Plan Review Details - Permit 12120698
Plan Review Stops For Permit 12120698
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-21 Cont ID  
Sent By rmcdouga Date 2013-03-21 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2013-03-20 Time 16:49 Sent To  
Notes
2013-03-21 14:22:34MASTER FOR MODEL "B" HAS BEEN REVIEWED FOR CODE
 COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-12 Cont ID  
Sent By rmcdouga Date 2013-02-12 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 14:46 Sent To  
Notes
2013-02-12 15:20:462010 FBC
  
 DENIED BY BUILDING
  
 1) THE WINDLOAD PRESSURES FOR THE OVERHEAD GARAGE DOOR
 SPECIFIED ON SHEET S-1 OF THE PLANS IS HIGHER THAN
 REQUIRED. THE PRODUCT APPROVAL THAT IS SUBMITTED IS
 REQUIRED TO MEET OR EXCEED THE PRESSURES SPECIFIED ON
 THE PLANS. DCA RULE 9N-3.
  
 2) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBCR 401.3. THESE CAN BE SUBMITTED WITH
 EACH PERMIT APPLIED FOR UNDER THE MASTER.
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, OVERHEAD GARAGE DOORS, ROOFING
 MATERIAL, BLOCK LINTELS, TRUSS ANCHORS, MULLIONS,
 HARDI-PLANK SIDING, ETC. AS REQUIRED BY DCA RULE 9N-3.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY
 AMENDMENTS 107.3.4.1.
  
 5) SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS DRAWINGS
 AND LAYOUTS THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD. FBCR 802.1.6.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-04 Cont ID  
Sent By rmcdouga Date 2013-01-04 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2013-01-04 Time 16:43 Sent To  
Notes
2013-01-04 16:43:192010 FBC
  
 DENIED BY BUILDING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 3) UPDATE THE WIND SPEED INFORMATION ON SHEET S-2 TO
 170 MPH VULT / 132 VASD. FBCR301.2.1
  
 4) UPDATE THE CODE AND STANDARDS REFERENCED ON SHEET
 S-2 TO FBC 2010, ACI 318 - 2008, ACI 530 - 2008 AND ACI
 315 - 2008. FBCR CHAPTER 43
  
 5) EXPOSURE CATEGORY C IS SPECIFIED ON THE PLANS. NOTE:
 IF THERE ARE ANY STRUCTURES THAT WILL BE CONSTRUCTED
 UNDER THIS MASTER WITHIN 600 FT OF THE INTER-COASTAL
 WATERWAY OR OTHER BODY OF WATER WITH A ONE MILE FETCH
 THEN THEY ARE CONSIDERED EXPOSURE D. FBCR 301.2.1.4.2
  
 6) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN.
 FBCR401.3
  
 7) UPDATE CODE AND STANDARDS ON THE COVER SHEET (IE
 2010 FBC, 2010 FIRE PREVENTION CODE,2008 NEC). NOTE:
 THE FAIRHOUSING GUIDELINES DO NOT APPLY TO ONE AND TWO
 FAMILY DWELLINGS.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, ROOFING MATERIAL, BLOCK LINTELS, TRUSS
 ANCHORS, ETC. AS REQUIRED BY DCA RULE 9N-3.
  
 9) PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY
 AMENDMENTS 107.3.4.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By rmcdouga Date 2013-02-12 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 14:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 08:21 Sent To  
Notes
2013-01-03 08:57:222010 FBC
  
 DENIED BY ELECTRIC
  
 1) ARC-FAULT CIRCUIT-INTERRUPTERS REQUIRED IN
 ACCORDANCE WITH 2008 NEC ARTICLE 210.12.
  
 2) TAMPER-RESISTANT RECEPTACLES REQUIRED IN ACCORDANCE
 WITH 2008 NEC ARTICLE 210.12.
  
 3) THE RECEPTACLE FOR THE GARAGE DOOR OPENER IS
 REQUIRED TO BE GFCI PROTECTED PER NEC ARTICLE 210.8
 (A)(2).
  
 4) PLEASE UPDATE THE CODE EDITIONS REFERENCED ON
 ELECTRICAL SHEETS TO 2010 FBC, 2007 NFPA 72, 2009 NFPA
 101 AND 2010 NFPA 1.
  
 5) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 REDLINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-21 Cont ID  
Sent By rmcdouga Date 2013-03-21 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2013-03-15 Time 18:29 Sent To  
Notes
2013-03-15 18:29:31TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-21 Cont ID  
Sent By rmcdouga Date 2013-03-21 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2013-03-14 Time 14:15 Sent To  
Notes
2013-03-15 14:15:48GAVE TO ROBBIE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By rmcdouga Date 2013-02-12 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 14:46 Sent To  
Notes
2013-02-12 15:52:30TWO SETS OF SITE SPECIFIC ENERGY CALCULATIONS AND HVAC
 EQUIPMENT SIZING CALCULATIONS WILL BE REQUIRED WITH
 EACH PERMIT APPLIED FOR UNDER THE MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:57 Sent To  
Notes
2013-01-03 10:26:112010 FBC
  
 DENIED BY MECHANICAL
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3.
  
 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 4) ON SHEET M-1 UPDATE THE WIND SPEED TO 170 MPH
 VULT/132 MPH VASD AND THE EDITION OF ASCE 7 TO ASCE
 7-10. FBCR 301.2.1 AND CHAPTER 43.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By rmcdouga Date 2013-02-12 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:38 Sent To  
Notes
2013-01-03 09:39:412010 FBC
  
 DENIED BY PLUMBING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) REVISE PLUMBING NOTE #1 ON SHEET P-2 TO REFERENCE
 THE 2010 FBC.
  
 3) REVISE THE AIR ADMITTANCE VALVE DETAIL TO REFERENCE
 THE CURRENT CODE SECTIONS (IE FBC PLUMBING 917.4 AND
 FBCR P3114.4).
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-12 Cont ID  
Sent By rmcdouga Date 2013-02-12 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 14:45 Sent To  
Notes
***NONE***