Plan Review Details - Permit 13010540
Plan Review Stops For Permit 13010540 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2013-02-22 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-02-22 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-02-22 |
Time |
14:25 |
Sent To |
|
|
Notes |
2013-02-22 14:36:58 | ELECTRICAL ENGINEER PROVIDED CLARIFICATION BY | | TELEPHONE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2013-02-12 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-02-12 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-02-12 |
Time |
08:55 |
Sent To |
|
|
Notes |
2013-02-12 09:06:15 | 13010540 | | 400 S. AUSTRALIAN | | INSTALL LIEBERT DX UNITS | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE SINGLE LINE ELECTRICAL RISER PLAN FOR EQUIPMENT | | CONNECTIONS. PROVIDE SPECIFICATION AND LISTING FOR THE | | INTERLOCKING SYSTEM WHICH PREVENTS BOTH SYSTEMS FROM | | OPERATING TOGETHER. NEC 215.5, 110.3 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-01-30 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-01-30 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-01-30 |
Time |
08:35 |
Sent To |
M |
|
Notes |
2013-01-30 09:49:45 | 13010540 | | 400 S. AUSTRALIAN | | INSTALL LIEBERT DX UNITS | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE SINGLE LINE ELECTRICAL RISER PLAN FOR EQUIPMENT | | CONNECTIONS. PROVIDE SPECIFICATION AND LISTING FOR THE | | INTERLOCKING SYSTEM WHICH PREVENTS BOTH SYSTEMS FROM | | OPERATING TOGETHER. NEC 215.5, 110.3 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2013-02-22 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-02-22 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-02-22 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-02-12 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2013-02-12 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2013-02-07 |
Time |
13:25 |
Sent To |
|
|
Notes |
2013-02-08 13:25:59 | IN MECHANICAL BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-01-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-01-30 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-01-22 |
Time |
15:43 |
Sent To |
|
|
Notes |
2013-01-22 15:43:26 | IN ELECTRIC BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2013-02-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-02-11 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-02-11 |
Time |
12:25 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2013-01-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-01-30 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-01-30 |
Time |
14:17 |
Sent To |
|
|
Notes |
2013-01-30 14:35:56 | MECHANICAL PLANS DENIED | | 1) PROVIDE INFORMATION ON THE SIZE FASTENERS USED TO | | ANCHOR | | PIPE STANDS AND UNISTRUT TO ROOF, TO MEET WIND | | RESISTANCE | | PER SECTION 301.12 1210 FBC (M) | | 2) PROVIDE A DETAIL ON HOW THE CONDENSER IS ANCHORED TO | | THE ROOF | | PER SECTION 301.12 FBC (M) 2010 | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND | | SECTION 606.3 INSTALLATION 2010 FBC (M) | | 4) REFER TO SECTION 606.4.1 SUPERVISION .2010 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
|