Plan Review Details - Permit 13010024
Plan Review Stops For Permit 13010024
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-14 Cont ID  
Sent By tgordon Date 2013-01-14 Time 09:34 Rev Time 0.00
Received By tgordon Date 2013-01-10 Time 13:23 Sent To  
Notes
2013-01-11 13:25:20GAVE TO TOM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-07 Cont ID  
Sent By tgordon Date 2013-01-07 Time 11:44 Rev Time 0.00
Received By tgordon Date 2013-01-03 Time 15:54 Sent To  
Notes
2013-01-03 15:54:53TO MECHANICAL
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-01-14 Cont ID  
Sent By tgordon Date 2013-01-14 Time 09:34 Rev Time 0.00
Received By tgordon Date 2013-01-14 Time 09:34 Sent To  
Notes
2013-01-14 09:37:39REVISION TO MECH. PLANS AND CHANGE OF DESIGNER OF MECH.
 PLANS, TO AZTIL A/C.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-07 Cont ID  
Sent By tgordon Date 2013-01-07 Time 10:23 Rev Time 0.00
Received By tgordon Date 2013-01-07 Time 10:22 Sent To  
Notes
2013-01-07 11:23:15*** CORRECTIONS NEEDED TO MECHANICAL PLAN REVISION ***
  
 1) NEED THE DESIGNER'S INFORMATION ON THE PLAN, COMPANY
 NAME, LICENSE NUMBER, INDIVIDUAL'S NAME, ETC. THAT
 APPLY. SEE 2004 FBC 106.1.
  
 2) PLANS SUBMITTED ARE DIFFICULT TO READ. SEE 2004 FBC
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 3) THE FOLLOWING CORRECTIONS ARE NEEDED TO COMPLY WITH
 2004 FBC 106.3.5.
 (A) CAN NOT DETERMINE IF THE AIR HANDLER UNITS ARE IN
 THE ATTIC OR CLOSET.
 (B) CAN NOT TELL WHAT DUCT SIZES GO TO WHAT DUCTS.
 (C) CAN NOT DO A PROPER REVIEW DUE TO THE QUALITY OF
 THE PLANS.
  
 4) NEED TO SHOW THE EQUIPMENT LISTING ON THE PLANS WITH
 THE PROPER INFORMATION, PER 2004 CITY OF WPB AMEND.
 106.3.5.4 (10).
  
 5) SHOW THE LOCATION & SIZE OF THE BATHROOM EXHAUST
 FANS AND CLOTHES DRYER VENT ON PLANS, AND THAT THEY
 COMPLY WITH 2004 FBC/R M1502 AND TABLE M1507.3.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732
  
  
  