Plan Review Details - Permit 12120699
Plan Review Stops For Permit 12120699
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2014-07-22 Cont ID  
Sent By rmcdouga Date 2014-07-22 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2014-07-22 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2014-07-22 Cont ID  
Sent By rmcdouga Date 2014-07-21 Time 19:01 Rev Time 0.00
Received By rmcdouga Date 2014-07-21 Time 17:10 Sent To  
Notes
2014-07-22 10:00:252010 FBC
  
 DENIED BY BUILDING
  
 1) HCD NEEDS TO CHOOSE THE PRODUCT APPROVALS THAT WILL
 BE USED FOR MASTER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 11:08 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 11:08 Sent To  
Notes
2014-06-30 11:52:032010 FBC
  
 TRUSS DRAWINGS ARE DENIED
  
 1) THE DESIGNER OF RECORD FOR THE STRUCTURE HAS
 INDICATED THAT THE TRUSS LAYOUT AND DRAWINGS FOR THE
 MODEL E HIP OPTION DO NOT MATCH THE STRUCTURAL PLANS.
 THE FRAMING AT THE FRONT PORCH IS DIFFERENT THAN THE
 PLANS.
  
 2) THE TRUSS DRAWINGS FOR THE MODEL E GABLE OPTION DO
 NOT HAVE THE DESIGNER OF RECORDS SHOP REVIEW STAMP ON
 THEM. THEY WILL NEED TO BE REVIEWED BY THE D.O.R. IT
 APPEARS THAT THE TRUSS LAYOUT AND DRAWINGS FOR THIS
 OPTION DOES NOT MATCH THE STRUCTURAL PLANS. THE TRUSS
 DRAWINGS HAVE A TWO PLY GIRDER (B5) NEAR THE FRONT
 PORCH AND THE STRUCTURAL DRAWING SHOW THE TRUSSES
 BEARING ON THE EXTERIOR WALL.
  
 3) THE TRUSS LAYOUT PLANS ARE NOT SIGNED AND SEALED BY
 THE TRUSS ENGINEER. FS 471 & FAC 61G-31.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-03-12 Cont ID  
Sent By rmcdouga Date 2014-03-12 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2014-03-12 Time 10:39 Sent To  
Notes
2014-03-12 10:39:482010 FBC
  
 "MASTER" DENIED BY BUILDING
  
 1) NEED TRUSS DRAWINGS AND PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
 SEE PREVIOUS REVIEW COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2014-02-19 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 14:33 Sent To  
Notes
2014-02-19 16:56:392010 FBC / MASTER MODEL "E"
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3 ( NO SHEET A-0.1 WAS
 SUBMITTED.)
  
 2) REVISE WIND DESIGN DATA ON SHEET S-2 TO REFERENCE
 THE 2010 FBC AND A WIND SPEED OF 170 MPH VULT EXPOSURE
 C AND CHANGE ALL OTHER REFERENCES FROM THE 2007
 BUILDING CODE TO THE 2010 FBC. FBC R 301.2.1
  
 3) ON SHEET S-2, REVISE NOTE 2, B TO REFERENCE ACI
 315-08. THE 2008 EDITION IS THE ONE REFERENCED BY THE
 2010 FBCR OR JUST SPECIFY THE CURRENT EDITION. FBCR
 CHAPTER 43
  
 4) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 MODEL "E" STRUCTURE HIP AND GABLE ROOF OPTIONS. FBC
 R802.1.6.1 THESE ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED FOR THE MASTER.
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" WIDE
 CAST-CRETE LINTELS. THE FLORIDA COVER SHEET IS OKAY.
 NOA NO. 12020913 FOR THE 8" WIDE LINTELS WAS NOT
 SUBMITTED. THE ONE THAT WAS IS FOR THE 4, 6 AND 12"
 WIDE LINTELS. DCA RULE 9N-3
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 MANUFACTURED SIDING (IE HARDI-BOARD) AND THE STRUCTURAL
 CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY DCA RULE
 9N-3.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 8) THE PLANS LIST THE CONDITIONED SPACE AS 1096 SQFT
 AND THE ENERGY CALCULATIONS HAVE 1072 SQFT. PLEASE
 CLARIFY WHY THERE IS A DIFFERENCE. CITY AMENDMENTS
 107.2.1
  
 9) THE PLANS SHOW TWO BATHROOMS AND THE BUILDING INPUT
 SUMMARY REPORT HAS ZERO BATHROOMS. PLEASE CALRIFY WHY
 THERE IS A DIFFERENCE. CITY AMENDMENTS 107.2.1
  
 10) THE WINDOW SCHEDULE SPECIFIES 24 EH AND 2843 EH
 SINGLE HUNG WINDOWS. WHAT DOES EH MEAN? THE 24 EH
 SINGLE HUNG WINDOW IS SPECIFIED AS THE BEDROOM EGRESS
 WINDOWS. A 24-5 SH WINDOW IS WHICH IS 37" X 56" IS
 REQUIRED TO MEET EGRESS REQUIREMENTS. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 12:50 Sent To  
Notes
2013-09-18 13:56:592010 FBC / MASTER MODEL "E"
  
 DENIED BY BUILDING
  
 1) SHEETS A0.1,1.2, 2.1,3.1A,3.1B,4.1,AND 5.1 ARE
 MISSING FROM THE PLAN SETS THAT WERE SUBMITTED. CITY
 AMENDMENTS 107.2.1
  
 2) THE PLANS ARE NOT IN THE ORDER SPECIFIED BY THE
 DRAWING INDEX ON THE COVER SHEET. CITY AMENDMENTS
 107.2.1
  
 3) SUBMIT TWO SETS OF MODEL "E" WORSE CASE ENERGY
 CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS FOR THE
 MASTER PER 2010 FBC ENERGY CONSERVATION. SITE SPECIFIC
 ENERGY CALCULATIONS WILL BE REQUIRED FOR EACH PERMIT
 APPLIED FOR UNDER THE MASTER.
  
 4) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3
  
 5) ON SHEET S-2 THE ALLOWABLE COMPONENT AND CLADDING
 WIND PRESSURES FOR THE WALL ZONES IN THE TABLE HAVE AN
 AREA OF 25 SQFT. THE PRESSURES SPECIFIED ON SHEET S-1
 ARE INCORRECTLY SPECIFYING THESE PRESSURES FOR OPENINGS
 THAT ARE LESS THAN 25 SQFT. FOR WORSE CASE, SPECIFY THE
 PRESSURES FOR A 10 SQFT AREA IN THE TABLE AND FOR THE
 SMALLER OPENINGS. FBC R301.2.1
  
 6) ON SHEET S-2, UNDER CONCRETE NOTE #3, THE 1994
 EDITION OF ACI 315 IS SPECIFIED. PLEASE CHANGE TO 2008
 EDITION WHICH IS THE EDITION REFERENCED BY THE 2010
 FBCR OR JUST CURRENT EDITION. FBCR CHAPTER 43
  
 7) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 MODEL "E" STRUCTURE. FBC R802.1.6.1 THESE ARE REQUIRED
 TO BE SUBMITTED AND REVIEWED FOR THE MASTER.
  
 8) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED FOR
 EACH TYPE OF WINDOW AND DOOR, STRUCTURAL MULLIONS, ROOF
 COVERING, STORM PANELS (IF IMPACT GLAZING IS NOT USED),
 BLOCK LINTELS, MANUFACTURED SIDING (IE HARDI-BOARD),
 STRUCTURAL CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY
 DCA RULE 9N-3. NOTE:THE COPIED PRODUCT APPROVALS FROM
 MODEL B THAT WERE SUBMITTED ARE CURRENT & CAN BE USED
 IF THESE ARE THE PRODUCTS THAT WILL BE INSTALLED FOR
 THIS MODEL.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 SEE REVIEW COMMENTS UNDER OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-04 Cont ID  
Sent By rmcdouga Date 2013-01-04 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2013-01-04 Time 16:42 Sent To  
Notes
2013-01-04 16:42:432010 FBC
  
 DENIED BY BUILDING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 3) UPDATE THE WIND SPEED INFORMATION ON SHEET S-2 TO
 170 MPH VULT / 132 VASD. FBCR301.2.1
  
 4) UPDATE THE CODE AND STANDARDS REFERENCED ON SHEET
 S-2 TO FBC 2010, ACI 318 - 2008, ACI 530 - 2008 AND ACI
 315 - 2008. FBCR CHAPTER 43
  
 5) EXPOSURE CATEGORY C IS SPECIFIED ON THE PLANS. NOTE:
 IF THERE ARE ANY STRUCTURES THAT WILL BE CONSTRUCTED
 UNDER THIS MASTER WITHIN 600 FT OF THE INTER-COASTAL
 WATERWAY OR OTHER BODY OF WATER WITH A ONE MILE FETCH
 THEN THEY ARE CONSIDERED EXPOSURE D. FBCR 301.2.1.4.2
  
 6) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN.
 FBCR401.3
  
 7) UPDATE CODE AND STANDARDS ON THE COVER SHEET (IE
 2010 FBC, 2010 FIRE PREVENTION CODE,2008 NEC). NOTE:
 THE FAIRHOUSING GUIDELINES DO NOT APPLY TO ONE AND TWO
 FAMILY DWELLINGS.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, ROOFING MATERIAL, BLOCK LINTELS, TRUSS
 ANCHORS, ETC. AS REQUIRED BY DCA RULE 9N-3.
  
 9) PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY
 AMENDMENTS 107.3.4.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2014-02-19 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 12:51 Sent To  
Notes
2013-09-18 14:58:382008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE
 MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT
 TO BE 35 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40
 AMP BREAKER. PLEASE CORRECT.
  
 2) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE
 MAXIMUM OVER CURRENT PROTECTION FOR THE AIR AHANDLER
 UNIT TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS
 A 45 AMP BREAKER. PLEASE CORRECT.
  
 3) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM
 RESISTANCE. NEC 250.56
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:54 Sent To  
Notes
2013-01-03 09:56:102010 FBC
  
 DENIED BY ELECTRIC
  
 1) ARC-FAULT CIRCUIT-INTERRUPTERS REQUIRED IN
 ACCORDANCE WITH 2008 NEC ARTICLE 210.12.
  
 2) TAMPER-RESISTANT RECEPTACLES REQUIRED IN ACCORDANCE
 WITH 2008 NEC ARTICLE 210.12.
  
 3) PLEASE UPDATE THE CODE EDITIONS REFERENCED ON
 ELECTRICAL SHEETS TO 2010 FBC, 2007 NFPA 72, 2009 NFPA
 101 AND 2010 NFPA 1.
  
 4) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 REDLINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-12 Cont ID  
Sent By rmcdouga Date 2014-03-12 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2014-03-10 Time 10:38 Sent To  
Notes
2014-03-12 10:39:02SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2014-02-19 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2014-02-05 Time 14:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2013-09-24 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2013-09-03 Time 12:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 15:53 Sent To  
Notes
2013-09-18 15:53:50NOT REQUIRED FOR MASTER. PLANS SUBMITTED FOR PERMIT
 UNDER THE MASTER ARE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY FOR IMPACT FEES. ONE SET OF APPROVED PLANS
 TO BE TAKEN TO COUNTY AND REVIEWED. THE PLANS WITH THE
 IMPACT FEE STAMP AND A COPY OF THE IMPACT FEE PAID
 RECEIPT ARE TO BE RETURNED TO WPB BUILDING DIVISION FOR
 REVIEW BEFORE THE BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2014-02-19 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 14:54 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 12:51 Sent To  
Notes
2013-09-18 14:54:072010 FBC
  
 DENIED BY MECHANICAL
  
 1) ON PLAN SHEET M-1. WIND LOAD REFERS TO TABLE 1609.6A
 FBC 2007. THIS TABLE IS NO LONGER IN THE CODE. CHANGE
 TO 2010 FBCR AND ASCE 7-10.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 11:27 Sent To  
Notes
2013-01-03 11:27:422010 FBC
  
 DENIED BY MECHANICAL
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3.
  
 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 4) ON SHEET M-1 UPDATE THE WIND SPEED TO 170 MPH
 VULT/132 MPH VASD AND THE EDITION OF ASCE 7 TO ASCE
 7-10. FBCR 301.2.1 AND CHAPTER 43.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-02-19 Cont ID  
Sent By rmcdouga Date 2014-02-19 Time 14:11 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 12:51 Sent To  
Notes
2013-09-18 14:59:432010 FBC
  
 PLUMBING DENIED
  
 1) REMOVE THE "WITH 2009 SUPPLEMENT" FROM PLUMBING NOTE
 1 ON SHEET P-2.
  
 2) CHANGE THE NOTE AT THE BOTTOM OF THE HORIZONTAL PIPE
 SLOPE TABLE ON SHEET P-2 FROM 2007 TO 2010 FBC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:52 Sent To  
Notes
2013-01-03 09:52:272010 FBC
  
 DENIED BY PLUMBING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) REVISE PLUMBING NOTE #1 ON SHEET P-2 TO REFERENCE
 THE 2010 FBC.
  
 3) REVISE THE AIR ADMITTANCE VALVE DETAIL TO REFERENCE
 THE CURRENT CODE SECTIONS (IE FBC PLUMBING 917.4 AND
 FBCR P3114.4).
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-24 Cont ID  
Sent By jroach Date 2013-09-24 Time 09:02 Rev Time 0.00
Received By jroach Date 2013-09-24 Time 09:02 Sent To  
Notes
2013-09-24 09:05:02PROVISO: MASTER PERMIT FOR STRUCTURE ONLY! EACH
 PROPERTY SHALL BE PERMITTED SEPARATELY AND SHALL
 PROVIDE SITE-SPECIFIC SITE PLANS, LANDSCAPE PLANS, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 1 Status N Date 2013-09-19 Cont ID  
Sent By llouie Date 2013-09-19 Time 08:25 Rev Time 0.00
Received By llouie Date 2013-09-19 Time 08:25 Sent To  
Notes
2013-09-19 08:26:39ZONING REVIEW NOT REQUIRED FOR MASTER; HOWEVER, PLEASE
 NOTE THE FOLLOWING:
  
 1.) A SURVEY SHALL BE REQUIRED FOR EACH SITE SPECIFIC
 PROJECT.
  
 2.) THE SITE PLAN FOR EACH SITE SPECIFIC PROJECT SHALL
 COMPLY WITH THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 3.) THE LANDSCAPING FOR EACH SITE SPECIFIC PROJECT
 SHALL REQUIRE A SEPARATE PERMIT AND SHALL BE
 ACCOMPANIED WITH LANDSCAPE AND IRRIGATION PLANS.
  