Plan Review Details - Permit 13010184
Plan Review Stops For Permit 13010184
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-04-29 Cont ID  
Sent By jwitmer Date 2013-04-29 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2013-04-29 Time 13:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-13 Cont ID  
Sent By jwitmer Date 2013-03-13 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2013-03-13 Time 10:35 Sent To  
Notes
2013-03-13 10:41:13BUILDING PLAN REVIEW
 PERMIT: 13010184
 ADD: 314 CLEMATIS 2ND FLOOR
 CONT: BEST INTERIOR CONSTRUCTION
 TEL: (305)640-3011
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REDUCED SCOPE OF WORK 2ND REVIEW
 DATE: 3/13/2013
 ACTION: DENIED
  
 1) THE DOOR LEADING FROM THE BREAK ROOM TO THE EXIT
 ACCESS CORRIDOR IS SWINGING IN THE WRONG DIRECTION,
 WITH AN OCCUPANT LOAD OF 50 OR GREATER THE DOOR NEEDS
 TO BE AN OUT SWING DOOR. 2010 FBC-B 1008.1.2 DOOR
 SWING. DOORS SHALL SWING IN THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS OR A GROUP H OCCUPANCY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-01-16 Cont ID  
Sent By jwitmer Date 2013-01-16 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2013-01-16 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-15 Cont ID  
Sent By rlecky Date 2013-03-15 Time 11:19 Rev Time 0.00
Received By rlecky Date 2013-03-15 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-01-10 Cont ID  
Sent By rlecky Date 2013-01-10 Time 10:57 Rev Time 0.00
Received By rlecky Date 2013-01-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-04-30 Cont ID  
Sent By wjolin Date 2013-04-30 Time 13:14 Rev Time 0.00
Received By wjolin Date 2013-04-30 Time 13:11 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-03-16 Cont ID  
Sent By wjolin Date 2013-03-16 Time 18:16 Rev Time 0.00
Received By wjolin Date 2013-03-16 Time 18:08 Sent To  
Notes
2013-03-16 18:15:58314 CLEMATIS STREET
 PERMIT #13010184
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-01-14 Cont ID  
Sent By wjolin Date 2013-01-14 Time 13:12 Rev Time 0.00
Received By wjolin Date 2013-01-14 Time 12:42 Sent To  
Notes
2013-01-14 13:11:58314 CLEMATIS STREET - SUITE 200
 PERMIT #13010184
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THEMODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-ROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-30 Cont ID  
Sent By lmartine Date 2013-04-30 Time 16:48 Rev Time 0.00
Received By lmartine Date 2013-04-25 Time 11:19 Sent To  
Notes
2013-04-26 11:20:29SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 15:05 Rev Time 0.00
Received By hmoser Date 2013-03-01 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-16 Cont ID  
Sent By jwitmer Date 2013-01-16 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2013-01-08 Time 11:21 Sent To  
Notes
2013-01-09 11:22:16SENT TO B9 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 15:05 Rev Time 0.00
Received By hmoser Date 2013-03-21 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-01-14 Cont ID  
Sent By tgordon Date 2013-01-14 Time 13:53 Rev Time 0.00
Received By tgordon Date 2013-01-14 Time 13:53 Sent To  
Notes
***NONE***