Plan Review Details - Permit 13010420
Plan Review Stops For Permit 13010420
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2013-04-08 Cont ID  
Sent By jwitmer Date 2013-04-08 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2013-04-08 Time 16:18 Sent To  
Notes
2013-04-08 16:19:19SUBMITTAL: RELEASE OF ARCHITECT
 CHANGE OF ARCHITECT
 SPECIAL INSPECTOR AGREEMENT WITH REQUIRED SIGNATURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-19 Cont ID  
Sent By jwitmer Date 2013-03-19 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2013-03-15 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-17 Cont ID  
Sent By jwitmer Date 2013-01-17 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2013-01-17 Time 11:54 Sent To  
Notes
2013-01-17 15:29:16BUILDING PLAN REVIEW
 PERMIT:13010420
 ADD: 550 S ROSEMARY, SUITE # 160
 CONT: KCA CONSTRUCTION
 TEL: (561)361-1491
 E-MAIL: [email protected]
  
 ARCHITET: ARTURO G. GRIEGO # AR 94011
  
 ENGINEER: J. SAUVE PE FL #57585
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 THE STRUCTURAL SHEETS INDICATE WORK TO BE COMPLETED
 UNDERTHE SCOPE OF THIS PERMIT WHICH WILL REQUIRE A
 THRESHOLD INSPECTOR.
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE
 REQUIRED PLAN REVIEWS, WHEN ALL DOCUMENTS HAVE BEEN
 SUBMITTED THE CHIEF BUILDING INSPECTOR KEN CONRAD WILL
 PASS THIS REVIEW STOP.PLEASE CALL THE CITY OF WEST PALM
 BEACH'S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONCRETE RESTORATION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2) LS1 NOR THE DOOR SCHEDULE FOUND ON A1.0 PROVIDE THE
 TYPE OF HARDWARE REQUIRED ON THE EGRESS DOORS, PLEASE
 REVIEW 2010 FBC-B 1008.1.10 FOR PANIC HARDWARE.
  
 3) THIS REVIEW WILL BE UNDER THE 2010 EXST BLDG CODE
 CHAPTER 9 CHANGE OF OCCUPANCY SINCE THERE ARE TENANT
 SPACES GOING FROM MERCANTILE TO A2, ASSEMBLY AND NEED
 TO MEET THE REQUIREMENTS OF 2010 EXST. BLDG CODE
 901.3.1 PARTIAL CHANGE OF OCCUPANCY. WHERE A PORTION OF
 AN EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION SECTION 912 SHALL APPLY.
  
 4) SHEET S1.1 INDICATES THE USE OF NON COMPRESSIBLE
 FOAM FILLER FOR USE IN THE STAGES, PLEASE PROVIDE
 MANUFACTURERS SPECIFICATION MEETING THE REQUIREMENTS OF
 2010 FBC-B TABLE 1607.1(4).
  
 5) 2010 EXISTING BUILDING CODE 912.8 ACCESSIBILITY,
 EXISTING BUILDINGS THAT UNDER GO A CHANGE OF OCCUPANCY
 SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 ACCESSIBILITY ACCESSIBILITY CODE.226.1 GENERAL. WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. IN ADDITION, WHERE WORK SURFACES ARE PROVIDED
 FOR USE BY OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT
 SHALL COMPLY WITH 902.
 ACCESSIBILITY CODE 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 6) THE STAGES DO NOT PROVIDE VERTICAL ACCESSIBILITY
 ACCESSIBILITY CODE, 201.1.1.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) 01/18/2013 PLEASE SEE SHEET A4.1 AND THE 2010 FL
 ACCESSIBILTY CODE REQUIREMENT FOR AMBULATORY STALLS IN
 BOTH THE MENS AND WOMENS RESTROOMS SECTION 213.3.1. &
 604.8.2 FOR AMBULATORY STALLS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2013-05-31 Cont ID  
Sent By dharvey Date 2013-05-31 Time 12:02 Rev Time 0.00
Received By dharvey Date 2013-05-31 Time 12:02 Sent To  
Notes
2013-05-31 12:04:015-31-13
 THIS STOP PUT IN BY ERROR. SEE REVISION #13050817
 VB

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-12 Cont ID  
Sent By rlecky Date 2013-03-12 Time 11:57 Rev Time 0.00
Received By rlecky Date 2013-03-12 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-12 Cont ID  
Sent By rlecky Date 2013-02-12 Time 12:40 Rev Time 0.00
Received By rlecky Date 2013-02-12 Time 11:04 Sent To  
Notes
2013-02-12 12:41:2113010420
 550 S. ROSEMARY AVE #160
 TEQUILA COWBOY AND WANNABE?S
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED
 TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE PANEL
 BOARDS. NEC 314.28
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE MAIN DISCONNECTING MEANS. NEC 110.22,
 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING
 SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS.
 INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR WALL OR CEILING MOUNTED
 TRANSFORMERS. NEC 110.26, 240.24
  
 VERIFY SERVICE CAPACITY FROM THE MAIN SERVICE FOR THIS
 OCCUPANCY BY CALCULATION. INCLUDE EXISTING AND
 POTENTIAL FUTURE OCCUPANCY LOADS WHICH WILL BE SUPPLIED
 FROM THE EXISTING SERVICE. NEC 215.2
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-03-25 Cont ID  
Sent By wjolin Date 2013-03-25 Time 11:23 Rev Time 0.00
Received By wjolin Date 2013-03-25 Time 10:44 Sent To  
Notes
2013-03-25 11:23:03550 SOUTH ROSEMARY AVENUE - SUITE #160
 PERMIT #13010420
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED
 SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND
 EXISTING PENETRATIONS SHALL BE A APPROPRIATELY
 PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT
 CORRIDOR INDICATING "EXIT CORRIDOR - NO STORAGE OR
 COMBUSTIBLES."
  
 REPEAT COMMENT - SHEET A1.0: ALL EXIT AND EXIT ACCESS
 DOORS TO BE EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE
 INCLUDING EXISTING DOORS LOCATED IN THE REAR EXIT
 ACCESS CORRIDOR ALONG COLUMN LINE "E." DOOR #111 TO BE
 PROVIDED WITH PANIC HARDWARE AS WELL.
  
 NEW COMMENT - SHEET A1.0: MAIN ENTRY #100 AND MAIN
 ENTRY #119 DOORS TO BE EQUIPPED WITH PANIC HARDWARE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-01-22 Cont ID  
Sent By wjolin Date 2013-01-22 Time 09:34 Rev Time 0.00
Received By wjolin Date 2013-01-22 Time 09:32 Sent To  
Notes
2013-01-22 09:34:15550 SOUTH ROSEMARY AVENUE ? SUITE #160
 PERMIT #13010420
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED
 SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND
 EXISTING PENETRATIONS SHALL BE A APPROPRIATELY
 PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT
 CORRIDOR INDICATING ?EXIT CORRIDOR ? NO STORAGE OR
 COMBUSTIBLES.?
  
 SHEET LS1.0: PROVIDE HANDRAILS ON BOTH SIDES OF STAIRS
 AT KJ BOOTH #104 AND MB CONTROL #112. HANDRAILS SHALL
 BE LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES.
  
 SHEET A1.0: ALL EXIT AND EXIT ACCESS DOORS TO BE
 EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE INCLUDING
 EXISTING DOORS LOCATED IN THE REAR EXIT ACCESS CORRIDOR
 ALONG COLUMN LINE ?E.? DOOR #111 TO BE PROVIDED WITH
 PANIC HARDWARE AS WELL.
  
 SHEET FA-1: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. PROVIDE FIRE ALARM MICROPHONE NEAR
 ANUNCIATOR PANEL. PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. MUSIC SHALL SHUT
 DOWN UPON ACTIVATION OF FIRE ALARM SYSTEM TO ALLOW FIRE
 ALARM MESSAGE TO BE INTELLIGIBLE.
  
 SHEET FA-1: NO FIRE ALARM NOTIFICATION APPLIANCES
 LOCATED IN KITCHEN PREP AREA OR OUTDOOR DINING AREA
 #118.
  
 SHEET FA-1: APPEAR TO HAVE INSUFFICIENT NUMBER OF
 NOTIFICATION APPLIANCES NEAR MECHANICAL BULL AREA
 #113/BAR #2.
  
 SHEET FS-1: CONSTRUCTION DOCUMENTS ESTABLISH BEN ELLIS
 AS ENGINEER OF RECORD; THEREFORE, FIRE SPRINKLER SHOP
 DRAWINGS AND HYDRAULIC CALCULATIONS SHALL NOT BE SIGNED
 AND SEALED BY THE CONTRACTOR PER FLORIDA STATUTE 633.
  
 SHEET FS-2: PROVIDE SPRINKLER PROTECTION IN WALK-IN
 BEER COOLER #110.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-01-18 Cont ID  
Sent By lwagner Date 2013-01-18 Time 15:24 Rev Time 0.00
Received By lwagner Date 2013-01-18 Time 15:24 Sent To  
Notes
2013-01-18 15:24:44GAS PERMIT IS REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-08 Cont ID  
Sent By jwitmer Date 2013-04-08 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2013-04-03 Time 18:14 Sent To  
Notes
2013-04-03 18:14:29SUBMITTAL ROUTED TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-29 Cont ID  
Sent By jwitmer Date 2013-03-29 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2013-03-08 Time 15:44 Sent To  
Notes
2013-03-08 17:42:07* * * EXPEDITED * * *
  
 C28
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-12 Cont ID  
Sent By rlecky Date 2013-02-12 Time 12:41 Rev Time 0.00
Received By rlecky Date 2013-01-16 Time 16:18 Sent To  
Notes
2013-01-16 16:20:28EXPEDITED
 C--6

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-03-15 Cont ID  
Sent By jwitmer Date 2013-03-15 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2013-03-15 Time 13:51 Sent To  
Notes
2013-03-15 13:52:05IMPACT FEES STAMPED NONE DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-17 Cont ID  
Sent By jwitmer Date 2013-01-17 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2013-01-17 Time 15:48 Sent To  
Notes
2013-01-17 15:48:07BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-03-27 Cont ID  
Sent By hmoser Date 2013-03-27 Time 15:56 Rev Time 0.00
Received By hmoser Date 2013-03-27 Time 14:35 Sent To  
Notes
2013-03-27 15:56:38PASS PROVISO
 1) SUBMIT ENERGY CALCULATIONS TO THE CITY
 BEFOR FIRST INSPECTION.
 2) HOODS AND COOLERS REQUIRE SEPARATE
 APPLICATION, PLANS AND PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-22 Cont ID  
Sent By tgordon Date 2013-01-22 Time 10:41 Rev Time 0.00
Received By tgordon Date 2013-01-22 Time 10:41 Sent To  
Notes
2013-01-22 11:31:55*** CORRECTIONS NEEDED FOR MECHANICAL REVIEW. ***
  
 1) SUBMIT COOLING LOAD CALCULATIONS, PER 2010
 FBC/ENERGY 503.2.1.
  
 2) SHOW ON MECHANICAL PLANS THE DUCT SMOKE DETECTORS AS
 SHOWN ON PLAN FA-1. SEE 2010 FBC/M 606.1.
  
 3) PLEASE STATE IF THE WATER HEATER IN THE DRY STORAGE
 ROOM #129 IS ELECTRIC OR GAS. IF GAS SHOW COMPLIANCE
 WITH 2010 FBC/G 304.1 COMBUSTION AIR.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-18 Cont ID  
Sent By lwagner Date 2013-01-18 Time 15:17 Rev Time 0.00
Received By lwagner Date 2013-01-17 Time 14:22 Sent To  
Notes
2013-01-18 15:23:40SEE BUILDING REVIEW COMMENTS FOR AMBULITORY STALLS

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2013-03-29 Cont ID  
Sent By jwitmer Date 2013-03-29 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2013-03-19 Time 15:29 Sent To  
Notes
2013-03-19 15:30:073/29/2013
 BUILDING PROVISO:
 THRESHOLD AGREEMENT IS MISSING SIGNATURES OF THE OWNER,
 CONTRACTOR & ENGINEER OF RECORD. THE B.O. ROBERT BROWN
 WILL GIVE THE CONTRACTOR ONE WEEK TO GAIN THE REQUIRED
 SIGNATURES OR REVOKE THE PERMIT.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2013-01-17 Cont ID  
Sent By jwitmer Date 2013-01-17 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2013-01-17 Time 09:42 Sent To  
Notes
2013-02-28 09:44:29BUILDING PLAN REVIEW
 PERMIT:13010420
 ADD: 550 S ROSEMARY, SUITE # 160
 CONT: KCA CONSTRUCTION
 TEL: (561)361-1491
 E-MAIL: [email protected]
  
 ARCHITET: ARTURO G. GRIEGO # AR 94011
  
 ENGINEER: J. SAUVE PE FL #57585
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 THE STRUCTURAL SHEETS INDICATE WORK TO BE COMPLETED
 UNDERTHE SCOPE OF THIS PERMIT WHICH WILL REQUIRE A
 THRESHOLD INSPECTOR.
 FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING
 AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE
 REQUIRED PLAN REVIEWS, WHEN ALL DOCUMENTS HAVE BEEN
 SUBMITTED THE CHIEF BUILDING INSPECTOR KEN CONRAD WILL
 PASS THIS REVIEW STOP.PLEASE CALL THE CITY OF WEST PALM
 BEACH'S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONCRETE RESTORATION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-03-21 Cont ID  
Sent By eschneid Date 2013-03-21 Time 15:31 Rev Time 0.50
Received By eschneid Date 2013-03-21 Time 15:31 Sent To  
Notes
2013-03-21 15:36:01PASSED
  
 1) INTERIOR WORK ONLY APPROVED.
  
 2) SEPARATE PERMITS REQUIRED FOR:
  
 A. EXTERIOR FACADE, TO INCLUDE WALL TREATMENTS.
 B. SIGNS
 C. AWNINGS
  
 3) PLEASE NOTE - THE PROPOSED MATERIALS (WOOD SIDING
 AND FLAGSTONE) ARE NOT MATERIALS USED IN THE
 MEDITERRANEAN VOCABULARY AND ARE THUS NOT PERMITTED BY
 THE CITYPLACE MASTER DESIGN GUIDELINES. CITYPLACE
 APPROVAL DOES NOT GUARANTEE COMPLIANCE WITH THE
 CITYPLACE MASTER DESIGN GUIDELINES.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-25 Cont ID  
Sent By eschneid Date 2013-01-25 Time 15:27 Rev Time 0.00
Received By eschneid Date 2013-01-25 Time 15:27 Sent To  
Notes
2013-01-25 15:33:39FAILED
  
 1) SHEET A1.0 STATES THAT THE EXTERIOR STOREFRONT IS
 UNDER A SEPARATE PERMIT, YET SHEETS 3.0 AND 3.1 ARE
 INCLUDED IN THE PERMIT SUBMITTAL AND DO NOT INDICATE
 THAT THE EXTERIOR STOREFRONT IS NOT PART OF THIS
 PERMIT.
  
 2) THE PROPOSED MATERIALS (WOOD SIDING AND FLAGSTONE)
 ARE NOT MATERIALS USED IN THE MEDITERRANEAN VOCABULARY
 AND ARE THUS NOT PERMITTED BY THE CITYPLACE MASTER
 DESIGN GUIDELINES.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-01-17 10:48:001/17/13