Plan Review Details - Permit 13010221
Plan Review Stops For Permit 13010221
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By jwitmer Date 2013-01-10 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2013-01-09 Time 15:30 Sent To  
Notes
2013-01-10 09:11:14BUILDING PLAN REVIEW
 PERMIT: 13010221
 ADD: EMBARCADERO DR
 CONT: TBD
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 JAN. 09/2013
 ACTION: DENIED
  
 NOTE: 2010 EXST BLDG CODE . 901.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 1) 2010 EXST BLDG CODE 912.1.1 COMPLIANCE WITH CHAPTER
 8.
 THE REQUIREMENTS OF CHAPTER 8 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 912.1.1.1 AND 912.1.1.2.
  
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION AND THAT PORTION IS NOT
 SEPARATED FROM THE REMAINDER OF THE BUILDING WITH A
 FIRE-RATED WALL/CEILING HAVING A FIRE-RESISTANCE RATING
 AS REQUIRED IN THE FLORIDA BUILDING CODE, BUILDING FOR
 THE SEPARATE OCCUPANCY, THE ENTIRE BUILDING SHALL
 COMPLY WITH ALL OF THE REQUIREMENTS OF CHAPTER 8
 APPLIED THROUGHOUT THE BUILDING FOR THE MOST
 RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING
 AND WITH THE REQUIREMENTS OF THIS CHAPTER.
 MOST RESTRICTIVE OCCUPANCY BETWEEN THE BUSINESS &
 EDUCATIONAL OCCUPANCIES IS EDUCATIONAL.
  
 801.2 COMPLIANCE.
 IN ADDITION TO THE PROVISIONS OF THIS CHAPTER, WORK
 SHALL COMPLY WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6
 AND 7. THE REQUIREMENTS OF SECTIONS 703, 704, AND 705
 SHALL APPLY WITHIN ALL WORK AREAS WHETHER OR NOT THEY
 INCLUDE EXITS AND CORRIDORS SHARED BY MORE THAN ONE
 TENANT AND REGARDLESS OF THE OCCUPANT LOAD.
  
 1A) 2010 EXST BLDG CODE 803.2.1 SEPARATION REQUIRED.
 WALLS SEPARATING THE UNITS (TENANT SEPERATION WALLS)
 THAT ARE NOT CONTINUOUS FROM THE FOUNDATION TO THE
 UNDERSIDE OF THE ROOF SHEATHING SHALL BE CONSTRUCTED TO
 PROVIDE A CONTINUOUS FIRE SEPARATION USING CONSTRUCTION
 MATERIALS CONSISTENT WITH THE EXISTING WALL OR
 COMPLYING WITH THE REQUIREMENTS FOR NEW STRUCTURES. ALL
 WORK SHALL BE PERFORMED ON THE SIDE OF THE WALL THAT IS
 PART OF THE WORK AREA.
  
 EXCEPTION: WHERE ALTERATIONS OR REPAIRS DO NOT RESULT
 IN THE REMOVAL OF WALL OR CEILING FINISHES EXPOSING THE
 STRUCTURE, WALLS ARE NOT REQUIRED TO BE CONTINUOUS
 THROUGH CONCEALED FLOOR SPACES.
  
 PLEASE NOTE: THE PROPOSED SPACE IS APPROXIMATELY 8,000-
 9,000 SQ FT IN AREA, IF THE SCHOOL EXPANDS SEE EXST
 BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 1B) EXST BLDG CODE 703.4 INTERIOR FINISH. THE INTERIOR
 FINISH OF WALLS AND CEILINGS IN EXITS AND CORRIDORS IN
 ANY WORK AREA SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTION: EXISTING INTERIOR FINISH MATERIALS THAT DO
 NOT COMPLY WITH THE INTERIOR FINISH REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. SHALL BE PERMITTED TO
 BE TREATED WITH AN APPROVED FIRE-RETARDANT COATING IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS TO
 ACHIEVE THE REQUIRED RATING.
  
 1C) EXST BLDG CODE 704 FIRE PROTECTION. 704.1.1
 CORRIDOR RATINGS. WHERE AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IS INSTALLED THROUGHOUT THE STORY, THE REQUIRED
 FIRE-RESISTANCE RATING FOR ANY CORRIDOR LOCATED ON THE
 STORY SHALL BE PERMITTED TO BE REDUCED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, BUILDING. IN ORDER TO
 BE CONSIDERED FOR A CORRIDOR RATING REDUCTION, SUCH
 SYSTEM SHALL PROVIDE COVERAGE FOR THE STAIRWELL
 LANDINGS SERVING THE FLOOR AND THE INTERMEDIATE
 LANDINGS IMMEDIATELY BELOW. CURRENTLY NOT SPRINKLERED,
 FBC TABLE 1018.1 E OCCUPANCY > 30 OCCUPANTS REQUIRES A
 ONE HOUR RATED FIRE CORRIDOR.
  
 SEE OTHER REQUIREMENTS LISTED IN 704.
  
 2) ESXT BLDG CODE 912.1.2 FIRE PROTECTION AND INTERIOR
 FINISH. THE PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR
 FIRE PROTECTION AND INTERIOR FINISH, RESPECTIVELY,
 SHALL APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION.
  
 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B 903.2.3 EDUCATIONAL WHEN THE FLOOR AREA >
 12,000 SQ FT.
  
 3) EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 2010 FBC-B 907.2.3 EDUCATIONAL OCCUPANT LOAD IS > THAN
 30 OCCUPANTS.
  
 4) EXST BLDG CODE 912.3 INTERIOR FINISH. IN AREAS OF
 THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 SEE REQUIRED FINISHES IN EXIT ACCESS CORRIDORS, EXITS
 AND ROOMS, 2010 FBC-B TABLE 803.9.
  
 5A) EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR CHANGE
 TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 EXCEPTIONS:
  
 1-3 DO NOT APPLY- STAIRWAYS.
  
 4. WHERE AN EXISTING CORRIDOR IS REQUIRED TO BE FIRE
 RATED, EQUIVALENCY CAN BE ACHIEVED BY EITHER
 SPRINKLERING THE BUILDING OR USING EQUIVALENCY AS PER
 NFPA 914 OR CHAPTER 7 OF THE FLORIDA BUILDING CODE,
 BUILDING FOR FIRE RESISTANCE. ALSO, SEE SECTION 1001.2
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 5. EXISTING CORRIDOR DOORWAYS, TRANSOMS AND OTHER
 CORRIDOR OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN
 SECTIONS 705.5.1, 705.5.2 AND 705.5.3.
  
 6. EXISTING DEAD-END CORRIDORS SHALL COMPLY WITH THE
 REQUIREMENTS IN SECTION 705.6.
  
 7. WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 REQUIRED, AN EXISTING OPERABLE WINDOW WITH CLEAR
 OPENING AREA NO LESS THAN 4 SQUARE FEET (0.38 M2) AND
 WITH MINIMUM OPENING HEIGHT AND WIDTH OF 22 INCHES (559
 MM) AND 20 INCHES (508 MM), RESPECTIVELY, WITH MAXIMUM
 SILL HEIGHT AT 44 INCHES (1118 MM) ABOVE THE FLOOR OR
 APPROVED PERMANENT ELEVATED AREA, SHALL BE ACCEPTED AS
 AN EMERGENCY ESCAPE AND RESCUE OPENING.
  
 2010 FBC-B 1029.4.1 EVERY ROOM OR SPACE GREATER THAN
 250 SQUARE FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES
 USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR
 NORMALLY SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR
 SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN
 BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS
 THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING:
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
 EXCEPTIONS:
 1. BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903.3.1.1.
 2. WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO THE OUTSIDE OF THE BUILDING.
  
 5B) 5A) EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2010 FBC-B 1018.2 CORRIDOR WIDTH:
 1018.2 44INCHES
 1018.2 (2) 36 INCHES < 50 OCCUPANTS
 1018.2(4) 72 INCHES > 99 OCCUPANTS (EDUCATIONAL)
  
 6) 912.4.3 EGRESS CAPACITY. EGRESS CAPACITY SHALL MEET
 OR EXCEED THE OCCUPANT LOAD AS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY.
  
 7) EXST BLDG CODE 912.8 ACCESSIBILITY. EXISTING
 BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH THE PROVISIONS OF THE
 FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 2010 FL ACCESSIBILITY CODE 202.4 ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1.
 ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL
 OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE
 ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO
 AN AREA CONTAINING A PRIMARY FUNCTION.
 EXCEPTIONS:
 1. RESIDENTIAL DWELLING UNITS SHALL NOT BE REQUIRED TO
 COMPLY WITH 202.4.
 2. IF A PRIVATE ENTITY HAS CONSTRUCTED OR ALTERED
 REQUIRED ELEMENTS OF A PATH OF TRAVEL AT A PLACE OF
 PUBLIC ACCOMMODATION OR COMMERCIAL FACILITY IN
 ACCORDANCE WITH THE SPECIFICATIONS IN THE 1994 OR 1997
 FLORIDA ACCESSIBILITY CODE, THE PRIVATE ENTITY IS NOT
 REQUIRED TO RETROFIT SUCH ELEMENTS TO REFLECT
 INCREMENTAL CHANGES IN THE PROPOSED STANDARDS SOLELY
 BECAUSE OF AN ALTERATION TO A PRIMARY FUNCTION AREA
 SERVED BY THAT PATH OF TRAVEL.
 3. THE PATH OF TRAVEL REQUIREMENTS SHALL NOT APPLY TO
 MEASURES TAKEN SOLELY TO COMPLY WITH BARRIER REMOVAL
 REQUIREMENTS.
 4. IF A PUBLIC ENTITY HAS CONSTRUCTED OR ALTERED
 REQUIRED ELEMENTS OF A PATH OF TRAVEL IN ACCORDANCE
 WITH THE SPECIFICATIONS IN EITHER THE 1994 OR 1997
 FLORIDA ACCESSIBILITY CODE OR THE UNIFORM FEDERAL
 ACCESSIBILITY STANDARDS, AS AN EQUIVALENT FACILITATION,
 BEFORE MARCH 15, 2012, THE PUBLIC ENTITY IS NOT
 REQUIRED TO RETROFIT SUCH ELEMENTS TO REFLECT
 INCREMENTAL CHANGES IN THIS CODE SOLELY BECAUSE OF AN
 ALTERATION TO A PRIMARY FUNCTION AREA SERVED BY THAT
 PATH OF TRAVEL.
 5. THE PATH OF TRAVEL REQUIREMENT SHALL NOT APPLY TO
 ALTERATIONS UNDERTAKEN SOLELY FOR PURPOSES OF MEETING
 THE PUBLIC ENTITY PROGRAM ACCESSIBILITY REQUIREMENTS OF
 ? 3.150, 28 CFR 35.
 6. IF A TENANT IS MAKING ALTERATIONS THAT WOULD TRIGGER
 THE REQUIREMENTS OF THIS SECTION, THOSE ALTERATIONS BY
 THE TENANT IN AREAS THAT ONLY THE TENANT OCCUPIES DO
 NOT TRIGGER A PATH OF TRAVEL OBLIGATION UPON THE
 LANDLORD WITH RESPECT TO AREAS OF THE FACILITY UNDER
 THE LANDLORD?S AUTHORITY, IF THOSE AREAS ARE NOT
 OTHERWISE BEING ALTERED.
  
  
 2010 FL ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 8) SCHOOLS, COLLEGES AND UNIVERSITIES
  
 443.1 SCOPE:
 FLORIDA?S PUBLIC AND PRIVATE SCHOOLS, COLLEGES, AND
 UNIVERSITIES SHALL COMPLY WITH ALL APPLICABLE
 REQUIREMENTS OF THE CODE AND THE FOLLOWING STANDARDS.
 THESE ARE MINIMUM STANDARDS; BOARDS OR OWNERS MAY
 IMPOSE MORE RESTRICTIVE REQUIREMENTS. ADDITIONAL
 REQUIREMENTS FOR PUBLIC EDUCATIONAL FACILITIES IN
 FLORIDA, INCLUDING PUBLIC SCHOOLS AND FLORIDA?S
 COLLEGES, ARE FOUND IN SECTION 423, STATE REQUIREMENTS
 FOR EDUCATIONAL FACILITIES.
  
 443.2 SITES
  
 443.2.1 DRAINAGE.
 SOIL, GRASS, AND PLANTING BEDS SHALL PROVIDE POSITIVE
 DRAINAGE AWAY FROM SIDEWALKS, BUT SHALL NOT FALL AWAY
 AT MORE THAN A 3-PERCENT GRADIENT SLOPE FOR A MINIMUM
 DISTANCE OF 5 FEET (1524 MM) FROM THE EDGE.
  
 443.2.2 PLAYGROUNDS AND EQUIPMENT.
 PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY
 SOUND, VERMINPROOF, AND SHALL NOT HAVE JAGGED OR SHARP
 PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO
 SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR
 DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD
 CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT,
 SLIDES, AND SWINGS.
  
 443.2.3 OUTDOOR WASTE CONTAINERS.
 A SMOOTH NONABSORBENT SURFACE SHALL BE PROVIDED FOR
 OUTDOOR WASTE CONTAINERS.
  
 443.3 BUILDING CONSTRUCTION
  
 443.3.1 RODENT PROOFING.
 BUILDINGS FOR GROUP E OCCUPANCIES SHALL BE RODENT
 PROOFED PER APPENDIX F, RODENTPROOFING.
  
 443.3.2 GLARE FROM NATURAL LIGHT.
 SOURCES OF NATURAL LIGHT IN INSTRUCTIONAL SPACES SHALL
 BE GLAZED WITH GLARE REDUCING MATERIALS OR SHALL BE
 SHIELDED TO PREVENT GLARE THAT CAN INTERFERE WITH
 SEEING TASK WITHIN THE INSTRUCTIONAL SPACE.
  
 443.3.3 AUTOMATED EXTERNAL DEFIBRILLATOR.
 AUTOMATED EXTERNAL DEFIBRILLATORS SHALL BE PROVIDED IN
 PUBLIC EDUCATIONAL FACILITIES THAT ARE A MEMBER OF THE
 FLORIDA HIGH SCHOOL ATHLETIC ASSOCIATION.
  
 443.3.4 DIAPER CHANGING STATIONS.
 A DIAPER CHANGING STATION SHALL BE LOCATED IN OR
 ADJACENT TO ANY CLASSROOM WHERE CHILDREN WEARING
 DIAPERS ARE IN ATTENDANCE. A HAND WASHING LAVATORY
 SHALL BE PROVIDED WITHIN THE CHANGING STATION AREA.
 ACCESS SHALL BE PROVIDED TO THE LAVATORY WITHOUT
 OPENING DOORS OR TOUCHING A HANDLE.
  
 443.3.5 PLUMBING
  
 443.3.5.1 STANDARDS.
 EDUCATIONAL AND ANCILLARY FACILITIES SHALL BE PROVIDED
 WITH TOILETS, HAND WASHING FACILITIES, AND DRINKING
 FOUNTAINS FOR ALL OCCUPANTS, IN RATIOS AND ACCESSIBLE
 AS REQUIRED BY THE FLORIDA BUILDING CODE, FLORIDA LAW,
 AND FEDERAL REQUIREMENTS.
  
 EXCEPTION: A SINGLE UNISEX TOILET ROOM IS ALLOWED WHERE
 PROVIDED IN CHILD CARE, PRE-KINDERGARTEN THROUGH GRADE
 3 AND ESE CLASSROOMS.
  
 443.3.5.2 TEACHER TOILETS.
 FACULTY AND STAFF TOILETS SHALL BE SEPARATE FROM
 STUDENT TOILETS.
  
 EXCEPTION: SEPARATION OF FACULTY/STAFF AND STUDENT
 TOILET FACILITIES IS NOT REQUIRED FOR COLLEGES AND
 UNIVERSITIES.
  
 443.3.5.3 TOILET ROOM ACCESS.
  
 443.3.5.3.1
 TOILET FACILITIES FOR PRE-K THROUGH GRADE 12 SHALL BE
 ACCESSIBLE UNDER CONTINUOUS ROOF COVER FROM ALL STUDENT
 OCCUPIED SPACES.
  
 EXCEPTION: RELOCATABLE CLASSROOMS INSTALLED FOR
 TEMPORARY USE.
  
 443.3.5.3.2 ACCESS TO GROUP TOILET ROOMS.
 ACCESS TO STUDENT GROUP TOILET ROOMS SHALL NOT BE
 THROUGH AN OCCUPIED SPACE, STORAGE SPACE, OR EQUIPMENT
 SPACE.
  
 443.3.5.4 SHIELDING DEVICE.
 THE ENTRY TO EACH GROUP TOILET ROOM SHALL BE PROVIDED
 WITH A DOOR, PARTITION, OR OTHER SHIELDING DEVICE TO
 BLOCK FROM VIEW THE OCCUPANTS IN THE TOILET ROOM. IF A
 DOOR IS PROVIDED, IT SHALL HAVE A CLOSER AND SHALL
 SWING OUT IN THE DIRECTION OF EGRESS.
  
 443.3.5.5 WALLS.
 WALLS IN TOILET ROOMS SHALL BE IMPERVIOUS TO A HEIGHT
 OF AT LEAST 4 FEET (1219 MM) ABOVE THE FLOOR. WALLS IN
 KITCHENS, SCULLERYS, CAN WASH AREAS, AND SHOWER ROOMS
 SHALL BE IMPERVIOUS TO A HEIGHT OF AT LEAST 6 FEET
 (1829 MM) ABOVE THE FLOOR. TOILET AND SHOWER PARTITIONS
 SHALL BE IMPERVIOUS.
  
 443.3.5.6 FLOOR DRAINS AND HOSE BIBBS.
 ALL GROUP TOILET ROOMS SHALL BE PROVIDED WITH AT LEAST
 ONE FLOOR DRAIN AND ONE EASILY ACCESSIBLE HOSE BIBB.
 THE FLOOR SHALL BE SLOPED DOWN TO THE DRAIN.
  
 443.3.5.7 HANDWASHING FACILITIES.
  
 443.3.5.7.1
 HANDWASHING FACILITIES SHALL BE LOCATED WITHIN OR
 ADJOINING EACH TOILET ROOM.
  
 443.3.5.7.2
 SOAP DISPENSERS FOR LIQUID, FOAM, OR POWDERED SOAP
 SHALL BE PROVIDED AT ALL HANDWASHING BASINS.
  
 443.3.5.7.3
 INDIVIDUAL TOWEL DISPENSERS OR HOT-AIR HAND DRYING
 DEVICES SHALL BE PROVIDED NEAR HANDWASHING BASINS.
  
 443.3.5.8 SHOWERS
  
 443.3.5.8.1
 SHOWER HEADS SHALL BE BASED ON THE PEAK LOAD TO BE
 ACCOMMODATED AT ONE TIME AND PROVIDED AT THE RATIO OF
 ONE SHOWER HEAD FOR EACH FIVE STUDENTS, LOCATED A
 MINIMUM OF 30 INCHES (762 MM) APART.
  
 443.3.5.8.2
 FLOORS SHALL BE DRAINED IN SUCH A MANNER THAT WASTE
 WATER FROM ANY SHOWER HEAD WILL NOT PASS OVER AREAS
 OCCUPIED BY OTHER BATHERS.
  
 443.3.5.8.3
 WATER SHALL BE HEATED AND THE TEMPERATURE AT THE SHOWER
 HEAD SHALL NOT EXCEED 110?F (43?C) NOR BE LESS THAN
 95?F (35?C).
  
 443.3.6 MECHANICAL
  
 443.3.6.1 NATURAL VENTILATION.
 NATURAL VENTILATION SHALL NOT BE PROVIDED IN TOILET
 ROOMS, SHOWER ROOMS, LOCKER ROOMS, AND STORAGE ROOMS
 FOR ATHLETIC EQUIPMENT OR SOILED CLOTHES.
  
 443.3.6.2 FANS AND BLOWERS.
 FANS AND BLOWERS SHALL BE SIZED AND DESIGNED TO PROVIDE
 THE REQUIRED AIR MOVEMENT WITHOUT EXCESSIVE OR
 DISTURBING NOISE THAT WOULD INTERFERE WITH THE
 EDUCATIONAL PROGRAM PROVIDED IN THE SPACE BEING
 VENTILATED.
  
 443.3.6.3 KILNS.
 KILN ROOMS AND AREAS SHALL BE PROVIDED WITH ADEQUATE
 EXHAUST TO DISPEL EMITTED HEAT TO THE EXTERIOR, AND
 THEY SHALL NOT BE CONNECTED TO ANY OTHER EXHAUST
 SYSTEM.
  
 443.3.6.4 CHEMISTRY LABORATORIES AND SCIENCE
 CLASSROOMS.
 HVAC SYSTEMS IN CHEMISTRY LABS AND SCIENCE CLASSROOMS
 SHALL BE DESIGNED AND INSTALLED TO ENSURE THAT
 CHEMICALS ORIGINATING FROM THE SPACE ARE NOT
 RECIRCULATED.
  
 EXCEPTION: A HIGH CAPACITY EMERGENCY EXHAUST SYSTEM
 PROVIDING TWENTY (20) AIR CHANGES PER HOUR MAY BE USED
 IN CHEMISTRY LABORATORIES AND SCIENCE CLASSROOMS WITH
 FUME HOODS. POSITIVE VENTILATION MAY BE PROVIDED VIA
 DOORS OR WINDOWS OPENING TO THE EXTERIOR. SIGNS
 PROVIDING OPERATIONAL INSTRUCTIONS SHALL BE PERMANENTLY
 INSTALLED AT THE EMERGENCY EXHAUST SYSTEM FAN SWITCH
 AND ADJACENT TO THE DOOR(S) OR WINDOW(S) TO BE OPENED.
  
 443.3.6.5 CHEMICAL STORAGE.
 ROOMS USED FOR THE STORAGE, HANDLING, AND DISPOSAL OF
 CHEMICALS USED IN SCHOOL, COLLEGE, AND UNIVERSITY
 LABORATORIES SHALL BE VENTED TO THE EXTERIOR. THE
 VENTILATION SYSTEM SHALL NOT BE CONNECTED TO THE
 AIR-CONDITIONING RETURN AIR SYSTEM, AND THE ROOMS SHALL
 BE KEPT AT MODERATE TEMPERATURES. CHEMICAL STORAGE
 CABINETS, WHEN VENTED TO THE EXTERIOR, SHALL BE
 MECHANICALLY VENTED IN ACCORDANCE WITH NFPA 30 AND NFPA
 91.
  
 443.3.7 LIGHTING.
  
 443.3.7.1 ILLUMINATION LEVEL IN
 CLASSROOMS/INSTRUCTIONAL SPACES.
 ILLUMINATION AT THE NORMAL TASK LEVEL FOR THE TYPE OF
 CLASSROOM/INSTRUCTION SPACE SHALL BE A MINIMUM OF FORTY
 (40) FOOT-CANDLES (400 LUX).
  
 443.3.7.2 ILLUMINATION UNIFORMITY IN
 CLASSROOMS/INSTRUCTION SPACES.
 LUMINARIES SHALL HAVE A CEILING ARRANGEMENT OR
 POSITIONED AROUND THE WALLS SUCH THAT A UNIFORMED
 ILLUMINATION LEVEL, WITHIN TEN (10) FOOT-CANDLES (100
 LUX), IS MAINTAINED AT THE STUDENTS REQUIRED NORMAL
 TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION SPACE.
  
 443.3.7.3 BRIGHTNESS RATIO IN CLASSROOMS/INSTRUCTIONAL
 SPACES.
 THE BRIGHTNESS RATIO BETWEEN THE STUDENT TASK LEVEL AND
 THE INSTRUCTION AREA OR AREAS OR VISUAL DISPLAY
 LOCATION SHALL BE ONE(1) TO FIVE(5) OR LESS.
  
 443.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS OF
 EGRESS LUMINARIES.
 ILLUMINATION SYSTEMS SHALL BE DESIGNED AND MAINTAINED
 SO THAT THE FAILURE OF ANY SINGLE LIGHTING UNIT, SUCH
 AS AN ELECTRIC LUMINARY, DOES NOT LEAVE ANY OCCUPIED
 SPACE OR MEANS OF EGRESS IN THE DARK. (SEE FLORIDA
 BUILDING CODE, BUILDING SECTION 1006 FOR ADDITIONAL
 MEANS OF EGRESS REQUIREMENTS.)
  
 443.3.7.5 GLARE ELIMINATION.
 ILLUMINATION OF PERMANENTLY INSTALLED MARKERBOARDS,
 CHALKBOARDS, AND OTHER INSTRUCTION AIDS SHALL BE
 DESIGNED TO ELIMINATE GLARE AND SHADOWS.
  
  
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By rlecky Date 2013-01-10 Time 16:31 Rev Time 0.00
Received By rlecky Date 2013-01-10 Time 14:46 Sent To  
Notes
2013-01-10 16:36:1813010221
 4431 EMBARCADERO DRIVE.
 CHANGE OF OCCUPANCY FROM B TO E
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. DUE TO THE LACK OF DETAIL THIS REVIEW
 IS SUBSTANTIALLY INCOMPLETE.
  
 PROVIDE TWO SETS OF LEGIBLE PLANS FROM A REGISTERED
 DESIGN PROFESSIONAL SHOWING COMPLIANCE WITH THE CODE.
 FBC 107.1
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT
 CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING, AND THE MAIN
 DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC
 250.20
  
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. NEC 230.2, 230.71
  
 PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS.
 INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE
 EQUIPMENT. NEC 210.3, 215.2, 220.40, 230.31, 408.4
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES SHALL BE PROTECTED WITH GFCI S. NEC
 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL,
 UNIFORMITY, BRIGHTNESS AND GLARE IN
 CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7
  
 A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A
 SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS
 REQUIRED. NFPA 101 15.3.4, FBC 907
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By wjolin Date 2013-01-10 Time 14:08 Rev Time 0.00
Received By wjolin Date 2013-01-10 Time 13:49 Sent To  
Notes
2013-01-10 14:07:034431 EMBARCADERO DRIVE
 PERMIT #13010221
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****CHANGE OF OCCUPANCY FROM BUSINESS TO
 EDUCATIONAL****
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EXIT
 ILLUMINATION, EMERGENCY LIGHTING, TRAVEL DISTANCES,
 COMMON PATH OF TRAVEL ETC.
  
 EXIT ACCESS CORRIDORS SHALL BE A MINIMUM OF 6 FEET IN
 WIDTH AND SHALL HAVE A 1-HOUR FIRE RESISTANCE RATING.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ENGINEERED FIRE ALARM CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY (EDUCATIONAL) OF
 THE BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
  
 FOR EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED
 ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2009.
  
 EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE
 PREVENTION CODE - NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INDICATE IF ANY COOKING IS PLANNED AT THIS LOCATION.
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH NFPA 96.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 DUE TO THE LACK OF PLAN INFORMATION, A THOROUGH AND
 COMPLETE FIRE REVIEW CANNOT BE COMPLETED AT THIS TIME.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By tgordon Date 2013-01-10 Time 11:31 Rev Time 0.00
Received By tgordon Date 2013-01-10 Time 11:31 Sent To  
Notes
2013-01-10 11:50:54*** PLANS SUBMITTED ARE LACKING MUCH NEEDED INFOMATION
 ***
  
 1) SEE FBC/EXISTING 909.1 MECHANICAL REQUIREMENTS.
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST
 REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL, THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, MECHANICAL PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
 2) SEE 2010 FBC/ENERGY 503.2.1 CALCULATION OF HEATING
 AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
  
 3) PROVIDE OUTDOOR AIR CALCULATIONS AND OUTDOOR AIR,
 PER 2010 FBC/M 403.2 OUTDOOR AIR REQUIRED.
 THE MINIMUM OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 403.3. VENTILATION SUPPLY
 SYSTEMS SHALL BE DESIGNED TO DELIVER THE REQUIRED RATE
 OF OUTDOOR AIRFLOW TO THE BREATHING ZONE WITHIN EACH
 OCCUPIABLE SPACE.
  
 4) SHOW EXHAUST AIR REQUIREMENTS FOR BATHROOMS AND ANY
 OTHER SPACES THAT MAY REQUIRE IT, PER 2010 FBC/M 403.3
 AND TABLE 403.3.
  
 5) PROVIDE FOR SHUTOFF DAMPER CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES SERVED ARE NOT IN USE, PER 2010
 FBC/ENERGY 503.2.4.4.
  
 6) PROVIDE FOR BALANCE RETURN AIR, PER 2010 FBC/M 601.4
 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 7) PER 2010 FBC/M 606.1 CONTROLS REQUIRED.
 AIR DISTRIBUTION SYSTEMS SHALL BE EQUIPPED WITH SMOKE
 DETECTORS LISTED AND LABELED FOR INSTALLATION IN AIR
 DISTRIBUTION SYSTEMS, AS REQUIRED BY THIS SECTION. DUCT
 SMOKE DETECTORS SHALL COMPLY WITH UL 268A. OTHER SMOKE
 DETECTORS SHALL COMPLY WITH UL 268.
  
 8) PER 2010 FBC/M 607.5 WHERE REQUIRED.
 FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE
 DAMPERS SHALL BE PROVIDED AT THE LOCATIONS PRESCRIBED
 IN SECTIONS 607.5.1 THROUGH 607.5.7. WHERE AN ASSEMBLY
 IS REQUIRED TO HAVE BOTH FIRE DAMPERS AND SMOKE
 DAMPERS, COMBINATION FIRE/SMOKE DAMPERS OR A FIRE
 DAMPER AND SMOKE DAMPER SHALL BE REQUIRED.
  
 2010 FBC/M 607.5.1 FIRE WALLS.
 DUCTS AND AIR TRANSFER OPENINGS PERMITTED IN FIRE WALLS
 IN ACCORDANCE WITH SECTION 706.11 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL BE PROTECTED WITH LISTED
 FIRE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING. WALLS BETWEEN TENANT SEPARATION, COMMON
 SPACES, AND LEASE SPACES WILL MOST LIKELY BE FIRE
 RATED.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By lwagner Date 2013-01-10 Time 13:23 Rev Time 0.00
Received By lwagner Date 2013-01-10 Time 11:51 Sent To  
Notes
2013-01-10 13:23:01FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE PLANS ARE NOT CLEAR AS TO THE REQUIRED DRINKING
 FOUNAINS AND SERVICE SINK. ONE DRINKING FOUNTAIN PER
 100 OCCUPANTS IS REQUIRED. FBC P-403.1
 PLEASE SEE BUILDING COMMENTS FOR ACCESSIBILITY
 REQUIREMENTS
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By ajones Date 2013-01-10 Time 14:15 Rev Time 0.00
Received By ajones Date 2013-01-10 Time 14:15 Sent To  
Notes
2013-01-10 14:18:061/10/13- FAILED- STAFF NEEDS A LETTER FOR CONGRESS
 CROSSINGS DEVELOPER'S ARCHITECTURAL REVIEW BOARD
 APPROVING THE USE OF A CHARTER SCHOOL AT THIS LOCATION.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-82-1441
  