Plan Review Details - Permit 13010504
Plan Review Stops For Permit 13010504
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2014-03-22 Cont ID  
Sent By jwitmer Date 2014-03-22 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2014-03-22 Time 12:00 Sent To  
Notes
2014-03-22 12:23:19 
 BUILDING PLAN REVIEW
 PERMIT: 13010504
 SUBMITTAL: DATED 3/17/2014
 ADD: 631 EVERNIA
 CONT: KAUFMAN LYNN CONSTRUCTION
 TEL: (561)827-2078
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 SUBMITTAL: 3/ 17/ 2014 FOR : FRAMED WALL ENGINEERING
 CALCULATIONS & SHOP DRAWINGS FOR THE SOUTHWEST ROOFTOP
 TOWER.
 1ST REVIEW
 DATE: SAT. MARCH 22/ 2014
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 REVISIONS SUBMITTED UNDER 13071115 INTRODUCED STEEL
 FRAMING WALL MEMBERS ON SHEETS A-601 & A-609, THE PLANS
 DID NOT INDICATE AS TO THE TYPE OF WALL SHEATHING WAS
 TO BE INSTALLED.
 UNDER THIS SUBMITTAL STEEL SHOP DRAWINGS & STRUCTURAL
 CALCULATIONS SHEET 46 OF 49 THE CALCULATIONS INDICATE
 THE USE OF 1/2 CDX PLYWOOD FOR THE PROPOSED WALL
 SHEATHING. THERE IS NO MENTION OF THE USE OF FIRE
 RETARDANT TREATED PLYWOOD BEING INSTALLED. PLEASE SEE
 THE FOLLOWING CODE SECTIONS AND CONCERNS, AND
 CORRECTIONS TO BE MADE.
  
 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV
 CONSTRUCTION.
 ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION,
 EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5,
 OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING
 WITH THE FOLLOWING LIMITATIONS:
 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE
 FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS.
 2. COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION
 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED
 IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP
 TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE REGARDLESS
 OF THE FIRE SEPARATION DISTANCE.
  
 IN THIS APPLICATION WE ARE ABOVE 60'-0" IN HEIGHT.
  
  
 2010 FBC-B 1509.2.4 TYPE OF CONSTRUCTION.PENTHOUSES
 SHALL BE CONSTRUCTED WITH WALLS, FLOORS AND ROOF AS
 REQUIRED FOR THE BUILDING.
 EXCEPTIONS:1. ON BUILDINGS OF TYPE I CONSTRUCTION, THE
 EXTERIOR WALLS AND ROOFS OF PENTHOUSES WITH A FIRE
 SEPARATION DISTANCE OF MORE THAN 5 FEET (1524 MM) AND
 LESS THAN 20 FEET (6096 MM) SHALL BE OF AT LEAST 1-HOUR
 FIRE RESISTANCE-RATED NONCOMBUSTIBLE CONSTRUCTION.
 WALLS AND ROOFS WITH A FIRE SEPARATION DISTANCE OF 20
 FEET (6096 MM) OR GREATER SHALL BE OF NONCOMBUSTIBLE
 CONSTRUCTION. INTERIOR FRAMING AND WALLS SHALL BE OF
 NONCOMBUSTIBLE CONSTRUCTION.
 2. ON BUILDINGS OF TYPE I CONSTRUCTION TWO STORIES
 ABOVE GRADE PLANE OR LESS AND TYPE II CONSTRUCTION, THE
 EXTERIOR WALLS AND ROOFS OF PENTHOUSES WITH A FIRE
 SEPARATION DISTANCE OF MORE THAN 5 FEET (1524 MM) AND
 LESS THAN 20 FEET (6096 MM) SHALL BE OF AT LEAST 1-HOUR
 FIRE-RESISTANCE-RATED NONCOMBUSTIBLE OR
 FIRE-RETARDANT-TREATED WOOD CONSTRUCTION. WALLS AND
 ROOFS WITH A FIRE SEPARATION DISTANCE OF 20 FEET (6096
 MM) OR GREATER SHALL BE OF NONCOMBUSTIBLE OR
 FIRE-RETARDANT-TREATED WOOD CONSTRUCTION. INTERIOR
 FRAMING AND WALLS SHALL BE OF NONCOMBUSTIBLE OR
 FIRE-RETARDANT-TREATED WOOD CONSTRUCTION.
  
  
 ANOTHER ISSUE WILL BE ADJUSTMENT FACTORS IN WOOD
 STRUCTURAL PANELS FOR THE FIRE RETARDANT TREATMENT OF
 THE PLYWOOD. SEE 2010 2303.2.5 STRENGTH ADJUSTMENTS.
 DESIGN VALUES FOR UNTREATED LUMBER AND WOOD STRUCTURAL
 PANELS, AS SPECIFIED IN SECTION 2303.1, SHALL BE
 ADJUSTED FOR FIRE-RETARDANT-TREATED WOOD. ADJUSTMENTS
 TO DESIGN VALUES SHALL BE BASED ON AN APPROVED METHOD
 OF INVESTIGATION THAT TAKES INTO CONSIDERATION THE
 EFFECTS OF THE ANTICIPATED TEMPERATURE AND HUMIDITY TO
 WHICH THE FIRE-RETARDANT-TREATED WOOD WILL BE
 SUBJECTED, THE TYPE OF TREATMENT AND REDRYING
 PROCEDURES
  
 2303.2.5.1 WOOD STRUCTURAL PANELS.
 THE EFFECT OF TREATMENT AND THE METHOD OF REDRYING
 AFTER TREATMENT, AND EXPOSURE TO HIGH TEMPERATURES AND
 HIGH HUMIDITIES ON THE FLEXURE PROPERTIES OF
 FIRE-RETARDANT-TREATED SOFTWOOD PLYWOOD SHALL BE
 DETERMINED IN ACCORDANCE WITH ASTM D 5516. THE TEST
 DATA DEVELOPED BY ASTM D 5516 SHALL BE USED TO DEVELOP
 ADJUSTMENT FACTORS, MAXIMUM LOADS AND SPANS, OR BOTH,
 FOR UNTREATED PLYWOOD DESIGN VALUES IN ACCORDANCE WITH
 ASTM D 6305. EACH MANUFACTURER SHALL PUBLISH THE
 ALLOWABLE MAXIMUM LOADS AND SPANS FOR SERVICE AS FLOOR
 AND ROOF SHEATHING FOR ITS TREATMENT.
  
  
 WHEN USING FIRE RETARDEANT TREATED PLYWOOD THERE IS A
 CORROSIVE EFFECT THAT IS CAUSED BY THE SALT SOLUTIONS
 IMPREGNATED INTO THE WOOD ON THE FASTENERS, PLEASE
 PROVIDE HOW THE METAL FRAMING MEMBERS WIL BE PROTECTED
 AS WELL AS COMPLIANCE WITH 2010 FBC-B 2304.9.5
 FASTENERS AND CONNECTORS IN CONTACT WITH
 PRESERVATIVE-TREATED AND FIRE-RETARDANT-TREATED WOOD.
 FASTENERS AND CONNECTORS IN CONTACT WITH
 PRESERVATIVE-TREATED AND FIRE-RETARDANT-TREATED WOOD
 SHALL BE IN ACCORDANCE WITH SECTIONS 2304.9.5.1 THROUGH
 2304.9.5.4. THE COATING WEIGHTS FOR ZINC-COATED
 FASTENERS SHALL BE IN ACCORDANCE WITH ASTM A 153.
  
 2304.9.5.1 FASTENERS AND CONNECTORS FOR
 PRESERVATIVE-TREATED WOOD.
 FASTENERS IN CONTACT WITH PRESERVATIVE-TREATED WOOD
 SHALL BE OF HOT-DIPPED ZINC-COATED GALVANIZED STEEL,
 STAINLESS STEEL, SILICON BRONZE OR COPPER. FASTENERS
 OTHER THAN NAILS, TIMBER RIVETS, WOOD SCREWS AND LAG
 SCREWS SHALL BE PERMITTED TO BE OF MECHANICALLY
 DEPOSITED ZINC-COATED STEEL WITH COATING WEIGHTS IN
 ACCORDANCE WITH ASTM B 695, CLASS 55 MINIMUM.
 CONNECTORS THAT ARE USED IN EXTERIOR APPLICATIONS AND
 IN CONTACT WITH PRESERVATIVE-TREATED WOOD SHALL HAVE
 COATING TYPES AND WEIGHTS IN ACCORDANCE WITH THE
 TREATED WOOD OR CONNECTOR MANUFACTURER?S
 RECOMMENDATIONS. IN THE ABSENCE OF MANUFACTURER?S
 RECOMMENDATIONS, A MINIMUM OF ASTM A 653, TYPE G185
 ZINC-COATED GALVANIZED STEEL, OR EQUIVALENT, SHALL BE
 USED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2014-02-10 Cont ID  
Sent By shill Date 2014-02-10 Time 11:24 Rev Time 0.00
Received By shill Date 2014-02-10 Time 11:24 Sent To  
Notes
2014-02-10 11:25:14RAILING SHOPS & CALCULATIONS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-21 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2014-01-21 Time 11:30 Sent To  
Notes
2014-01-21 11:39:14ROOF PT SHOP DRAWINGS & STUD RAIL DETAIL
 FRICTION & ELONGATION CALCULATIONS FOR ROOF DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2013-12-02 Cont ID  
Sent By jwitmer Date 2013-12-02 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2013-12-02 Time 09:54 Sent To  
Notes
2013-12-02 09:55:58POST-TENSION CABLE SHOP DRAWINGS & CALCULATIONS FOR
 LEVEL 3 & 4. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2013-11-20 Cont ID  
Sent By jwitmer Date 2013-11-20 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2013-11-20 Time 14:22 Sent To  
Notes
2013-11-20 14:24:34SUBMITTAL:
 NOV. 15/2013 SHOP DRAWINGS FOR 2 ND LEVEL POST-TENSION
 CABLES & FRICTION & ELONGATION CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2013-11-04 Time 16:12 Sent To  
Notes
2013-11-04 16:15:00SUBMITTAL:
 PLAZA DECK LEVEL 1 TENDON LAYOUT & FRICTION &
 ELONGATION CALCULATIONS PLAZA LEVEL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2013-10-19 Cont ID  
Sent By jwitmer Date 2013-10-19 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2013-10-19 Time 09:30 Sent To  
Notes
2013-10-19 10:20:45BUILDING PLAN REVIEW
 PERMIT: 13010504
 ADD: 631 EVERNIA ST
 CONT: KAUFMAN LYNN
 TEL: (561)827-2078
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: SAT. OCT. 19/2013
 ACTION: DENIED
  
 1) SHORING SHOP DRAWINGS:
 PLAZA DECK BEAM SHORING
 PLAZA DECK SHORING
 2ND LEVEL SHORING
  
  
 SPECIAL INSPECTION PLAN HAS NOT BEEN REVIEWED BY THE
 DESIGN PROFESSIONAL.
  
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-05-06 Cont ID  
Sent By jwitmer Date 2013-05-06 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2013-05-06 Time 07:30 Sent To  
Notes
2013-05-06 10:16:03PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 5TH REVIEW
 MAY 06/ 2013
 ACTION: PROVISO BEFORE PERMIT ISSUANCE
  
  
  
 1) 5TH REVIEW IN PROCESS OF UNITY OF TITLE, ENGINEERING
 WILL NOTIFY ME ONCE THE UNITY OF TITLE HAS BEEN
 RECORDED.
  
 THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) INFORMATIONAL ONLY, THIS BUILDING IS CONSIDERED A
 THRESHOLD BUILDING, (3) SETS OF PLANS, PRODUCT
 APPROVALS WILL REQUIRED, ONE SET FOR THE SPECIAL
 INSPECTOR, ONE FOR THE FIELD, AND A COPY WILL BE KEPT
 ELECTRONICALLY BY THE BUILDING DEPARTMENT, FOR OUR
 RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) COMPLIED.
  
 2B). THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C-D) COMPLIED.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS
 MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2E)(2) 3RD REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3-20) COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-04-24 Cont ID  
Sent By jwitmer Date 2013-04-23 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 09:00 Sent To  
Notes
2013-04-22 13:28:11 
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 3RD REVIEW
 APRIL 22/ 2013
 ACTION: DENIED
  
 4TH REVIEW APRIL 24/2013
  
 1) 3RD REVIEW IN PROCESS OF UNITY OF TITLE, ENGINEERING
 WILL NOTIFY ME ONCE THE UNITY OF TITLE HAS BEEN
 RECORDED.
  
 THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) 3RD REQUEST! THIS BUILDING IS CONSIDERED A THRESHOLD
 BUILDING, (3) SETS OF PLANS, PRODUCT APPROVALS WILL
 REQUIRED, ONE SET FOR THE SPECIAL INSPECTOR, ONE FOR
 THE FIELD, AND A COPY WILL BE KEPT ELECTRONICALLY BY
 THE BUILDING DEPARTMENT, FOR OUR RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) 3RD REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 3RD REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS. ALL TRADES THAT
 PENETRATE THE FIRE RATED SLAB WILL NEED TO USE ONE
 PRODUCT THAT IS TO BE SPECED OUT BY THE DESIGNER OF
 RECORD, SO ALL PENETRATIONS WILL REQUIRE THE
 ENGINEERING SHEETS FOR THAT SPECIFIC PRODUCT AND
 APPLICATION.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONCRETE
 RESTORATION. THIS MAY BE SUBMITTED TO KEN CONRAD BY
 E-MAIL. KEN CONRAD: [email protected]
  
 2E)(2) 3RD REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) SOILS REPORT BY ARDAMEN 11/19/2012, & 12/27/2012.
 2010 FBC-B 1803.2 SOILS INVESTIGATION ARE PROVIDED WILL
 REQUIRE A PEDS SIGNATURE SINCE THEY ARE SIGNED AND
 SEALED.
  
 4-5) COMPLIED.
  
 6) 3RD REQUEST 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP) BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2ND 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 CORNELL GAGARGE DOOR PLEASE CIRCLE WHICH TYPE OF DOOR
 IS TO BE INSTALLED AND ASSOCIATED PRESSURES.
  
 (B) WINDOWS/ MULLIONS PLEASE CIRCLE WHICH APPLICATIONS
 WILL BE USED FOR TYPE OF GLAZING SIZE OF WINDOW AND
 ASSOCIATED PRESSURES, PLEASE INDICATE IF STEEL
 RE-INFORCEMENT WILL BE REQUIRED FOR THE ASSOCIATED
 PRESSUES.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING MEMBRANE
 COVER SHEET IS ACTUALLY ROOFING INSULATION, NOT THE
 ROOFING MEMBRANE, NO PRODUCT APPROVAL WAS SUBMITTED FOR
 THE ROOF COVERING.
 METAL ROOFING PLEASE CIRCLE WHICH SUB-SYSTEM IS TO BE
 INSTALLED, AND IF ENHANCED FASTENING WILL BE ALLOWED
 SEE ALLOWED. NOTE ONLY THE COVER SHEET WAS UPLOADED,
 NEITHER THE EVALUATION REPORT WAS UPLOADED NOR THE
 INSTALATION INSTRUCTIONS.
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) 2COMPLIED.
  
 9) SHEET LS-101:
  
 9A-F) COMPLIED .
  
  
 10) SHEET A-201:
 10A-B) COMPLIED.
 .
 10C) BUILDING PROVISO: TO BE SUPPLIED AS A LOW VOLTAGE
 PERMIT. PROVIDE COMPLIANCE WITH F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 10D)(1) 3RD REQUEST. MACHINE ROOM-LESS ELEVATORS SHEET
 A-621. KONE ECOSPACE. WILL NEED MANUFACTURERS
 REQUIREMENTS FOR INSTALLATION. MAY STILL NEED TO
 INCORPORATE HOIST WAY VENTING REQUIREMENTS FOUND IN
 2010 FBC-B 3004.
  
 10D) (2) COMPLIED. PROVIDE COMPLIANCE WITH 3002.4
 ELEVATOR CAR TO ACCOMMODATE AN AMBULANCE STRETCHER.
  
 11) SHEET A202 TRASH CHUTE
 11A)3RD REQUEST. SEMI COMPLIED, LS-103/ LS-104. THE
 NORTH STAIRWELL INDICATES THE TRASH CHUTE ACTUALLY
 PENETRATING THE 2 HOUR FIRE RATED STAIR ENCLOSURE.
 PLEASE REVIEW 2010 FBC-B 1022.4 PENETRATIONS INTO &
 THROUGH AN EXIT ENCLOSURE. PLEASE REVIEW THE
 REQUIREMENTS FOR TERMINATION ROOM 708.13.4 ALSO SEE
 708.8. 708.8 DEALS WITH HOW THE TRASH CHUTE WILL
 PENETRATE THE 2 HOUR SHAFT.T .
  
 11B) COMPLIED.
  
 11C) COMPLIED.
  
 11D) 4/24/13 COMPLIED. 4TH REVIEW.
  
 11E) 3RD REQUEST. 4/24/2013 4TH REVIEW. SHEET A-601
 DETAIL # 1 TRASH CHUTE SHAFT STOPS AT THE BOTTOM OF THE
 2ND FLOOR, IT DOES NOT CONTINUE THROUGH TO THE 1ST
 FLOOR ALTHOUGH THE SHAFT DOES PENETRATE THE 2ND FLOOR
 ASSEMBLY AND 1ST FLOOR WALL. PLEASE SEE 708.11
 ENCLOSURE AT THE BOTTOM . TRASH CHUTE DETAILS WERE
 UPLOADED AND DEPICT A 2 HR HEAT ACTIVATED ACCORDIAN
 FIRE DAMPER. PLEASE PROVIDE THE MANUFACTURERS
 INSTALATION INSTRUCTIONS THAT WILL THE DAMPER TO BE
 INSTALLED ON A 45 DEGREE ANGLE, IT IS DEPICTED IN THERE
 LITERATURE AS A HORIZONTAL APPLICATION.
  
 11F) COMPLIED.
  
 11G) 3RD REQUEST. 4TH REVIEW 4/24/13 2010 FBC-B
 708.13.6. AUTOMATIC SPRINKLERS SYSTEM. AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.2.11.2. F] 903.2.11.2
 RUBBISH AND LINEN CHUTES.BUILDINGS WITH SHUTES GREATER
 THAN 3 STORIES SHALL HAVE ADDTIONAL HEADS AT
 ALTERNATING FLOORS. NEITHER THE TRASH CHUTE NOR FIRE
 SPRINKLER DRAWINGS HAVE ONLY ONE FIRE SPRINKLER HEAD AT
 THE 3RD FLOOR.
 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN
 CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING
 THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT
 ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE
 FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE
 FIRE SPRINKLERS.
  
 12) COMPLIED.
  
 13) 2ND REQUEST. SHEET A450 DETAILS 1-3 HAVE GENERAL
 NOTES, A602, A609, A-620 AT DETAILS INDICATING SOLID
 SHEATHING THEN NOTES 1 & 2 THE SPECIFIC NOTE INDICATES
 THE USE OF DENSE-DECK. PLEASE BE AWARE OF PRESSURES
 FROM THE PRODUCT APPROVAL WILL BE FOR 3/4 INCH OR 5/8
 CDX PLYWOOD NOT FOR DENSE DECK, IF PLYWOOD IS USED IT
 NEEDS TO BE FIRE RETARDENT TREATED PLYWOOD SEE 603.1.1.
  
 4/24/13 NOTE HAVE BEEN CHANGED TO 5/8 INCH CDX PLYWOOD,
 NO MENTION OF FIRE RETARDENT TREATED PLYWOOD.
  
 13) COMPLIED.
  
 14A) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPIED.
  
 17) COMPLIED.
  
 18A-B COMPLIED.
  
 18C) 3RD REQUEST.4TH REVIEW 4/24/13/ PLEASE SHOW
 COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE
 SOUND, FLOOR CEILING ASSEMBLIES TO HAVE A INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50, (45 IF FIELD
 TESTED). THE PLANS DO NOT PROVIDE WHAT FLOOR FINISHES
 WILL OCCUR IN THTE TENANT SUITES NOR THE COMMON AREAS
 OR ELECTRICAL ROOMS ...
  
 19) COMPLIED
  
 20)COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 *****INFORMATIONAL*****PLEASE!!!!!!!: WHEN RESUBMITTING
 PLANS PLEASE INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-25 Cont ID  
Sent By jwitmer Date 2013-03-25 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2013-03-25 Time 13:21 Sent To  
Notes
2013-03-25 16:35:54 
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2ND REVIEW
 MARCH 25/ 2013
 ACTION: DENIED
  
 1) SEMI-COMPLIED.
  
 THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) 2ND REQUEST! THIS BUILDING IS CONSIDERED A THRESHOLD
 BUILDING, (3) SETS OF PLANS, PRODUCT APPROVALS WILL
 REQUIRED, ONE SET FOR THE SPECIAL INSPECTOR, ONE FOR
 THE FIELD, AND A COPY WILL BE KEPT ELECTRONICALLY BY
 THE BUILDING DEPARTMENT, FOR OUR RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONCRETE
 RESTORATION. THIS MAY BE SUBMITTED TO KEN CONRAD BY
 E-MAIL. KEN CONRAD: [email protected]
  
 2E)(2) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) MISSING SOILS REPORT BY ARDAMEN 11/19/2012, &
 12/27/2012. 2010 FBC-B 1803.2 SOILS INVESTIGATION
 REQUIRED.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2ND 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) 2ND REQUEST. FOLDER CONTAINING WALL LOUVER NOA
 11-0408.05 EXPIRED JULY 09/12. CUT SHEET FOR THE RUSKIN
 ACL 12450 LIST A NOA 11-0207.21 BUT NOT PROVIDED.
  
 9) SHEET LS-101:
  
 9A-F) COMPLIED .
  
  
 10) SHEET A-201:
 10A) 2ND REQUEST. IN BOTH STAIRWELLS THE NORTH AND EAST
 CONTINUE BELOW GRADE, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 1022.7 DISCHARGE IDENTIFICATION. A STAIRWAY
 IN AN EXIT ENCLOSURE SHALL NOT CONTINUE BELOW ITS LEVEL
 OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
  
 10B) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B: [F] 914.1 SHAFTWAY MARKINGS.
 VERTICAL SHAFTS SHALL BE IDENTIFIED AS REQUIRED BY
 SECTIONS 914.1.1 AND 914.1.2.
  
 [F] 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS.
 OUTSIDE OPENINGS ACCESSIBLE TO THE FIRE DEPARTMENT AND
 THAT OPEN DIRECTLY ON A HOISTWAY OR SHAFTWAY
 COMMUNICATING BETWEEN TWO OR MORE FLOORS IN A BUILDING
 SHALL BE PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED
 LETTERS AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE
 BACKGROUND. SUCH WARNING SIGNS SHALL BE PLACED SO AS TO
 BE READILY DISCERNIBLE FROM THE OUTSIDE OF THE
 BUILDING.
  
 [F] 914.1.2 INTERIOR ACCESS TO SHAFTWAYS.
 DOOR OR WINDOW OPENINGS TO A HOISTWAY OR SHAFTWAY FROM
 THE INTERIOR OF THE BUILDING SHALL BE PLAINLY MARKED
 WITH THE WORD ?SHAFTWAY? IN RED LETTERS AT LEAST 6
 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. SUCH
 WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE.
  
 EXCEPTION: MARKINGS SHALL NOT BE REQUIRED ON SHAFTWAY
 OPENINGS THAT ARE READILY DISCERNIBLE AS OPENINGS ONTO
 A SHAFTWAY BY THE CONSTRUCTION OR ARRANGEMENT.
  
 [F] 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
 10) 2ND REQUEST. SHEET A-201:
 10C) PROVIDE COMPLIANCE WITH F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 10D) MACHINE ROOM-LESS ELEVATORS SHEET A-621. KONE
 ECOSPACE. WILL NEED MANUFACTURERS REQUIREMENTS FOR
 INSTALLATION. MAY STILL NEED TO INCORPORATE HOIST WAY
 VENTING REQUIREMENTS FOUND IN 2010 FBC-B 3004. PROVIDE
 COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE AN
 AMBULANCE STRETCHER.
  
 11) SHEET A202 TRASH CHUTE
 11A) SEMI COMPLIED, LS-103/ LS-104. THE NORTH STAIRWELL
 INDICATES THE TRASH CHUTE ACTUALLY PENETRATING THE 2
 HOUR FIRE RATED STAIR ENCLOSURE. PLEASE REVIEW 2010
 FBC-B 1022.4 PENETRATIONS INTO & THROUGH AN EXIT
 ENCLOSURE. PLEASE REVIEW THE REQUIREMENTS FOR
 TERMINATION ROOM 708.13.4.
  
 11B) SEMI-COMPLIED. LS-103 ? LS-104. THE TRASH CHUTE
 VESTIBULE COMMON TO 2ND- 6TH FLOORS, BEING LOCATED IN A
 VESTIBULE. SHEET LS-103/ LS-104 THE 2010 FBC-B 708.13.3
 REQUIRES REFUSE CHUTES TO HAVE A SEPARATE ACCESS ROOM
 TO BE A 1 HR FIRE BARRIER ENCLOSURE AND 3/4 HR OPENING
 PROTECTIVES. THE LIFE SAFETY SHEETS DO NOT INDICATE A
 3/4 HR RATING ON THE DOOR. 708.13.1 OPENINGS SHALL NOT
 OPEN INTO CORRIDORS. 708.13.1.
  
 11C) 2ND REQUEST LS-103/ LS-104. THE TRASH CHUTE IS
 DEPICTED TO BE IN A RATED SHAFT WITH A A/C DUCT IN THE
 SAME ENCLOSURE. 2010 FBC-B 708.13.1 A SHAFT ENCLOSURE
 CONTAINING A REFUSE CHUTE SHALL NOT BE USED FOR ANY
 OTHER PURPOSE AND SHALL BE ENCLOSED IN ACCORDANCE WITH
 708.4.
  
 11D) 2ND REQUEST. SHEET A-601DETAIL # 1 INDICATES THE
 REFUSE CHUTE GOES THROUGH THE ROOF BUT THE SHAFT
 ENCLOSURE STOPS AT THE CEILING OF THE 6TH FLOOR, PLEASE
 REVIEW 708.12 ENCLOSURES AT THE TOP AND THE REQUIRED
 FIRE RATING OF MATERIALS.
  
 11E) 2ND REQUEST. SHEET A-601 DETAIL # 1 TRASH CHUTE
 SHAFT STOPS AT THE BOTTOM OF THE 2ND FLOOR, IT DOES NOT
 CONTINUE THROUGH TO THE 1ST FLOOR ALTHOUGH THE SHAFT
 DOES PENETRATE THE 2ND FLOOR ASSEMBLY AND 1ST FLOOR
 WALL. PLEASE SEE 708.11 ENCLOSURE AT THE BOTTOM .
  
 11F) 2ND REQUEST. PLEASE PROVIDE MANUFACTURERS SPEC ON
 THE MATERIALS TO BE USED FOR THE REFUSE CHUTE.
 708.13.2.
  
 11G) 2ND REQUEST. 2010 FBC-B 708.13.6. AUTOMATIC
 SPRINKLERS SYSTEM. AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTION
 903.2.11.2. F] 903.2.11.2 RUBBISH AND LINEN CHUTES.
 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN
 CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING
 THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT
 ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE
 FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE
 FIRE SPRINKLERS.
  
 12) 2ND REQUEST. SHEET A-402 DETAILS A-601/ DETAIL # 1,
 A-602 DETAIL # 1 BOTH DEAL WITH ROOFTOP CONSTRUCTION.
 NOTE: METAL SPANISH TILE ROOFING TO BE ATTACHED TO 5/8?
 DENSEDECK WHICH WILL BE SECURED TO THE METAL DECK. NOTE
 THE PRODUCT APPROVALS FOR THE METAL ROOF TILE MAY NOT
 INCLUDE DENSE DECK AS THE DECKING MATERIAL THEY WERE
 TESTED WITH NOR THE METAL B DECK BELOW THAT. IF THAT IS
 THE CASE THE ENGINEER OF RECORD WILL NEED TO PROVIDE
 CALCULATIONS TO RESIST THE MOMENT OF UPLIFT. COMPONENTS
 & CLADDING 1609.6.4.4.1.
  
 13) 2ND REQUEST. SHEET A450 DETAILS 1-3 HAVE GENERAL
 NOTES AT DETAILS INDICATING SOLID SHEATHING THEN NOTES
 1 & 2 THE SPECIFIC NOTE INDICATES THE USE OF
 DENSE-DECK. PLEASE BE AWARE OF PRESSURES FROM THE
 PRODUCT APPROVAL WILL BE FOR 3/4 INCH OR 5/8 CDX
 PLYWOOD NOT FOR DENSE DECK, IF PLYWOOD IS USED IT NEEDS
 TO BE FIRE RETARDENT TREATED PLYWOOD SEE 603.1.1.
  
 13A) 2ND REQUEST. 2010 WPB ADMINISTRATIVE CODE DOES NOT
 ALLOW FOR THE USE OF TERMS SUCH AS ?EQUIVALENT, ? SUCH
 INFORMATION SHALL BE SPECIFIC AND TECHNICAL IN NATURE.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13B) 2ND REQUEST. THIS BUILDING TYPE IS INDICATED AS A
 TYPE I-B BUILDING PLEASE SEE 2010 FBC-B 603.1.1 FIRE
 RETARDANT TREATED WOOD AND ALLOWABLE USES.
  
 13C) 2ND REQUEST. PLEASE BE AWARE OF THE ROOFING
 MATERIALS (PRODUCT APPROVALS) THAT WERE TESTED AN THE
 THICKNESS OF THE ROOF DECKING SHEATHING, AND
 LIMITATIONS SET FORTH IN THE PRODUCT APPROVALS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 14) 2ND REQUEST. SHEET A452 ROOF DETAIL # 1 INDICATES
 THE USE OF LIGHT WEIGHT INSULATING CONCRETE AND THE
 INSULATION BEING TAPERED TO A MINIMAL AMOUNT. 2010
 ENERGY CODE 506.2.1 REQUIRES A MINIMUM OF R-19 FOR
 MULTI-FAMILY RESIDENCES, AS DEPICTED THERE IS LESS THAN
 A R-19 INSULATION AT THE ROOF DRAINS A MINIMUM OF R-19
 INSULATION NOT AN AVERAGE. SEE 2007 BOAF INFORMAL
 INTERPRETATION # 5438. WILL NEED ADDITIONAL INFORMATION
 ON THE LIGHTWEIGHT CONCRETE INSULATION.
  
 15) 2ND REQUEST. A-609 DETAIL # 2 INDICATES THE USE OF
 PRE-MANUFACTURED FOAM FACTORY # 419 TRIM ON THE
 EXTERIOR OF THE BUILDING AT A HEIGHT GREATER THAN 40
 FEET ABOVE GRADE. SEE 2010 FBC-B 1406.2.2 (2).
 COMBUSTIBLE EXTERIOR TRIM.
  
 16) 2ND REQUEST. SHEET A-630 INDICATEES STAIR RAILING
 DETAILS, NONE ARE SHOWN HANDRAILS OR GAURDRAILS. 2010
 FBC-B 1013.3 GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES IN DIAMETER. GAURDRAILS TO
 COMPLY WITH 1013.
  
 17) 2ND REQUEST. SHEET -634 DETAIL # 1 INDICATES THE
 USE OF ICYENE FOAM WALL INSULATION, PLEASE PROVIDE
 TESTING REPORT FOR THE ICYENE SHOWING COMPLIANCE WITH
 FBC-B 2603.4.
  
 18A) 2ND REQUEST, SHEET A-650 P2 PLEASE PROVIDE EITHER
 THE UL LISTING INDICATING THE I HOUR FIRE RATING.
  
 18B) 2ND REQUEST.SHEET A650 P2 INDICATES A STC RATING
 OF 49 FOR UL LISTING # U465, THE 2010 FBC-B 1207.2
 REQUIRES A STC RATING OF 50 (45 IF FIELD TESTED).
  
 18C) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2010
 FBC-B 1207.3 STRUCTURE BORNE SOUND, FLOOR CEILING
 ASSEMBLIES TO HAVE A INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50, (45 IF FIELD TESTED).
  
 19)2ND REQUEST A-202 PLAZA DECK, PLEASE SHOW COMPLIANCE
 WITH THE REQUIREMENT 2010 FBC-B 424.1.1 EFFECTIVE
 BARRIER REQUIREMENTS FOR POOLS AND SPAS & 424.1.3.1.9..
  
 20)COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 *****INFORMATIONAL*****PLEASE!!!!!!!: WHEN RESUBMITTING
 PLANS PLEASE INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-21 Cont ID  
Sent By jwitmer Date 2013-02-21 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2013-02-14 Time 08:08 Sent To  
Notes
2013-02-21 16:27:57 
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 1ST REVIEW
 FEB. 14/ 2013
 ACTION: DENIED
  
 1) PLEASE REVIEW THE ADDRESS FOR THIS PROJECT, THE
 CITY?S ADDRESS FOR THIS PCN NUMBER IS 631 EVERNIA WHERE
 AS THE PLANS INDICATE 627 EVERNIA, PLEASE CORRECT THE
 DISCREPANCY. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 THE CIVIL PLAN C-3 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 (3) SETS OF PLANS, PRODUCT APPROVALS WILL REQUIRED, ONE
 SET FOR THE SPECIAL INSPECTOR, ONE FOR THE FIELD, AND A
 COPY WILL BE KEPT ELECTRONICALLY BY THE BUILDING
 DEPARTMENT, FOR OUR RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. THIS MAY
 BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) MISSING SOILS REPORT BY ARDAMEN 11/19/2012, &
 12/27/2012. 2010 FBC-B 1803.2 SOILS INVESTIGATION
 REQUIRED.
  
 4) SHEET S-01 THE WIND DESIGN LIST THIS AS A ?B?
 EXPOSURE. PLEASE REVIEW 2010 FBC-B 1609.4.2 SURFACE
 ROUGHNESS C, THIS SITE MEETS THE REQUIREMENTS OF A C
 EXPOSURE WITH THE WIND DIRECTION FROM THE NW QUADRANT.
 THIS WILL EFFECT THE PRESSURES ILLUSTRATED UNDER THE
 WIND LOAD CHARTS FOR COMPONENTS AND CLADDING.
  
 5) SHEET S-01 WIND LOAD COMPONENTS AND CLADDING CHART.
 PLEASE INCLUDE THE COMPONENTS AND CLADDING PRESSURES
 FOR 10 SQ FT AND 20 SQ FT SINCE THESE WILL BE THE SIZES
 REQUIRED FOR A LOT OF WINDOWS (20 SQ FT) AND 10 SQ FT
 FOR THE ROOF TOP PRESSURES, WE USE THE AREA FOR
 FASTENERS WHICH IS THE 10 SQ FT.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) FOLDER CONTAINING WALL LOUVER NOA 11-0408.05 EXPIRED
 JULY 09/12. CUT SHEET FOR THE RUSKIN ACL 12450 LIST A
 NOA 11-0207.21 BUT NOT PROVIDED.
  
 9) SHEET LS-101:
 9A) THE SHEET INDICATES G02 TO BE THE FIRE PUMP ROOM
 WITH A PARTIAL 2 HR WALL AROUND THE ROOM PLEASE REVIEW
 2010 FBC-B 913.2.1 PROTECTION OF FIRE PUMP ROOMS ARE TO
 BE COMPLETELY SURROUNDED BY A 2 HOUR WALL, ? SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING?? PLEASE ALSO
 PROVIDE OPENING PROTECTION FOR THE DOORWAY 2010 FBC-B
 TABLE 715.4.
  
 9) LS-101
  
 9B) SHEET A-201 ALSO INDICATES A PUMP ROOM 020, IS THIS
 A FIRE PUMP ROOM?
  
 9C) THE 2010 FBC-B FIRE PUMP ROOMS 913.2 ARE TO BE
 PROTECTED AGAINST THE INTERRUPTION OF SERVICE AND BE
 PROTECTED IN ACCORDANCE WITH NFPA 20 AGAINST FLOODING.
 WITH THE FIRE PUMP IN THE BASEMENT IF THERE IS A FIRE
 WHERE THE FIRE SPRINKLERS DO GO OFF, WHAT WILL STOP THE
 WATER FROM RISING IN THE FIRE PUMP ROOM.
  
 9D) ROOM G-03 INDICATES THAT IT IS A STORAGE ROOM WHAT
 IS THE PURPOSE OF THIS ROOM? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 9E) THIS SHEET INDICATES STORAGE G04, THE PLANS DO NOT
 INDICATE DOORS INTO THIS SPACE PLEASE PROVIDE
 ADDITIONAL INFORMATION. 107.2.1.3.
  
 9F) THE PLANS INDICATE A LIFT G10 PLEASE PROVIDE
 ADDITIONAL INFORMATION, WHAT WILL THIS LIFT BE USED
 FOR? 107.2.1.3.
  
 10) SHEET A-201:
 10A) IN BOTH STAIRWELLS THE NORTH AND EAST CONTINUE
 BELOW GRADE, PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 1022.7 DISCHARGE IDENTIFICATION. A STAIRWAY IN AN EXIT
 ENCLOSURE SHALL NOT CONTINUE BELOW ITS LEVEL OF EXIT
 DISCHARGE UNLESS AN APPROVED BARRIER IS PROVIDED AT THE
 LEVEL OF EXIT DISCHARGE TO PREVENT PERSONS FROM
 UNINTENTIONALLY CONTINUING INTO LEVELS BELOW.
 DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS SPECIFIED
 IN SECTION 1011.
  
 10B) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B: [F]
 914.1 SHAFTWAY MARKINGS.
 VERTICAL SHAFTS SHALL BE IDENTIFIED AS REQUIRED BY
 SECTIONS 914.1.1 AND 914.1.2.
  
 [F] 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS.
 OUTSIDE OPENINGS ACCESSIBLE TO THE FIRE DEPARTMENT AND
 THAT OPEN DIRECTLY ON A HOISTWAY OR SHAFTWAY
 COMMUNICATING BETWEEN TWO OR MORE FLOORS IN A BUILDING
 SHALL BE PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED
 LETTERS AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE
 BACKGROUND. SUCH WARNING SIGNS SHALL BE PLACED SO AS TO
 BE READILY DISCERNIBLE FROM THE OUTSIDE OF THE
 BUILDING.
  
 [F] 914.1.2 INTERIOR ACCESS TO SHAFTWAYS.
 DOOR OR WINDOW OPENINGS TO A HOISTWAY OR SHAFTWAY FROM
 THE INTERIOR OF THE BUILDING SHALL BE PLAINLY MARKED
 WITH THE WORD ?SHAFTWAY? IN RED LETTERS AT LEAST 6
 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. SUCH
 WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE.
  
 EXCEPTION: MARKINGS SHALL NOT BE REQUIRED ON SHAFTWAY
 OPENINGS THAT ARE READILY DISCERNIBLE AS OPENINGS ONTO
 A SHAFTWAY BY THE CONSTRUCTION OR ARRANGEMENT.
  
 [F] 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
 10) SHEET A-201:
 10C) PROVIDE COMPLIANCE WITH F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 10D) MACHINE ROOM-LESS ELEVATORS SHEET A-621. KONE
 ECOSPACE. WILL NEED MANUFACTURERS REQUIREMENTS FOR
 INSTALLATION. MAY STILL NEED TO INCORPORATE HOIST WAY
 VENTING REQUIREMENTS FOUND IN 2010 FBC-B 3004. PROVIDE
 COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE AN
 AMBULANCE STRETCHER.
  
 11) SHEET A202 TRASH CHUTE
 11A) THE NORTH STAIRWELL INDICATES THE TRASH CHUTE
 ACTUALLY PENETRATING THE 2 HOUR FIRE RATED STAIR
 ENCLOSURE. PLEASE REVIEW 2010 FBC-B 1022.4 PENETRATIONS
 INTO & THROUGH AN EXIT ENCLOSURE.
  
 11B) THE TRASH CHUTE VESTIBULE COMMON TO 2ND- 6TH
 FLOORS, BEING LOCATED IN A VESTIBULE. THE 2010 FBC-B
 708.13.3 REQUIRES REFUSE CHUTES TO HAVE A SEPARATE
 ACCESS ROOM TO BE A 1 HR FIRE BARRIER ENCLOSURE AND ?
 HR OPENING PROTECTIVE?S. 708.13.1 OPENINGS SHALL NOT
 OPEN INTO CORRIDORS. 708.13.1.
  
 11C) THE TRASH CHUTE IS DEPICTED TO BE IN A RATED SHAFT
 WITH A A/C DUCT IN THE SAME ENCLOSURE. 2010 FBC-B
 708.13.1 A SHAFT ENCLOSURE CONTAINING A REFUSE CHUTE
 SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE
 ENCLOSED IN ACCORDANCE WITH 708.4.
  
 11D) SHEET A-601DETAIL # 1 INDICATES THE REFUSE CHUTE
 GOES THROUGH THE ROOF BUT THE SHAFT ENCLOSURE STOPS AT
 THE CEILING OF THE 6TH FLOOR, PLEASE REVIEW 708.12
 ENCLOSURES AT THE TOP AND THE REQUIRED FIRE RATING OF
 MATERIALS.
  
 11E) SHEET A-601 DETAIL # 1 TRASH CHUTE SHAFT STOPS AT
 THE BOTTOM OF THE 2ND FLOOR, IT DOES NOT CONTINUE
 THROUGH TO THE 1ST FLOOR ALTHOUGH THE SHAFT DOES
 PENETRATE THE 2ND FLOOR ASSEMBLY AND 1ST FLOOR WALL.
 PLEASE SEE 708.11 ENCLOSURE AT THE BOTTOM .
  
 11F) PLEASE PROVIDE MANUFACTURERS SPEC ON THE MATERIALS
 TO BE USED FOR THE REFUSE CHUTE. 708.13.2.
  
 11G) 2010 FBC-B 708.13.6. AUTOMATIC SPRINKLERS SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2. F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN
 CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING
 THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT
 ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE
 FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE
 FIRE SPRINKLERS.
  
 12) SHEET A-402 DETAILS A-601/ DETAIL # 1, A-602 DETAIL
 # 1 BOTH DEAL WITH ROOFTOP CONSTRUCTION. NOTE: METAL
 SPANISH TILE ROOFING TO BE ATTACHED TO 5/8? DENSEDECK
 WHICH WILL BE SECURED TO THE METAL DECK. NOTE THE
 PRODUCT APPROVALS FOR THE METAL ROOF TILE MAY NOT
 INCLUDE DENSE DECK AS THE DECKING MATERIAL THEY WERE
 TESTED WITH NOR THE METAL B DECK BELOW THAT. IF THAT IS
 THE CASE THE ENGINEER OF RECORD WILL NEED TO PROVIDE
 CALCULATIONS TO RESIST THE MOMENT OF UPLIFT. COMPONENTS
 & CLADDING 1609.6.4.4.1.
  
 13) SHEET A450 DETAILS 1-3 HAVE GENERAL NOTES AT
 DETAILS INDICATING SOLID SHEATHING THEN NOTES 1 & 2 THE
 SPECIFIC NOTE INDICATES THE USE OF ?? PLYWOOD SHEATHING
 OR EQUIVALENT.
  
 13A) 2010 WPB ADMINISTRATIVE CODE DOES NOT ALLOW FOR
 THE USE OF TERMS SUCH AS ?EQUIVALENT, ? SUCH
 INFORMATION SHALL BE SPECIFIC AND TECHNICAL IN NATURE.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13B) THIS BUILDING TYPE IS INDICATED AS A TYPE I-B
 BUILDING PLEASE SEE 2010 FBC-B 603.1.1 FIRE RETARDANT
 TREATED WOOD AND ALLOWABLE USES.
  
 13C) PLEASE BE AWARE OF THE ROOFING MATERIALS (PRODUCT
 APPROVALS) THAT WERE TESTED AN THE THICKNESS OF THE
 ROOF DECKING SHEATHING, AND LIMITATIONS SET FORTH IN
 THE PRODUCT APPROVALS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 14) SHEET A452 ROOF DETAIL # 1 INDICATES THE USE OF
 LIGHT WEIGHT INSULATING CONCRETE AND THE INSULATION
 BEING TAPERED TO A MINIMAL AMOUNT. 2010 ENERGY CODE
 506.2.1 REQUIRES A MINIMUM OF R-19 FOR MULTI-FAMILY
 RESIDENCES, AS DEPICTED THERE IS LESS THAN A R-19
 INSULATION AT THE ROOF DRAINS A MINIMUM OF R-19
 INSULATION NOT AN AVERAGE. SEE 2007 BOAF INFORMAL
 INTERPRETATION # 5438. WILL NEED ADDITIONAL INFORMATION
 ON THE LIGHTWEIGHT CONCRETE INSULATION.
  
 15) A-609 DETAIL # 2 INDICATES THE USE OF
 PRE-MANUFACTURED FOAM FACTORY # 419 TRIM ON THE
 EXTERIOR OF THE BUILDING AT A HEIGHT GREATER THAN 40
 FEET ABOVE GRADE. SEE 2010 FBC-B 1406.2.2 (2).
 COMBUSTIBLE EXTERIOR TRIM.
  
 16) SHEET A-631 DETAIL# 1, A HANDRAIL SECTION /
 GUARDRAIL, THE PLANS INDICATE THE PICKETS TO BE 5
 INCHES ON CENTER AND A 1X1 INCH PICKET. 2010 FBC-B
 1013.3 GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES IN DIAMETER.
  
 17) SHEET -634 DETAIL # 1 INDICATES THE USE OF ICYENE
 FOAM WALL INSULATION, PLEASE PROVIDE TESTING REPORT FOR
 THE ICYENE SHOWING COMPLIANCE WITH FBC-B 2603.4.
  
 18A) SHEET A-650 P2 PLEASE PROVIDE EITHER THE UL
 LISTING INDICATING THE I HOUR FIRE RATING.
  
 18B) SHEET A650 P2 INDICATES A STC RATING OF 49 FOR UL
 LISTING # U465, THE 2010 FBC-B 1207.2 REQUIRES A STC
 RATING OF 50 (45 IF FIELD TESTED).
  
 18C) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1207.3
 STRUCTURE BORNE SOUND, FLOOR CEILING ASSEMBLIES TO HAVE
 A INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50,
 (45 IF FIELD TESTED).
  
 19) A-202 PLAZA DECK, PLEASE SHOW COMPLIANCE WITH THE
 REQUIREMENT 2010 FBC-B 424.1.1 EFFECTIVE BARRIER
 REQUIREMENTS FOR POOLS AND SPAS.
  
 20) SHEET S-01 INDICATES THE WIND EXPOSURE TO BE A ?B?
 EXPOSURE, THE 2010 FBC-B 1609.4.2 SURFACE ROUGHNESS
 WHERE WIND CAN RACE IN ANY QUADRANT 150 WIDE AND 600
 FEET LONG, EXPOSURE C. UPDATE EXPOSURE AND ASSOCIATED
 PRESSURE TABLES.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 11:14 Rev Time 0.00
Received By rlecky Date 2013-03-22 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 15:18 Rev Time 0.00
Received By rlecky Date 2013-02-06 Time 14:37 Sent To  
Notes
2013-02-22 15:22:5413010504
 631 EVERNIA STREET
 FIVE STORY CONDO
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 E2.3
 ILLUMINATION OF THE MEANS OF EGRESS SHALL BE CONTINUOUS
 DURING THE TIME LIGHTING IS NEEDED. VERIFY THAT ALL
 REQUIRED EMERGENCY LIGHTING HAS BATTERY BACK UP. FBC
 1006.1.2
  
 E3.1
 ADDITIONAL RECEPTACLES ARE REQUIRED IN TEH KITCHEN AND
 AT THE ENTRANCE WALL AREA. NEC 210.52
 NOTE 7 IS NOT APPROPRIATE BECAUSE NON METALLIC SHEATHED
 CABLE IS NOT PERMITTED IN THIS OCCUPANCY. NEC 334.12
  
 E4.1
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 THE RESIDENTIAL 400 AMP METER CENTER APPEARS TO REQUIRE
 AN ADDITIONAL SET OF FEEDERS. NEC 215.5
  
 PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE PUMP
 FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL WIRING
 AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED.
 INDICATE THE FIRE RATING AND MATERIAL REQUIRED. NEC
 695.6, 695.14
  
 VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORY?S. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT
 MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN
 THE MOTOR IS OPERATING AT 115% OF THE FULL ?LOAD
 CURRENT RATING. NEC 695.6 , 695.7
  
 INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE
 IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY
 INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC
 700.9
  
 PROVIDE SIGNS AT THE SERVICE INDICATING THE TYPE AND
 LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC
 700.8
  
 PROVIDE PANEL SCHEDULES FOR PANEL P AND PANEL H1A. FBC
 107
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By Mgonzale Date 2013-06-07 Time   Rev Time 1.00
Received By mgonzale Date 2013-06-07 Time   Sent To I
Notes
2013-06-07 10:12:23PLANS FOR SITE DEVELOPMENT HAVE BEEN APPROVED THRU ESD.
  
 SATISFACTORY.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2013-05-07 Cont ID  
Sent By wjolin Date 2013-05-07 Time 10:08 Rev Time 0.00
Received By wjolin Date 2013-05-07 Time 09:47 Sent To  
Notes
2013-05-07 10:08:50610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #5 COMPLETED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-04-23 Cont ID  
Sent By wjolin Date 2013-04-23 Time 13:42 Rev Time 0.00
Received By wjolin Date 2013-04-23 Time 09:05 Sent To  
Notes
2013-04-23 13:42:19610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 SHEET T101: ADD THE FIRE SPRINKLER ENGINEERING
 DOCUMENTS TO THEDRAWING SHEET INDEX.
  
 SHEET FP1- FP12: CORRECT THE SITE ADDRESS FROM 627
 EVERNIA STREET TO 631 EVERNIA STREET.
  
 SHEET FP3: PROVIDE SPRINKLER PROTECTION IN EQUIPMENT
 STORAGE ROOM LOCATED ON POOL DECK.
  
 SHEET FP3: THERE APPEAR TO BE SEVERAL SOFFITS
 OBSTRUCTING SPRINKLER SPRAY IN AND AROUND THE CLUBHOUSE
 AREA. FOR EXAMPLE SPRINKLERS ARE SHOWN 11'-0' AFF IN
 THE LIGHT COVE ADJACENT TO STEPPED CEILINGS OF 10'-0"
 AND 9'-0" AFF. THE SPRINKLER LOCATIONS DO NOT APPEAR TO
 COMPLY WITH OBSTRUCTION TABLE 8.6.5.1.2 (NFPA 13 - 2007
 EDITION).
  
 SHEET FP5: WEST STAIR - IT IS DIFFICULT TO DETERMINE IF
 THE CORRIDOR SPRINKLER WILL PROTECT THE STAIR ENTRY
 VESTIBULE.
  
 SHEET FP12: PROVIDE 2-1/2" FIRE DEPARTMENT STANDPIPE
 HOSE VALVES WITHOUT THE 1-1/2" REDUCER.
  
 FIRE ALARM: PER LOCAL AMENDMENT; DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL ALARM IN LIEU OF A SUPERVISORY
 ALARM CONDITION.
  
 SHEET FA2.1: PROVIDE FIRE ALARM ANNUNCIATOR PANEL IN
 LOBBY #001
  
 SHEET FA2.1: PROVIDE NOTIFICATION APPLIANCE IN LAUNDRY
 #015.
  
 SHEET FA4.1: PROVIDE NOTIFICATION APPLIANCE IN COMMON
 LAUNDRY ROOM. TYPICAL EACH FLOOR.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-04-22 Cont ID  
Sent By wjolin Date 2013-04-22 Time 09:48 Rev Time 0.00
Received By wjolin Date 2013-04-22 Time 08:01 Sent To  
Notes
2013-04-22 09:23:17610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE PROTECTION DRAWINGS FP-1 THROUGH
 FP-12 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW. ALSO, THESE DRAWINGS
 DO NOT APPEAR IN THE DRAWING INDEX SHEET T-101.
 RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION
 DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE
 ISSUED.
 ORIGINAL COMMENT - FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE PROTECTION DRAWINGS FP-1 THROUGH
 FP-12 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW. ALSO, THESE DRAWINGS
 DO NOT APPEAR IN THE DRAWING INDEX SHEET T-101.
 RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION
 DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE
 ISSUED.
 ORIGINAL COMMENT - PROVIDE AN AUTOMATIC CLASS I
 STANDPIPE SYSTEM THROUGHOUT THE BUILDING INCLUDING THE
 PARKING GARAGE.
  
 RESPONSE COMMENT (04/22/13): THE ELECTRONIC TRACKING
 SOFTWARE INDICATES THIS IS STILL DRAWING VERSION #2
 (SUBMITTED 03/14/13) SO NOTHING HAS BEEN CHANGED SINCE
 THE COMMENT.
 RESPONSE COMMENT (03/27/13): SEVERAL OF THE DOORS DO
 NOT INDICATE THE TYPE OF HARDWARE TO BE USED. ON SHEET
 A-202 FOR EXAMPLE, DOORS LOCATED IN CLUBHOUSE #002 HAVE
 DOORS #002A (MARK SF-8) AND #002D (MARK F-1) THAT SERVE
 AN ASSEMBLY USE WITH AN OCCUPANT LOAD EXCEEDING 100
 PERSONS BUT THE DOOR SCHEDULE DOES NOT INDICATE THE USE
 OF PANIC HARDWARE. ANOTHER EXAMPLE IS NORTH STAIR DOOR
 #002E (MARK SS15) WHERE THE PLAN STATES, "FIRE EXIT
 HARDWARE" BUT THE DOOR SCHEDULE DOES NOT. ON SHEET
 A-201, DOOR #G03 (MARK F2) INDICATES PANIC HARDWARE IN
 THE SCHEDULE BUT THIS IS A FIRE RATED DOOR NEEDING FIRE
 EXIT HARDWARE. THESE ARE JUST SOME EXAMPLES. PLEASE
 VERIFY ALL DOORS THROUGHOUT PLANS.
  
 RESPONSE COMMENT (04/22/13): THE ELECTRONIC TRACKING
 SOFTWARE INDICATES THIS IS STILL DRAWING VERSION #2
 (SUBMITTED 03/14/13); NO FLOOR DRAIN SHOWN ON SHEET
 P1.2.
 RESPONSE COMMENT (03/27/13): STILL NO FLOOR DRAIN SHOWN
 ON SHEET P1.2.
 REPEAT COMMENT - SHEET P1.2: NO FLOOR DRAIN PROVIDED IN
 FIRE PUMP ROOM.
  
 RESPONSE COMMENT (04/22/13): THE ELECTRONIC TRACKING
 SOFTWARE INDICATES THIS IS STILL DRAWING VERSION #1
 (SUBMITTED 02/16/13).THE FLOOR PLAN FOR SHEET MEP1.1
 NEEDS TO BE UPDATED TO REFLECT THE ARCHITECTURAL
 CHANGES SHOWING THE 2-HOUR FIRE BARRIER SEPARATION
 BETWEEN THE STAIR SHAFT AND TRASH CHUTE.
 RESPONSE COMMENT (03/27/13): NON-ESSENTIAL STAIR
 EQUIPMENT IS STILL SHOWN ON THE PLAN.
 REPEAT COMMENT - SHEET MEP1.1: STAIR SHAFT PENETRATIONS
 SHALL BE LIMITED TO EQUIPMENT ESSENTIAL TO THE FUNCTION
 OF THE STAIR (SPRINKLERS, STANDPIPES, STAIR
 PRESSURIZATION DUCTS, ETC.)
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE ALARM DRAWINGS FA1.1 THROUGH
 FA1.7 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW.
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: NO FIRE ALARM CONSTRUCTION DOCUMENTS COULD
 BE LOCATED. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES WITH VOICE ANNOUNCEMENTS AND MICROPHONE.
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE ALARM DRAWINGS FA1.1 THROUGH
 FA1.7 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW.
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PROVIDE PHASE 1 RECALL AND PHASE II
 FIREFIGHTER EMERGENCY OPERATIONS FOR ELEVATORS. PROVIDE
 SMOKE DETECTION IN ELEVATOR LOBBY AND MACHINE ROOM
 AREAS. ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE
 ALARM SYSTEM.
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE ALARM DRAWINGS FA1.1 THROUGH
 FA1.7 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW.
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 RESPONSE COMMENT (04/22/13): THE ARCHITECTURAL RESPONSE
 LETTER INDICATES FIRE ALARM DRAWINGS FA1.1 THROUGH
 FA1.7 HAVE BEEN UPLOADED; HOWEVER, THESE DRAWINGS COULD
 NOT BE FOUND DURING PLAN REVIEW.
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PROVIDE TAMPER SWITCHES FOR SUPERVISING THE
 BACKFLOW PREVENTER IN THE OPEN POSITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-03-27 Cont ID  
Sent By wjolin Date 2013-03-27 Time 13:18 Rev Time 0.00
Received By wjolin Date 2013-03-27 Time 10:39 Sent To  
Notes
2013-03-27 11:12:59610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT (03/27/13): PLEASE PROVIDE A NOTE ON
 THE PLANS.
 ORIGINAL COMMENT: ALL CONSTRUCTION WORK SHALL CONFORM
 TO THE REQUIREMENTS OF NFPA 241. THE FIRE PROTECTION
 STANDPIPE SYSTEM SHALL BE EXTENDED TO EACH FLOOR AS
 EACH FLOOR IS CONSTRUCTED. PORTABLE FIRE EXTINGUISHERS
 SHALL BE LOCATED THROUGHOUT THE CONSTRUCTION AREA.
 SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED
 OUTSIDE THE BUILDING, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION
 DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE
 ISSUED.
 ORIGINAL COMMENT - FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION
 DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE
 ISSUED.
 ORIGINAL COMMENT - PROVIDE AN AUTOMATIC CLASS I
 STANDPIPE SYSTEM THROUGHOUT THE BUILDING INCLUDING THE
 PARKING GARAGE.
  
 RESPONSE COMMENT (03/27/13): SHEET A202 STILL INDICATES
 "TRASH CHUTE THROUGH WALL."
 ORIGINAL COMMENT - SHEET A202: TRASH CHUTE STAIR
 PENETRATIONS ARE NOT PERMITTED ON ANY LEVEL PER SECTION
 7.1.3.2 (NFPA 101).
  
 RESPONSE COMMENT (03/27/13): SEVERAL OF THE DOORS DO
 NOT INDICATE THE TYPE OF HARDWARE TO BE USED. ON SHEET
 A-202 FOR EXAMPLE, DOORS LOCATED IN CLUBHOUSE #002 HAVE
 DOORS #002A (MARK SF-8) AND #002D (MARK F-1) THAT SERVE
 AN ASSEMBLY USE WITH AN OCCUPANT LOAD EXCEEDING 100
 PERSONS BUT THE DOOR SCHEDULE DOES NOT INDICATE THE USE
 OF PANIC HARDWARE. ANOTHER EXAMPLE IS NORTH STAIR DOOR
 #002E (MARK SS15) WHERE THE PLAN STATES, "FIRE EXIT
 HARDWARE" BUT THE DOOR SCHEDULE DOES NOT. ON SHEET
 A-201, DOOR #G03 (MARK F2) INDICATES PANIC HARDWARE IN
 THE SCHEDULE BUT THIS IS A FIRE RATED DOOR NEEDING FIRE
 EXIT HARDWARE. THESE ARE JUST SOME EXAMPLES. PLEASE
 VERIFY ALL DOORS THROUGHOUT PLANS.
 REPEAT COMMENT - SHEET A800: FIRE-RATED DOORS SHOULD BE
 EQUIPPED WITH FIRE EXIT HARDWARE IN LIEU OF THE
 SPECIFIED PANIC HARDWARE.
  
 RESPONSE COMMENT (03/27/13): STILL NO FLOOR DRAIN SHOWN
 ON SHEET P1.2.
 REPEAT COMMENT - SHEET P1.2: NO FLOOR DRAIN PROVIDED IN
 FIRE PUMP ROOM.
  
 RESPONSE COMMENT (03/27/13): NON-ESSENTIAL STAIR
 EQUIPMENT IS STILL SHOWN ON THE PLAN.
 REPEAT COMMENT - SHEET MEP1.1: STAIR SHAFT PENETRATIONS
 SHALL BE LIMITED TO EQUIPMENT ESSENTIAL TO THE FUNCTION
 OF THE STAIR (SPRINKLERS, STANDPIPES, STAIR
 PRESSURIZATION DUCTS, ETC.)
  
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: NO FIRE ALARM CONSTRUCTION DOCUMENTS COULD
 BE LOCATED. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES WITH VOICE ANNOUNCEMENTS AND MICROPHONE.
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PROVIDE PHASE 1 RECALL AND PHASE II
 FIREFIGHTER EMERGENCY OPERATIONS FOR ELEVATORS. PROVIDE
 SMOKE DETECTION IN ELEVATOR LOBBY AND MACHINE ROOM
 AREAS. ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE
 ALARM SYSTEM.
  
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1
 THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX
 SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS.
 ELECTRICAL: PROVIDE TAMPER SWITCHES FOR SUPERVISING THE
 BACKFLOW PREVENTER IN THE OPEN POSITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-07 Cont ID  
Sent By wjolin Date 2013-02-07 Time 10:06 Rev Time 0.00
Received By wjolin Date 2013-02-06 Time 09:50 Sent To  
Notes
2013-02-06 15:13:02610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (627 EVERNIA STREET)
 DOES NOT MATCH THE ADDRESS PROVIDED ON THE PERMIT
 APPLICATION (631 EVERNIA STREET).
  
 PROVIDE A FREESTANDING SIGN (IN FRONT OF THE FIRE
 DEPARTMENT CONNECTION) READING, "FIRE LANE - NO PARKING
 BY ORDER OF THE FIRE DEPARTMENT." SIGN SHALL BE 12" X
 18" WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL
 BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF
 THE SIGN.
  
 ALL CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. THE FIRE PROTECTION STANDPIPE SYSTEM SHALL
 BE EXTENDED TO EACH FLOOR AS EACH FLOOR IS CONSTRUCTED.
 PORTABLE FIRE EXTINGUISHERS SHALL BE LOCATED THROUGHOUT
 THE CONSTRUCTION AREA. SMOKING SHALL BE PROHIBITED
 EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED OUTSIDE THE BUILDING, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER
 THE BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS
 CAN THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE
 ENGINEERED CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN AUTOMATIC CLASS I STANDPIPE SYSTEM
 THROUGHOUT THE BUILDING INCLUDING THE PARKING GARAGE.
  
 PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH 7.2.2.5 (A) THROUGH
 (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (M) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 PER NFPA 101 SECTION 7.2.2.5.4.2: WHEREVER AN ENCLOSED
 STAIR REQUIRES TRAVEL IN AN UPWARD DIRECTION TO REACH
 THE LEVEL OF EXIT DISCHARGE, SPECIAL SIGNS WITH
 DIRECTIONAL INDICATORS SHOWING THE DIRECTION TO THE
 LEVEL OF EXIT DISCHARGE SHALL BE PROVIDED AT EACH FLOOR
 LEVEL LANDING FROM WHICH UPWARD DIRECTION OF TRAVEL IS
 REQUIRED.
  
 SHEET LS100: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET LS102: PROVIDE FLOOR PAINT (OR SIMILAR MARKINGS)
 LEADING FROM EAST STAIR ENCLOSURE TO REAR EXTERIOR EXIT
 STAIR.
  
 SHEET LS102: INDICATE THE FIRE RATING OF THE WALLS FOR
 THE FIRE PUMP ROOM AND THE TRASH COLLECTION ROOM.
  
 SHEET A202: TRASH CHUTE STAIR PENETRATIONS ARE NOT
 PERMITTED ON ANY LEVEL PER SECTION 7.1.3.2 (NFPA 101).
  
 SHEET A800: NONE OF THE DOOR NUMBERS (001A, 001B, 016A
 ETC.) CAN BE LOCATED IN THE DOOR SCHEDULE.
  
 SHEET A800: FIRE-RATED DOORS SHOULD BE EQUIPPED WITH
 FIRE EXIT HARDWARE IN LIEU OF THE SPECIFIED PANIC
 HARDWARE.
  
 SHEET P1.2: NO FLOOR DRAIN PROVIDED IN FIRE PUMP ROOM.
  
 SHEET MEP1.1: STAIR SHAFT PENETRATIONS SHALL BE LIMITED
 TO EQUIPMENT ESSENTIAL TO THE FUNCTION OF THE STAIR
 (SPRINKLERS, STANDPIPES, STAIR PRESSURIZATION DUCTS,
 ETC.)
  
 SHEET E2.1: EXIT SIGN NEEDS TO IDENTIFY EXIT IS THROUGH
 A SIDE-SWINGING DOOR NOT A ROLLING OVERHEAD DOOR.
  
 SHEET E2.2: OCCUPANTS SHOULD NOT BE DIRECTED TO EXIT
 THROUGH THE FITNESS CENTER.
  
 SHEET E2.2: PROVIDE EXTERIOR EXIT SIGNS IDENTIFYING THE
 EXTERIOR STAIRS AS EXITS.
  
 SHEET E2.2: PROVIDE LIGHTING AND EMERGENCY LIGHTING
 ALONG THE ENTIRE EXIT PATHS LEADING TO A PUBLIC WAY.
  
 ELECTRICAL: NO FIRE ALARM CONSTRUCTION DOCUMENTS COULD
 BE LOCATED. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES WITH VOICE ANNOUNCEMENTS AND MICROPHONE.
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 ELECTRICAL: PROVIDE PHASE 1 RECALL AND PHASE II
 FIREFIGHTER EMERGENCY OPERATIONS FOR ELEVATORS. PROVIDE
 SMOKE DETECTION IN ELEVATOR LOBBY AND MACHINE ROOM
 AREAS. ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE
 ALARM SYSTEM.
  
 ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 ELECTRICAL: PROVIDE TAMPER SWITCHES FOR SUPERVISING THE
 BACKFLOW PREVENTER IN THE OPEN POSITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 17:36 Sent To  
Notes
2014-04-18 17:36:44ZONING PROVISOS: INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2014-01-21 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2014-01-14 Time 09:16 Sent To  
Notes
2014-01-15 09:17:19POST TENSION CABLES SHOP DRAWINGS SENT TO J. WITMER'S
 DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2014-01-21 Cont ID  
Sent By jwitmer Date 2013-11-26 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2013-11-26 Time 10:00 Sent To  
Notes
2013-11-27 10:01:23POST TENSION CABLE SHOP DRAWINGS SUBMITTAL SENT TO
 JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2013-10-31 Time 17:12 Sent To  
Notes
2013-10-31 17:12:32INCOMING SENT TO JW DESK .JW

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-10-31 Cont ID  
Sent By jwitmer Date 2013-10-19 Time 17:10 Rev Time 0.00
Received By jwitmer Date 2013-10-17 Time 10:32 Sent To  
Notes
2013-10-17 10:33:34TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-05-30 Cont ID  
Sent By rregueir Date 2013-05-07 Time 08:31 Rev Time 0.00
Received By rregueir Date 2013-05-03 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2013-05-02 Time   Rev Time 0.00
Received By cpuell Date 2013-04-10 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-04-05 Time   Rev Time 0.00
Received By rregueir Date 2013-03-15 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-02-22 Time   Rev Time 0.00
Received By rlecky Date 2013-01-30 Time 09:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2013-06-06 Cont ID  
Sent By jwitmer Date 2013-06-06 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2013-06-06 Time 11:44 Sent To  
Notes
2013-06-06 11:46:21IMPACT FEE ASSESSMENT
 JUNE 03/2013
 MU-2013-12047
 $357678.65

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-04-22 Cont ID  
Sent By jwitmer Date 2013-04-22 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 13:30 Sent To  
Notes
2013-04-22 13:30:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-04-22 Cont ID  
Sent By jwitmer Date 2013-04-22 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 13:30 Sent To  
Notes
2013-04-22 13:30:16BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-02-21 Cont ID  
Sent By jwitmer Date 2013-02-21 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2013-02-21 Time 16:26 Sent To  
Notes
2013-02-21 16:26:40BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-02 Cont ID  
Sent By rregueir Date 2013-05-02 Time 14:50 Rev Time 0.00
Received By hmoser Date 2013-05-02 Time 14:50 Sent To  
Notes
2013-05-02 14:51:59PASS PROVISO
 1) DETAIL # 8 PAGE M0.2 PROVIDE THE BOLT SIZE THAT
 ANCHORS THE CURB TO THE ROOF FROM THE ENGINEER AT ROUGH
 INSPECTION.
 PER SECTION 301.12 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE DUCT TO
 STAND AND
 STAND TO ROOF TIE DOWN AT ROUGH INSPECTION .
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 10:55 Rev Time 0.00
Received By hmoser Date 2013-02-06 Time 10:55 Sent To  
Notes
2013-02-06 11:30:21PASS PROVISO
 1) DETAIL # 8 PAGE M0.2 PROVIDE THE BOLT SIZE THAT
 ANCHORS THE CURB TO THE ROOF FROM THE ENGINEER AT ROUGH
 INSPECTION.
 PER SECTION 301.12 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE DUCT TO
 STAND AND
 STAND TO ROOF TIE DOWN AT ROUGH INSPECTION .
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 3) IN REGARDS TO PAGE M1.1 REFER TO SECTION 404
 ENCLOSED PARKING GARAGES
 CONCENTRATION OF CARBON MONOXIDE 25 PARTS PER MILLION.
 2010 FBC (M)
 4) PROVIDE THE MANUFACTURERS INSTRUCTIONS FOR THE
 DRYERS AT ROUGH INSPECTION
 PER SECTION 504.6.4.2 FBC (M)
 5) PROVIDE A DUCT SMOKE DETECTOR FOR AHU #2.
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC (M)
 6) PROVIDE METAL DOORS FOR AHU- 1A AND AHU-1B
 PER SECTION 602.2.1 MATERIALS WITHIN PLENUMS .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 15:28 Rev Time 0.00
Received By lwagner Date 2013-05-08 Time 15:18 Sent To  
Notes
2013-05-08 15:30:36P1.2 & P2.1 OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-03-25 Cont ID  
Sent By lwagner Date 2013-03-25 Time 09:21 Rev Time 0.00
Received By lwagner Date 2013-03-22 Time 08:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-11 Cont ID  
Sent By lwagner Date 2013-02-11 Time 09:56 Rev Time 0.00
Received By lwagner Date 2013-02-05 Time 15:48 Sent To  
Notes
2013-02-08 14:24:44FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. THE CENTRAL LAUNDRY ROOMS WILL REQUIRE A 3" FLOOR
 DRAIN.
 412.4 PUBLIC LAUNDRIES AND CENTRAL WASHING FACILITIES.
 IN PUBLIC COIN-OPERATED LAUNDRIES AND IN THE CENTRAL
 WASHING FACILITIES OF MULTIPLE-FAMILY DWELLINGS, THE
 ROOMS CONTAINING AUTOMATIC CLOTHES WASHERS SHALL BE
 PROVIDED WITH FLOOR DRAINS LOCATED TO READILY DRAIN THE
 ENTIRE FLOOR AREA. SUCH DRAINS SHALL HAVE A MINIMUM
 OUTLET OF NOT LESS THAN 3 INCHES (76 MM) IN DIAMETER.
  
 2. SHEET P 0.1 PLASTIC PAN IN PLENUM IS REQUIRED TO BE
 PLENUM RATED OR METAL.
 SEE M602.2.1 MATERIALS WITHIN PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.6, MATERIALS WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 3. SHEET P 2.3 SHOWS A 3/4" WATER MAIN SUPPLYING A 1"
 PIPE FOR THE POOL.
  
 4. SHEET P 3.1 THE WATTS BRVT VALVE IS NOT SHOWN WITH A
 DRAIN LINE. IF THE DRAIN IS TO THE PAN THE WATER HEATER
 WILL BE REQUIRED TO BE RAISED TO BE OUT OF ANY RESIDUAL
 WATER IN THE PAN.
  
 5. SHEET A 401 SHOWS A TOTAL OF 14 ROOF DRAINS AND 13
 (ONE IS MISSING) EMERGENCY OVERFLOW DRAINS. SHEET P.2.4
 SHOWS A TOTAL OF 21 ROOF DRAINS AND NO EMERGENCY
 OVERFLOW DRAINS.
 ALSO, SECONDARY ROOF DRAINS ARE REQUIRED TO BE ON A
 SEPARATE SYSTEM.
 1107.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT
 OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM.
 DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT
 WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONNEL.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2014-09-08 Time 07:56 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2013-06-07 Cont ID  
Sent By jwitmer Date 2013-06-07 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2013-06-07 Time 15:00 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2013-03-25 Cont ID  
Sent By jwitmer Date 2013-03-25 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2013-03-25 Time 13:20 Sent To  
Notes
2013-03-25 13:21:36THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
  
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT UNTIL
 THESE ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF
 BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2013-03-25 Cont ID  
Sent By jwitmer Date 2013-03-25 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2013-03-25 Time 13:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status   Date   Cont ID  
Sent By AAponte Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-08-08 11:14:178/8/14 ZONING SENT TO AA. SG
2014-06-16 12:12:576/16/14 ZONING SENT TO AA. SG
2014-04-22 08:38:204/22/14 ZONING RECEIVED, SENT TO AA. SG

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-06 Cont ID  
Sent By aaponte Date 2013-05-06 Time 16:17 Rev Time 0.00
Received By aaponte Date 2013-05-03 Time 15:20 Sent To  
Notes
2013-05-06 16:28:07PROVISO:
 1. PARKING STRIPING DETAIL SHALL BE CORRECTED TO
 INDICATE THE LINES IN COLOR WHITE ACCORDING TO CITY
 STANDARDS.
 2. PLEASE INCLUDE THE SIEWALK AND THE STREET LEVEL ON
 ALL BUILDING SECTIONS AND FACADES ( TO THE CURB LINE),
 AND SHOW PLANTING AREAS WHERE PROVIDED (A-601,
 602,603,604 AND ELEVATIONS)
 3. DETAILS SHALL BE PROVIDED FOR THE RESOLUTION OF THE
 ENTRANCE STAIRS ENCROACHING INTO THE ROW AND THE
 PROPOSED PLANTING AREA (DETAILS FOR CONCRETE CURB AS
 PLANTER EDGE). PLANTING SPECS HAVE BEEN PROVIDED
 ALREADY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822 1439

Review Stop Z ZONING
Rev No 2 Status F Date 2013-04-24 Cont ID  
Sent By aaponte Date 2013-04-24 Time 14:45 Rev Time 0.00
Received By aaponte Date 2013-04-24 Time 14:45 Sent To  
Notes
2013-04-24 14:48:401. NOTE NO. 5 ON LP-1 TALKS ABOUT NORTH AND EAST
 PARCELS. PLEASE CORRECT AS THIS IS ONLY ONE PROPERTY.
 2. PLEASE LOOK AT NOTE NO. 4 ON PREVIOUS REVIEW.
 ALTERNATIVE SPECIE HAS BEEN REMOVED ON REVISED
 DRAWINGS, AND IT SHALL BE INCORPORATED AS REQUIRED ON
 PREVIOUS REVIEW.
 3. NOTE 1,6,8 AND 9 FROM PREVIOUS REVIEW HAVE NOT BEEN
 ADDRESSED.
 4. PERENNIAL PEANUT IS NOT ACCEPTABLE FOR THE PLANTING
 AREA ALONG EVERNIA STREET. AN ENHANCED PLANT MATERIAL
 SHALL BE PROPOSED FOR THAT AREA DUE TO ITS
 CONFIGURATION AS A PLANTER.
 5. PLEASE PROVIDE DETAIL OF THE CONFIGURATION OF THE
 SIDEWALK AND ITS GRADING IN RELATION WITH THE BUILDING
 ENTRANCE. DETAILS ARE ALSO NECESSARY FOR THE PROPOSED
 PLANTING AREA (CURB DETAIL, PLACEMENT AND TRANSITION TO
 SIDEWALK CURB).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-05 Cont ID  
Sent By aaponte Date 2013-04-05 Time 16:30 Rev Time 0.00
Received By aaponte Date 2013-04-04 Time 08:16 Sent To  
Notes
2013-04-05 16:32:431. MECHANICAL EQUIPMENT LOCATED ON THE ALLEY SHALL BE
 ENCLOSED AND SCREENED WITH AN OPAQUE FENCE OR WALLL AND
 HEDGES.
 2. STRIPIND DETAIL FOR PARKING SPACES DO NOT MEET CITY
 STANDARDS. LINE SHALL BE WHITE. CORRECT DIMENSIONS.
 3. PARAPET WALL SHALL BE AS HIGH AS THE MECHANICAL
 EQUIPMENT ON THE ROOF TOP AND FULLY ENCLOSE THE AC
 UNITS.
 4. THE NOTE ON THE STREET TREES SHALL READ LIVE OAKS"
 CATHEDRAL". ALTERNATIVE TREE IF OVERHEAD UTILITIES CAN
 NOT BE PLACED UNDERGROUND SILVER BUTTON WOOD.
 5. ROOT BARRIERS SHALL BE INSTALLED FOR ALL THE STREET
 TREES. STRUCTURAL SOIL UNDER THE SIDEWALK IS ALSO
 RECOMMENDED 10 FEET AROUND EACH TREE.
 6. PLEASE INCLUDE ALL THE PROJECT DATA IN THE STIE PLAN
 SHEET AS APPROVED IN THE SITE PLAN APPROVAL SET.
 INCLUDE NEW COUNTS FOR PARKING SPACES PROVIDED VS
 REQUIRED.
 7. NEW PLANTERS ON THE SIDEWALK DO NOT REFLECT THE CURB
 DETAIL AS DISCUSSED IN SEPARATE MEETINGS.
 8. PLEASE CHECK THE LOCATION OF ALL THE PROPERTY LINES
 AND THE SETBACK LINES ON ALL THE ELEVATIONS. WEST
 ELEVATION SEEMS TO HAVE THE WRONG SETBACK LINE.
 9. PLEASE INCLUDE THE SIDEWALK AND STREET LEVEL ON THE
 BUILDING SECTIONS. SHOW PLANTING AREAS ALONG THE
 SIDEWALK. (A-601, A-602, A-603,A-604).
 10. PLEASE INCLUDE INFORMATION REGARDING THE SIDEWLAK
 ELEVATION AND THE PROPOSED PLANTING BED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  
2013-02-21 14:16:402/21/13