Plan Review Details - Permit 13010418
Plan Review Stops For Permit 13010418
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-02-07 Cont ID  
Sent By shill Date 2013-02-07 Time 08:43 Rev Time 0.00
Received By shill Date 2013-02-07 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-31 Cont ID  
Sent By shill Date 2013-01-31 Time 08:21 Rev Time 0.00
Received By shill Date 2013-01-31 Time 08:20 Sent To  
Notes
2013-01-31 08:25:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1-4. OK
  
 5. SEE FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1.
 COMPONENTS BEING CHANGED ARE TO MEET THE REQUIREMENTS
 OF FBC 2010 ENERGY CONSERVATION CHAPTER 4 WHEN THE
 ESTIMATED COST EXCEEDS 30 PERCENT OF THE ASSESSED VALUE
 OF THE STRUCTURE.
  
 2ND REVIEW, NOT ADDRESSED. THIS IS PROVIDED FROM THE
 MANUFACTURER.
  
 NEW COMMENTS:
  
 HORIZONTAL ROLLER METHOD OF INSTALLATION PROPOSED
 (-60PSF) DOES NOT COMPLY WITH DESIGN PRESSURES
 SPECIFIED BY ENGINEER (-60.9). EITHER REVISE THE DESIGN
 PRESSURES OR THE PRODUCT APPROVAL WILL BE REDLINED FOR
 YOU TO INDICATE A METHOD OF INSTALLATION WHICH MEETS
 -63PSF.
  
 PLEASE SEND PRIVATE PROVIDER'S RESUME TO KEN CONRAD AT
 [email protected].
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-22 Cont ID  
Sent By shill Date 2013-01-22 Time 09:14 Rev Time 0.00
Received By shill Date 2013-01-22 Time 07:06 Sent To  
Notes
2013-01-22 09:39:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS.
 THERE IS A NOTE ON SHEET A1 THAT EMERGENCY ESCAPE AND
 RESCUE OPENINGS (FOR SLEEPING ROOMS) TO COMPLY WITH FBC
 1029 (SEE ALSO FBC R310).
  
 2. REVISE FLOOR PLAN TO INCLUDE HORIZONTAL ROLLER
 CONFIGURATIONS AND SINGLE HUNG CONFIGURATIONS OR REVISE
 WINDOW SCHEDULE TO INCLUDE THIS INFORMATIN (**SLEEPING
 ROOMS ONLY**). FOR INSTANCE, SEE OPENING O. THE WINDOW
 WIDTH EXCEEDS MAX FOR AN XO WINDOW, SEE SHEET 4, BUT
 NOT CLEAR WHETHER AN XOX (DETAIL B OR C) WILL MEET
 MINIMUM EGRESS WIDTH. SEE ALSO SHEET 4 OF SINGLE HUNG
 PRODUCT APPROVAL.
  
 3. A2, WINDOW BUCK DETAIL, SPECIFICATION PROPOSES A 1X3
 BEVELED BUCK. THIS CONFLICTS WITH THE GRAPHIC AND FBC R
 612.10.2.1 WHICH REQUIRES FULL SUPPORT OF THE WINDOW
 UNLESS OTHERWISE TESTED.
  
 4. DELEGATED ENGINEERING TO BE REVIEWED BY ENGINEER OF
 RECORD, FS471, FAC61G15 (WINDOW DESIGN PRESSURE
 ENGINEERING AND FLOOR PLAN).
  
 5. SEE FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1.
 COMPONENTS BEING CHANGED ARE TO MEET THE REQUIREMENTS
 OF FBC 2010 ENERGY CONSERVATION CHAPTER 4 WHEN THE
 ESTIMATED COST EXCEEDS 30 PERCENT OF THE ASSESSED VALUE
 OF THE STRUCTURE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-30 Cont ID  
Sent By rlecky Date 2013-01-30 Time 13:04 Rev Time 0.00
Received By rlecky Date 2013-01-30 Time 12:54 Sent To B
Notes
2013-01-30 13:04:19THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-24 Cont ID  
Sent By rlecky Date 2013-01-24 Time 12:18 Rev Time 0.00
Received By rlecky Date 2013-01-24 Time 12:11 Sent To  
Notes
2013-01-24 12:19:2113010418
 227 ELWA PLACE
 SF REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-04 Cont ID  
Sent By mdekle Date 2013-02-04 Time   Rev Time 0.00
Received By mdekle Date 2013-02-01 Time 11:57 Sent To  
Notes
2013-02-01 11:58:15SENT TO MURRIAH. DID NOT ADDRESS BUILDING ISSUES. PLANS
 STILL IN LARGE DENIED BIN UNDER 'T'.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-31 Cont ID  
Sent By shill Date 2013-01-31 Time 08:25 Rev Time 0.00
Received By shill Date 2013-01-29 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-29 Cont ID  
Sent By rmcdouga Date 2013-01-29 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2013-01-16 Time 16:42 Sent To  
Notes
2013-01-16 16:43:29EXPEDITED
 R--12

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-29 Cont ID  
Sent By rmcdouga Date 2013-01-29 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2013-01-29 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2013-02-07 Cont ID  
Sent By mdekle Date 2013-02-07 Time   Rev Time 0.00
Received By mdekle Date 2013-02-07 Time 13:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2013-02-04 Cont ID  
Sent By mdekle Date 2013-02-04 Time   Rev Time 0.00
Received By mdekle Date 2013-02-04 Time   Sent To  
Notes
2013-02-04 15:36:03REVIEW STATUS: FAILED
  
 THE RESUBMITTAL DID NOT HAVE ANY DETAILS ATTACHED.
 PLEASE PROVIDE FURTHER ELABORATION REGARDING THE
 SUBMITTAL WHICH ONLY INCLUDED TWO SURVEYS WITH HAND
 DRAWN CIRCLES??
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 ZONING PLAN REVIEW
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-01-24 Cont ID  
Sent By mdekle Date 2013-01-24 Time   Rev Time 0.00
Received By mdekle Date 2013-01-24 Time   Sent To  
Notes
2013-01-24 13:40:07PLANNING: **** PASSED W/PROVISO ****
  
 1.PRIOR TO THE FIRST INSPECTION, THE APPLICANT MUST
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-18 Cont ID  
Sent By mdekle Date 2013-01-18 Time   Rev Time  
Received By mdekle Date 2013-01-18 Time   Sent To  
Notes
2013-01-18 10:35:41PLANNING: **** FAILED ****
  
 RESPOND TO COMMENTS IN WRITING.
  
 1. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE
 VALUE OF THE PROPOSED WORK ($76,000.00) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($123,336.00) (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  
2013-01-17 10:51:011/17/13