Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-11 Cont ID  
Sent By rmcdouga Date 2013-01-11 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2013-01-11 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-09 Cont ID  
Sent By rmcdouga Date 2013-01-09 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2013-01-09 Time 16:29 Sent To  
Notes
2013-01-09 16:49:162010 FBC
  
 DENIED BY BUILDING
  
 1) THE SELECTED ROOFING SYSTEM ON PAGE 6 OF NOA NUMBER
 10-0330.02 HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF.
 THE STRUCTURE IS LOCATED ON THE INTER-COASTAL WATERWAY
 IN EXPOSURE CATEGORY D WITH A 170 MPH WIND-SPEED.
 BECAUSE THE REQUIRED UPLIFT PRESSURES EXCEED THE DESIGN
 PRESSURE, RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 IS REQUIRED BY LIMITATION NUMBER 7 OF THE NOA.
 LIMITATION NUMBER 7 ON PAGE 11 OF THE NOA, REQUIRES THE
 CALCULATIONS TO BE PREPARED, SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW