Plan Review Details - Permit 12120697
Plan Review Stops For Permit 12120697
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2014-07-29 Cont ID  
Sent By rmcdouga Date 2014-07-29 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2014-07-29 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2014-07-22 Cont ID  
Sent By rmcdouga Date 2014-07-22 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2014-07-22 Time 07:30 Sent To  
Notes
2014-07-22 09:51:002010 FBC
  
 1) TRUSS LAYOUT AND DRAWINGS WERE NOT RE-SUBMITTED.
  
 2) HCD NEEDS TO CHOOSE PRODUCT APPROVALS THAT ARE TO BE
 USED FOR MASTER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-06-30 Cont ID  
Sent By rmcdouga Date 2014-06-30 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2014-06-30 Time 12:25 Sent To  
Notes
2014-06-30 13:02:482010 FBC
  
 TRUSS DRAWINGS ARE DENIED
  
 1) THE TRUSS LAYOUT AND DRAWINGS FOR THE MODEL 'A'
 GABLE OPTION DO NOT HAVE THE DESIGNER OF RECORD FOR THE
 STRUCTURE'S SHOP DRAWING REVIEW STAMP ON THEM. THEY
 NEED TO BE REVIEWED BY THE D.O.R. THE TRUSS LAYOUT
 APPEARS TO BE CONSISTENT WITH THE STRUCTURAL PLANS.
  
 2) THE TRUSS LAYOUT AND DRAWINGS FOR THE MODEL 'A' HIP
 OPTION DO NOT HAVE THE DESIGNER OF RECORD FOR THE
 STRUCTURE'S SHOP DRAWING REVIEW STAMP ON THEM. THEY
 NEED TO BE REVIEWED BY THE D.O.R. THE TRUSS LAYOUT
 APPEARS TO BE CONSISTENT WITH THE STRUCTURAL PLANS.
  
 3) THE TRUSS LAYOUTS FOR BOTH OPTIONS HAVE NOT BEEN
 SIGNED AND SEALED BY THE TRUSS ENGINEER. FS 471 & FAC
 61G15-31.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-03-12 Cont ID  
Sent By rmcdouga Date 2014-03-12 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2014-03-12 Time 06:42 Sent To  
Notes
2014-03-12 10:37:212010 FBC
  
 "MASTER" DENIED BY BUILDING
  
 1) NEED TRUSS DRAWINGS AND PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
 SEE PREVIOUS REVIEW COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-22 Cont ID  
Sent By rmcdouga Date 2014-02-22 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 19:00 Sent To  
Notes
2014-02-22 10:34:342010 FBC / MASTER MODEL "A"
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A GENERIC MODEL "A" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3 ( NO SHEET A-0.1 WAS
 SUBMITTED.)
  
 2) REVISE WIND DESIGN DATA ON SHEET S-2 TO REFERENCE
 THE 2010 FBC AND A WIND SPEED OF 170 MPH VULT/132 MPH
 VASD EXPOSURE C AND CHANGE ALL OTHER REFERENCES FROM
 THE 2007 BUILDING CODE TO THE 2010 FBC. FBC R 301.2.1
  
 3) ON SHEET S-2, REVISE NOTE 2, B TO REFERENCE ACI
 315-08. THE 2008 EDITION IS THE ONE REFERENCED BY THE
 2010 FBCR OR JUST SPECIFY THE CURRENT EDITION. FBCR
 CHAPTER 43
  
 4) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 MODEL "A" STRUCTURE HIP AND GABLE ROOF OPTIONS. FBC
 R802.1.6.1 THESE ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED FOR THE MASTER.
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" WIDE
 CAST-CRETE LINTELS. THE FLORIDA COVER SHEET IS OKAY.
 NOA NO. 12020913 FOR THE 8" WIDE LINTELS WAS NOT
 SUBMITTED. THE ONE THAT WAS IS FOR THE 4, 6 AND 12"
 WIDE LINTELS. DCA RULE 9N-3
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 OVERHEAD GARAGE DOOR AND THE STRUCTURAL CONNECTORS (IE
 TRUSS ANCHORS) AS REQUIRED BY DCA RULE 9N-3.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 8) THE PLANS SHOW TWO BATHROOMS AND THE BUILDING INPUT
 SUMMARY REPORT HAS ZERO BATHROOMS. PLEASE CALRIFY WHY
 THERE IS A DIFFERENCE. CITY AMENDMENTS 107.2.1
  
 9) THE WINDOW SCHEDULE SPECIFIES 24 EH AND 2843 EH
 SINGLE HUNG WINDOWS. WHAT DOES EH MEAN? THE 24 EH
 SINGLE HUNG WINDOW IS SPECIFIED AS THE BEDROOM EGRESS
 WINDOWS. A 24-5 SH WINDOW IS WHICH IS 37" X 56" IS
 REQUIRED TO MEET EGRESS REQUIREMENTS. PLEASE CLARIFY.
  
 PLEASE SUBMIT A RESPONSE LETTER THAT DETAILS HOW EACH
 OF THE REVIEW COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 12:14 Rev Time 0.00
Received By rmcdouga Date 2013-09-17 Time 18:18 Sent To  
Notes
2013-09-17 18:43:592010 FBC / MASTER MODEL "A"
  
 DENIED BY BUILDING
  
 1) SHEETS A0.1,1.2, 2.1,3.1A,3.1B,4.1,AND 5.1 ARE
 MISSING FROM THE PLAN SETS THAT WERE SUBMITTED. CITY
 AMENDMENTS 107.2.1
  
 2) THE PLANS ARE NOT IN THE ORDER SPECIFIED BY THE
 DRAWING INDEX ON THE COVER SHEET. CITY AMENDMENTS
 107.2.1
  
 3) SUBMIT TWO SETS OF MODEL "A" WORSE CASE ENERGY
 CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS FOR THE
 MASTER PER 2010 FBC ENERGY CONSERVATION. SITE SPECIFIC
 ENERGY CALCULATIONS WILL BE REQUIRED FOR EACH PERMIT
 APPLIED FOR UNDER THE MASTER.
  
 4) SUBMIT TWO COPIES OF A GENERIC MODEL "A" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3
  
 5) ON SHEET S-2 THE ALLOWABLE COMPONENT AND CLADDING
 WIND PRESSURES FOR THE WALL ZONES IN THE TABLE HAVE AN
 AREA OF 25 SQFT. THE PRESSURES SPECIFIED ON SHEET S-1
 ARE INCORRECTLY SPECIFYING THESE PRESSURES FOR OPENINGS
 THAT ARE LESS THAN 25 SQFT. FOR WORSE CASE, SPECIFY THE
 PRESSURES FOR A 10 SQFT AREA IN THE TABLE AND FOR THE
 SMALLER OPENINGS. FBC R301.2.1
  
 6) ON SHEET S-1, THERE ARE TWO SETS OF PRESSURES
 SPECIFIED FOR THE GARAGE DOOR. THIS IS ONE OPENING,
 THEREFORE, ONLY ONE SET OF PRESSURES SHOULD BE USED FOR
 IT. FBC R301.2.1
  
 7) ON SHEET S-2, UNDER CONCRETE NOTE #3, THE 1994
 EDITION OF ACI 315 IS SPECIFIED. PLEASE CHANGE TO 2008
 EDITION WHICH IS THE EDITION REFERENCED BY THE 2010
 FBCR OR JUST CURRENT EDITION. FBCR CHAPTER 43
  
 8) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FBC R802.1.6.1 THESE ARE REQUIRED TO BE
 SUBMITTED AND REVIEWED FOR THE MASTER.
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE SHED ROOFS OVER
 THE EXTERIOR DOORS ON THE LEFT AND RIGHT ELEVATIONS.
 FBC R301.1
  
 9) TWO COPIES OF PRODUCT APPROVALS ARE REQUIRED FOR
 EACH TYPE OF WINDOW AND DOOR, STRUCTURAL MULLIONS, ROOF
 COVERING, OVERHEAD GARAGE DOOR, STORM PANELS (IF IMPACT
 GLAZING IS NOT USED), BLOCK LINTELS, MANUFACTURED
 SIDING (IE HARDI-BOARD), STRUCTURAL CONNECTORS (IE
 TRUSS ANCHORS) AS REQUIRED BY DCA RULE 9N-3. NOTE:THE
 COPIED PRODUCT APPROVALS FROM MODEL B THAT WERE
 SUBMITTED ARE CURRENT & CAN BE USED IF THESE ARE THE
 PRODUCTS THAT WILL BE INSTALLED FOR THIS MODEL.
  
 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 SEE REVIEW COMMENTS UNDER OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 11:29 Sent To  
Notes
2013-01-03 13:16:502010 FBC
  
 DENIED BY BUILDING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 3) UPDATE THE WIND SPEED INFORMATION ON SHEET S-2 TO
 170 MPH VULT / 132 VASD. FBCR301.2.1
  
 4) UPDATE THE CODE AND STANDARDS REFERENCED ON SHEET
 S-2 TO FBC 2010, ACI 318 - 2008, ACI 530 - 2008 AND ACI
 315 - 2008. FBCR CHAPTER 43
  
 5) EXPOSURE CATEGORY C IS SPECIFIED ON THE PLANS. NOTE:
 IF THERE ARE ANY STRUCTURES THAT WILL BE CONSTRUCTED
 UNDER THIS MASTER WITHIN 600 FT OF THE INTER-COASTAL
 WATERWAY OR OTHER BODY OF WATER WITH A ONE MILE FETCH
 THEN THEY ARE CONSIDERED EXPOSURE D. FBCR 301.2.1.4.2
  
 6) SUBMIT TWO COPIES OF A SURFACE DRAINAGE PLAN.
 FBCR401.3
  
 7) UPDATE CODE AND STANDARDS ON THE COVER SHEET (IE
 2010 FBC, 2010 FIRE PREVENTION CODE,2008 NEC). NOTE:
 THE FAIRHOUSING GUIDELINES DO NOT APPLY TO ONE AND TWO
 FAMILY DWELLINGS.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, ROOFING MATERIAL, BLOCK LINTELS, TRUSS
 ANCHORS, ETC. AS REQUIRED BY DCA RULE 9N-3.
  
 9) PRODUCT APPROVALS ARE REQUIRED TO REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PER CITY
 AMENDMENTS 107.3.4.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-02-22 Cont ID  
Sent By rmcdouga Date 2014-02-22 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2014-02-22 Time 10:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-09-17 Cont ID  
Sent By rmcdouga Date 2013-09-17 Time 18:28 Rev Time 0.00
Received By rmcdouga Date 2013-09-17 Time 18:18 Sent To  
Notes
2013-09-17 18:43:172008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE
 MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT
 TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40
 AMP BREAKER. PLEASE CORRECT.
  
 2) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM
 RESISTANCE. NEC 250.56
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:53 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:53 Sent To  
Notes
2013-01-03 09:54:222010 FBC
  
 DENIED BY ELECTRIC
  
 1) ARC-FAULT CIRCUIT-INTERRUPTERS REQUIRED IN
 ACCORDANCE WITH 2008 NEC ARTICLE 210.12.
  
 2) TAMPER-RESISTANT RECEPTACLES REQUIRED IN ACCORDANCE
 WITH 2008 NEC ARTICLE 210.12.
  
 3) THE RECEPTACLE FOR THE GARAGE DOOR OPENER IS
 REQUIRED TO BE GFCI PROTECTED PER NEC ARTICLE 210.8
 (A)(2).
  
 4) PLEASE UPDATE THE CODE EDITIONS REFERENCED ON
 ELECTRICAL SHEETS TO 2010 FBC, 2007 NFPA 72, 2009 NFPA
 101 AND 2010 NFPA 1.
  
 5) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 REDLINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-29 Cont ID  
Sent By rmcdouga Date 2014-07-29 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2014-07-25 Time 09:27 Sent To  
Notes
2014-07-28 09:27:26RE-SUBMITTAL SENT TO ROBERT MCDOUGAL'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-12 Cont ID  
Sent By rmcdouga Date 2014-03-12 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2014-03-10 Time 06:42 Sent To  
Notes
2014-03-12 06:42:47SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-22 Cont ID  
Sent By rmcdouga Date 2014-02-22 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2014-02-05 Time 19:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 12:15 Rev Time 0.00
Received By rmcdouga Date 2013-09-03 Time 18:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-09-17 Cont ID  
Sent By rmcdouga Date 2013-09-17 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2013-09-17 Time 18:44 Sent To  
Notes
2013-09-17 18:46:13NOT REQUIRED FOR MASTER. PLANS SUBMITTED FOR PERMIT
 UNDER THE MASTER ARE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY FOR IMPACT FEES. ONE SET OF APPROVED PLANS
 TO BE TAKEN TO COUNTY AND REVIEWED. THE PLANS WITH THE
 IMPACT FEE STAMP AND A COPY OF THE IMPACT FEE PAID
 RECEIPT ARE TO BE RETURNED TO WPB BUILDING DIVISION FOR
 REVIEW BEFORE THE BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-02-20 Cont ID  
Sent By rmcdouga Date 2014-02-20 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2014-02-20 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-09-17 Cont ID  
Sent By rmcdouga Date 2013-09-17 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2013-09-17 Time 18:18 Sent To  
Notes
2013-09-17 18:28:362010 FBC
  
 DENIED BY MECHANICAL
  
 1) ON PLAN SHEET M-1. WIND LOAD REFERS TO TABLE 1609.6A
 FBC 2007. THIS TABLE IS NO LONGER IN THE CODE. CHANGE
 TO 2010 FBCR AND ASCE 7-10.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 11:26 Sent To  
Notes
2013-01-03 11:26:572010 FBC
  
 DENIED BY MECHANICAL
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3.
  
 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 405.4.
  
 4) ON SHEET M-1 UPDATE THE WIND SPEED TO 170 MPH
 VULT/132 MPH VASD AND THE EDITION OF ASCE 7 TO ASCE
 7-10. FBCR 301.2.1 AND CHAPTER 43.
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-02-20 Cont ID  
Sent By rmcdouga Date 2014-02-20 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2014-02-19 Time 19:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-09-17 Cont ID  
Sent By rmcdouga Date 2013-09-17 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2013-09-17 Time 18:18 Sent To  
Notes
2013-09-17 18:24:382010 FBC
  
 PLUMBING DENIED
  
 1) REMOVE THE "WITH 2009 SUPPLEMENT" FROM PLUMBING NOTE
 1 ON SHEET P-2.
  
 2) CHANGE THE NOTE AT THE BOTTOM OF THE HORIZONTAL PIPE
 SLOPE TABLE ON SHEET P-2 FROM 2007 TO 2010 FBC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rmcdouga Date 2013-01-03 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 09:51 Sent To  
Notes
2013-01-03 09:51:432010 FBC
  
 DENIED BY PLUMBING
  
 1) TWO OR MORE SETS OF PLANS THAT HAVE BEEN SIGNED AND
 SEALED BY THE DESIGNER OF RECORD ARE REQUIRED TO BE
 SUBMITTED FOR PERMIT PER CITY AMENDMENTS 107.1.
  
 2) REVISE PLUMBING NOTE #1 ON SHEET P-2 TO REFERENCE
 THE 2010 FBC.
  
 3) REVISE THE AIR ADMITTANCE VALVE DETAIL TO REFERENCE
 THE CURRENT CODE SECTIONS (IE FBC PLUMBING 917.4 AND
 FBCR P3114.4).
  
 NOTE: THE ONE SET OF PLANS THAT WAS SUBMITTED WAS
 RED-LINED TO SHOW WHERE CORRECTIONS WERE NEEDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-24 Cont ID  
Sent By jroach Date 2013-09-24 Time 09:09 Rev Time 0.00
Received By jroach Date 2013-09-24 Time 09:09 Sent To  
Notes
2013-09-24 09:09:56PROVISO: MASTER PERMIT FOR STRUCTURE ONLY! EACH
 PROPERTY SHALL BE PERMITTED SEPARATELY AND SHALL
 PROVIDE SITE-SPECIFIC SITE PLANS, LANDSCAPE PLANS, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.

Review Stop Z ZONING
Rev No 1 Status N Date 2013-09-19 Cont ID  
Sent By llouie Date 2013-09-19 Time 08:05 Rev Time 0.00
Received By llouie Date 2013-09-19 Time 08:05 Sent To  
Notes
2013-09-19 08:19:02ZONING REVIEW NOT REQUIRED FOR MASTER; HOWEVER, PLEASE
 NOTE THE FOLLOWING:
  
 1.) A SURVEY SHALL BE REQUIRED FOR EACH SITE SPECIFIC
 PROJECT.
  
 2.) THE SITE PLAN FOR EACH SITE SPECIFIC PROJECT SHALL
 COMPLY WITH THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 3.) THE LANDSCAPING FOR EACH SITE SPECIFIC PROJECT
 SHALL REQUIRE A SEPARATE PERMIT AND SHALL BE
 ACCOMPANIED WITH LANDSCAPE AND IRRIGATION PLANS.
  