Plan Review Details - Permit 13010540
Plan Review Stops For Permit 13010540
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 14:35 Rev Time 0.00
Received By rlecky Date 2013-02-22 Time 14:25 Sent To  
Notes
2013-02-22 14:36:58ELECTRICAL ENGINEER PROVIDED CLARIFICATION BY
 TELEPHONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-02-12 Cont ID  
Sent By rlecky Date 2013-02-12 Time 09:06 Rev Time 0.00
Received By rlecky Date 2013-02-12 Time 08:55 Sent To  
Notes
2013-02-12 09:06:1513010540
 400 S. AUSTRALIAN
 INSTALL LIEBERT DX UNITS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SINGLE LINE ELECTRICAL RISER PLAN FOR EQUIPMENT
 CONNECTIONS. PROVIDE SPECIFICATION AND LISTING FOR THE
 INTERLOCKING SYSTEM WHICH PREVENTS BOTH SYSTEMS FROM
 OPERATING TOGETHER. NEC 215.5, 110.3
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-30 Cont ID  
Sent By rlecky Date 2013-01-30 Time 09:47 Rev Time 0.00
Received By rlecky Date 2013-01-30 Time 08:35 Sent To M
Notes
2013-01-30 09:49:4513010540
 400 S. AUSTRALIAN
 INSTALL LIEBERT DX UNITS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SINGLE LINE ELECTRICAL RISER PLAN FOR EQUIPMENT
 CONNECTIONS. PROVIDE SPECIFICATION AND LISTING FOR THE
 INTERLOCKING SYSTEM WHICH PREVENTS BOTH SYSTEMS FROM
 OPERATING TOGETHER. NEC 215.5, 110.3
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 14:36 Rev Time 0.00
Received By rlecky Date 2013-02-22 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-12 Cont ID  
Sent By rlecky Date 2013-02-12 Time 09:06 Rev Time 0.00
Received By rlecky Date 2013-02-07 Time 13:25 Sent To  
Notes
2013-02-08 13:25:59IN MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-30 Cont ID  
Sent By hmoser Date 2013-01-30 Time 15:01 Rev Time 0.00
Received By hmoser Date 2013-01-22 Time 15:43 Sent To  
Notes
2013-01-22 15:43:26IN ELECTRIC BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-11 Cont ID  
Sent By hmoser Date 2013-02-11 Time 12:33 Rev Time 0.00
Received By hmoser Date 2013-02-11 Time 12:25 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-30 Cont ID  
Sent By hmoser Date 2013-01-30 Time 14:17 Rev Time 0.00
Received By hmoser Date 2013-01-30 Time 14:17 Sent To  
Notes
2013-01-30 14:35:56MECHANICAL PLANS DENIED
 1) PROVIDE INFORMATION ON THE SIZE FASTENERS USED TO
 ANCHOR
 PIPE STANDS AND UNISTRUT TO ROOF, TO MEET WIND
 RESISTANCE
 PER SECTION 301.12 1210 FBC (M)
 2) PROVIDE A DETAIL ON HOW THE CONDENSER IS ANCHORED TO
 THE ROOF
 PER SECTION 301.12 FBC (M) 2010
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND
 SECTION 606.3 INSTALLATION 2010 FBC (M)
 4) REFER TO SECTION 606.4.1 SUPERVISION .2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]