACCESS TO THE SECOND FLOOR IS BY
 MEANS OF AN UNPROTECTED, UNECLOSED MONUMENTAL STAIR. IN
 AN EMERGENCY SITUATION, MANY OCCUPANTS WILL RELY ON
 LEAVING THE BUILDING THE SAME WAY THEY ENTERED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-04 Cont ID  
Sent By wjolin Date 2013-02-04 Time 13:09 Rev Time 0.00
Received By wjolin Date 2013-02-04 Time 09:15 Sent To  
Notes
2013-02-04 11:19:40700 SOUTH ROSEMARY AVENUE - #104
 PERMIT #13010720
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A0.2: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 SHEET A0.2: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET A2.2: PROVIDE 18" DEEP NON-COMBUSTIBLE DRAFT
 CURTAIN AND WATER CURTAIN (CLOSELY SPACED SPRINKLERS)
 AROUND THE FLOOR/CEILING OPENING CREATED BY THE
 MONUMENTAL STAIR.
  
 SHEET A2.2: AEROBICS ROOM #200 IS USING AN OCCUPANT
 LOAD FACTOR OF 50 SQ.FT. PER PERSON WHILE AN OCCUPANT
 LOAD FACTOR OF 15 SQ.FT. PER PERSON WOULD BE MORE
 APPROPRIATE AS THERE DOES NOT APPEAR TO BE ANY EXERCISE
 EQUIPEMENT IS THIS ROOM.
  
 SHEET A2.3: IF THE AEROBICS ROOM OCCUPANT LOAD IS
 REFACTORED USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON, THE OCCUPANT LOAD ON THE SECOND FLOOR IS
 APPROXIMATELY 500 PERSONS AND WOULD RESULT IN A NEEDED
 EGRESS WIDTH OF 100 INCHES. THERE APPEARS TO ONLY BE 72
 INCHES OF EGRESS WIDTH PROVIDED WITH ENTRY INTO TWO
 EXISTING EXIT STAIR TOWERS.
  
 SHEET A2.3: THE MEANS OF EGRESS ARRANGEMENT FROM THE
 SECOND FLOOR IS OF GREAT CONCERN. THE OCCUPANTS NEED TO
 HAVE ACCESS TO THE MAIN ENTRANCE/EXIT. IT IS UNCLEAR
 FROM THE PLANS IF ENTRY VESTIBULE #1 OR ENTRY VESTIBULE
 #2 (OR BOTH) ARE INTENDED TO BE THE MAIN ENTRANCE/EXIT.
 IN EITHER CASE, THE MAIN ROUTE OF ACCESS TO THE SECOND
 FLOOR IS BY MEANS OF AN UNPROTECTED, UNECLOSED
 MONUMENTAL STAIR. IN AN EMERGENCY SITUATION, MANY
 OCCUPANTS WILL RELY ON LEAVING THE BUILDING THE SAME
 WAY THEY ENTERED. THE CURRENT EGRESS DESIGN DOES NOT
 MEET THE FOLLOWING SECTIONS OF THE LIFE SAFETY CODE:
  
 LIFE SAFETY CODE REFERENCES:
 12.2.3.6.3 THE MAIN ENTRANCE/EXIT SHALL BE AT THE LEVEL
 OF EXIT DISCHARGE OR SHALL CONNECT TO A STAIRWAY OR
 RAMP LEADING TO A STREET.
 12.2.3.6.4 IN ASSEMBLY OCCUPANCIES, EACH LEVEL OF THE
 ASSEMBLY OCCUPANCY SHALL HAVE ACCESS TO THE MAIN
 ENTRANCE/EXIT, AND SUCH ACCESS SHALL HAVE THE CAPACITY
 TO ACCOMMODATE ONE-HALF OF THE OCCUPANT LOAD OF SUCH
 LEVELS.
 12.2.3.7 OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO THE MAIN ENTRANCE/EXIT
 AND SHALL BE PROVIDED WITH ADDITIONAL EXITS OF A WIDTH
 TO ACCOMMODATE NOT LESS THAN ONE-HALF OF THE TOTAL
 OCCUPANT LOAD SERVED BY THAT LEVEL.
  
 SHEET A5.0: FIRE EXIT HARDWARE SHALL BE PROVIDED ON
 FIRE-RATED DOORS.
  
 SHEET EL3.1: AN EXIT SIGN SHOULD NOT BE PLACED OVER THE
 MONUMENTAL STAIR.
  
 SHEET E4.2: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 SHEET FP-1: PROVIDE CLOSELY SPACED SPRINKLERS (AND 18"
 DEEP NON-COMBUSTIBLE DRAFT CURTAIN) AROUND
 FLOOR/CEILING OPENING OF THE MONUMENTAL STAIR.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-23 Cont ID  
Sent By jwitmer Date 2013-07-23 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2013-06-25 Time 06:41 Sent To  
Notes
2013-06-28 15:20:11C33
  
  
2013-06-26 06:41:48C41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-05-20 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2013-04-05 Time 13:49 Sent To  
Notes
2013-04-05 13:49:19C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 14:46 Rev Time 0.00
Received By rlecky Date 2013-01-25 Time 13:55 Sent To  
Notes
2013-01-25 13:55:57C--1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-07-23 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 10:06 Sent To  
Notes
2013-07-10 10:07:457/23/2013 CALLED PBC IMPACT FEE OFFICE CITY PLACE DOES
 NOT NEED TO PAY IMPACT FEES FOR THIS CHANGE OF
 OCCUPANCY, NO ADDITIONAL SQUARE FOOTAGE, I SPOKE WITH
 MICHELLE AT 233-5019.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-04-26 Time 15:04 Rev Time 0.00
Received By jwitmer Date 2013-04-26 Time 15:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-02-06 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2013-02-06 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-07-15 Cont ID  
Sent By H MOSER Date 2013-07-15 Time 14:21 Rev Time 0.00
Received By hmoser Date 2013-07-15 Time 10:10 Sent To  
Notes
2013-07-15 14:21:31PASS PROVISO
 REVISION REQUIRED
 1) MISSING FIRE DAMPER ON PAGE M3.0
 FCU-11-04 . PER SECTION 607.5.1 FIRE WALLS
 2010 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE
 CURB TO ROOF TIE DOWN INCLUDING BOLT SIZE
 AND BOLT PATTERN. PROVIDE BOLT SIZE FOR THE RTU. TO
 CURB TIE DOWN
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-04-12 Cont ID  
Sent By MOSER Date 2013-04-12 Time 13:59 Rev Time 0.00
Received By hmoser Date 2013-04-12 Time 13:33 Sent To  
Notes
2013-04-12 13:59:16PLANS DENIED
 PROVIDE A FULL SET OF MECHANICAL PLANS.
 PLEASE RESPOND COMMENTS FROM LAST REVIEW.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-07 Cont ID  
Sent By hmoser Date 2013-02-07 Time 14:45 Rev Time 0.00
Received By hmoser Date 2013-02-07 Time 08:48 Sent To  
Notes
2013-02-07 14:44:55MECHANICAL PLANS DENIED
 1) PROVIDE DUCT SIZE ON ALL AIR CONDITIONING
 AND EXHAUST DUCT.
 PER SECTION 107 FBC
 2) ELECTRICAL ROOM IS NOT ON MECHANICAL PLANS.
 FAN COIL SCHEDULE SHOWS AN FCU-UL-01
 UNSEALED IN THE ROOM.PER SECTION 107 FBC
 3) ROOF CURB DETAIL # 6 DOES NOT SHOW THE
 SIZE OR TYPE SCREWS FOR ANCHORING TO ROOF
 PER SECTION 301.12 WIND RESISTANCE FBC (M)
 4) MISSING FIRE DAMPERS ON UNIT FCU-LL-03
 PER SECTION 607.5.1 FIRE WALLS FBC (M) 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-15 Cont ID  
Sent By lwagner Date 2013-04-15 Time 11:26 Rev Time 0.00
Received By lwagner Date 2013-04-15 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-29 Cont ID  
Sent By lwagner Date 2013-01-29 Time 15:48 Rev Time 0.00
Received By lwagner Date 2013-01-28 Time 09:58 Sent To  
Notes
2013-01-29 15:50:24P905.4 NO HORIZONTAL DRY VENTS LESS THAN 6" ABOVE FLOOD
 LEVEL.

Review Stop Z ZONING
Rev No 3 Status P Date 2013-07-18 Cont ID  
Sent By eschneid Date 2013-07-17 Time 16:02 Rev Time 1.00
Received By eschneid Date 2013-07-17 Time 16:02 Sent To  
Notes
2013-07-17 16:48:15PASSED
  
 1) LIGHTING MOUNTED UNDER THE CANOPY SHALL BE FLUSH OR
 RECESS MOUNTED.
  
 2) SEPARATE PERMIT APPLICATION WITH PLANS ARE REQUIRED
 FOR:
  
 A. SIGNS - PLEASE NOTE THAT THE SIGN MAY NOT BE
 INSTALLED ON TOP OF THE METAL AWNING, BUT IT MAY ONLY
 BE MOUNTED TO THE BUILDING FACADE.
  
 B. FENCES - THE FENCE PERMIT SHALL INCLUDE PLANS FOR
 THE FENCE, INCLUDING HEIGHT AND MATERIAL, AND 2 COPIES
 OF A PLAN SHOWING THE LOCATION OF THE FENCES. NOTE: THE
 DECORATIVE FENCE LOCATION CURRENTLY SHOWN ON SHEET A3
 WOULD BLOCK THE SIDEWALK CONNECTION THAT IS SHOWN ON
 THE LANDLORD IMPROVEMENTS AS PART OF PERMIT NO.
 13030406.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-04-23 Cont ID  
Sent By SCHNEIDE Date 2013-04-22 Time 13:19 Rev Time 2.00
Received By eschneid Date 2013-04-22 Time 13:17 Sent To  
Notes
2013-04-22 17:30:57FAILED
  
 PLEASE PROVIDE RESPONSES TO THE COMMENTS IN WRITING.
  
 1) FOR STAFF TO ADEQUATELY REVIEW THE SUBMITTAL, THE
 OLD SHEETS SHALL BE REMOVED FROM THE PLAN ROLL AND THE
 NEW SHEETS SHALL BE INSERTED.
  
 2) THE PLANS SHALL CLEARLY DELINEATE WHAT IS COVERED
 UNDER THIS PERMIT SUBMITTAL AND WHAT IS PART OF THE
 LANDLORD WORK (THE LANDLORD PERMIT SHALL MATCH THIS
 LIMIT OF WORK) OR OTHER PERMIT.
  
 3) WHILE THE MINOR AMENDMENT IS NOT YET APPROVED, THE
 PROPOSED METAL AWNING OVER THE EASTERN ENTRY WAY WILL
 BE APPROVED AS SHOWN ON THE MINOR AMENDMENT. PLEASE
 NOTE THAT THE SIGN MAY NOT BE INSTALLED ON TOP OF THE
 METAL AWNING, BUT IT MAY ONLY BE MOUNTED TO THE
 BUILDING FACADE.
  
 4) THE METAL AWNING DIMENSIONS ON SHEET A 3.2 AND SHEET
 S 2 ARE DIFFERENT. BOTH PLANS SHALL SHOW THE SAME
 DIMENSIONS.
  
 5) THE NEW SIDEWALK, AS PROPOSED, ON THE EAST SIDE OF
 THE BUILDING INCLUDING THE ACCESSIBLE ROUTE TO THE
 DISABLED PARKING SPACES, IS NOT APPROVED. FULL DETAILS
 ON HOW THE SIDEWALK WILL FUNCTION, INCLUDING
 DIMENSIONS, ARE REQUIRED. ADDITIONALLY, A FULLY
 COMPLIANT ACCESSIBLE ROUTE, WITH DIMENSIONS, SHALL BE
 PROVIDED AND PLANS SHOWING SUCH SHALL BE SUBMITTED WITH
 THIS PERMIT. THE ROUTE INCLUDED WITH THE MINOR
 AMENDMENT IS NOT FULLY COMPLIANT.
  
 6) REPEAT COMMENT: PLEASE NOTE THAT NOW THAT THE
 TRANSFORMER AREA IS A PUBLICLY ACCESSED AREA, PLEASE
 SHOW HOW THE MECHANICAL EQUIPMENT WILL BE SCREENED IN
 ACCORDANCE WITH THE REQUIREMENT FROM THE CITYPLACE DRI
 THAT ALL GROUND LEVEL MECHANICAL EQUIPMENT, INCLUDING
 BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE
 UTILITY SERVICE CONNECTIONS; HEATING, VENTILATING, AND
 AIR CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND
 EQUIPMENT LOCATION.
  
 7) REPEAT COMMENT: IT APPEARS THAT THERE IN NEW
 EQUIPMENT BEING INSTALLED ON THE ROOF. IN ACCORDANCE
 WITH THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION
 THAT ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT
 NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY
 SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR
 CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND
 EQUIPMENT LOCATION. - THE RESPONSE TO THE ZONING
 COMMENT REFERENCES A ROOF WORK PERMIT BY THE LANDLORD,
 YET THE RESPONSE TO THE MECHANICAL REVIEWER MENTIONS
 ROOF CURB DETAILS. THIS COMMENT RESPONSE AND THE PLANS
 INDICATE ROOF WORK IS BEING DONE. VERIFICATION OF
 ROOFTOP MECHANICAL EQUIPMENT SCREENING IS REQUIRED AS
 PART OF THIS PERMIT AS WELL AS THE OTHER PERMIT. THIS
 IS AN EXAMPLE OF COMMENT NO. 2.
  
 8) REPEAT COMMENT: THE CITYPLACE APPROVAL STAMP WAS NOT
 PROVIDED ON THE PLANS.
  
 9) PLEASE NOTE THAT ZONING STAFF HAS NO ISSUES WITH THE
 INTERIOR WORK SHOWN ON THE PLANS AND THAT IF THE
 EXTERNAL WORK IS EXCLUDED FROM THE PERMIT WOULD PASS AN
 INTERIOR ONLY PERMIT.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-02-14 Cont ID  
Sent By escheide Date 2013-02-14 Time 08:43 Rev Time 2.00
Received By eschneid Date 2013-02-14 Time 08:43 Sent To  
Notes
2013-02-14 09:20:35FAILED
  
 PLEASE PROVIDE RESPONSES TO THE COMMENTS IN WRITING.
  
 1) THE PROPOSED CANOPY ON THE EAST SIDE OF THE BUILDING
 AND THE NEW SIDEWALK ARE MODIFICATIONS TO THE APPROVED
 CITYPLACE MASTER SITE PLAN AND REQUIRE APPROVAL OF A
 MINOR PLANNED DEVELOPMENT AMENDMENT. THESE FEATURES
 SHALL NOT BE INCLUDED ON THIS PERMIT UNLESS THE MINOR
 AMENDMENT IS APPROVED. THE MINOR AMENDMENT REQUIREMENT
 HAS BEEN DISCUSSED WITH CITYPLACE. PLEASE NOTE THAT NOW
 THAT THE TRANSFORMER AREA IS A PUBLICLY ACCESSED AREA,
 THE MECHANICAL EQUIPMENT SHALL BE SCREENED IN
 ACCORDANCE WITH THE REQUIREMENT FROM THE CITYPLACE DRI
 THAT ALL GROUND LEVEL MECHANICAL EQUIPMENT, INCLUDING
 BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE
 UTILITY SERVICE CONNECTIONS; HEATING, VENTILATING, AND
 AIR CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND
 EQUIPMENT LOCATION.
  
 2) IT APPEARS THAT THERE IN NEW EQUIPMENT BEING
 INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE
 DRI, PLEASE PROVIDE VERIFICATION THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH
 ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION.
  
 3) THE EXISTING CLEAR STOREFRONT GLAZING SHALL REMAIN
 AT NOT ONLY THE KIDS KLUB, BUT ALSO THE SPINNING ROOM,
 ALONG SOUTH ROSEMARY AVENUE. THE NOTE IS CLEARLY SHOWN
 AT THE KIDS KLUB AREA, BUT NOT AT THE SPINNING ROOM,
 WHERE THE LABEL STATES "MIRROR". PLEASE CLARIFY.
  
 4) THE CITYPLACE APPROVAL STAMP WAS NOT PROVIDED ON THE
 PLANS.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.