Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-24 Cont ID  
Sent By shill Date 2013-01-24 Time 10:52 Rev Time 0.00
Received By shill Date 2013-01-24 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-23 Cont ID  
Sent By shill Date 2013-01-23 Time 14:45 Rev Time 0.00
Received By shill Date 2013-01-23 Time 14:45 Sent To  
Notes
2013-01-23 14:51:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. INDICATE SYSTEM PROPOSED. SEE SHEET 6 OF 16 OF FLAT
 DECK PRODUCT APPROVAL, FBC 1609. THE INFORMATION
 HIGHLIGHTED ON PAGE 3 ARE PRODUCTS (COMPONENTS), A PART
 OF A ROOF ASSEMBLY.
  
 2. IF THE PROPOSED ASSEMBLY DOES NOT MEET THE MINIMUM
 DESIGN PRESSURE REQUIREMENT OF -102PSF FOR ZONE 3,
 ENGINEERING FOR ENHANCED FASTENING IS REQUIRED, FBC
 1609. PLEASE NOTE THAT TWO DIFFERENT SYSTEMS MEET THIS
 PRESSURE, SEE SHEET 6.
  
  