Plan Review Details - Permit 12120636
Plan Review Stops For Permit 12120636
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-02-07 Cont ID  
Sent By jwitmer Date 2013-02-07 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2013-02-07 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-17 Cont ID  
Sent By jwitmer Date 2013-01-17 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2013-01-17 Time 10:18 Sent To  
Notes
2013-01-17 11:38:00BUILDING PLAN REVIEW
 PERMIT: 12120636
 ADD: 1801 PALM BEACH LAKES, JC PENNEY CO.
 CONT: TO BE DETERMINED
 CONTACT: RACHEL SANCHEZ
 TEL: (954)748-7420
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 JAN. 17/ 2013
 ACTION: DENIED
  
 1) SHEET A006 THE OCCUPANCY PLAN PROVIDES THE OCCUPANT
 LOADS AND EGRESS AISLES TO THE EXIT DOORWAYS, THE PLAN
 DOES PROVIDE THE REQUIRED EXIT REQUIRED IN INCHES AND
 EXIT PROVIDED IN INCHES.
  
 WHAT THE PLAN FAILS TO INDICATE HOW THE FOUR EXITS THAT
 ARE IN THE COMMON WALL TO THE MALL AREA ARE GOING TO BE
 PROTECTED TO THE EXIT DISCHARGE. IT APPEARS ONE OF THE
 STAIRWELLS WITH TWO EXIT DOORS EMPTIES DIRECTLY BEHIND
 AN EXTERIOR WALL OF THE MALL THAT WILL BE DEMOLISHED,
 HOW ARE THESE DOORS AND EXIT DISCHARGE GOING TO BE
 PROTECTED DURING THE DEMOLISHION AND NEW CONSTRUCTION.
  
 THE OTHER TWO EXIT DOORS EMPTY INTO A COMMON MALL AREA,
 PLEASE PROVIDE HOW THESE OPENINGS WILL BE PROTECTED TO
 THE EXIT DISCHARGE.
  
 2) PLEASE BE AWARE OF WORK BEING COMPLETED WITHOUT THE
 BENEFIT OF PERMIT. PERMIT 10090508 1801 PB LAKES, FOR
 JC PENNEY TO CLOSE OFF THE ENTRY FROM THE MALL AND
 PENNEY STORE HAS NEVER BEEN ISSUED, FORBES CONSTRUCTION
 APPLIED FOR THE PERMIT, OWES FEES AND NEVER PICKED UP
 THIS PERMIT. WILL BE INVESTIGATED!!!
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-01-14 Cont ID  
Sent By rlecky Date 2013-01-14 Time 09:57 Rev Time 0.00
Received By rlecky Date 2013-01-14 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 10:44 Rev Time 0.00
Received By wjolin Date 2013-02-12 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-01-14 Cont ID  
Sent By wjolin Date 2013-01-14 Time 12:02 Rev Time 0.00
Received By wjolin Date 2013-01-14 Time 11:16 Sent To  
Notes
2013-01-14 12:02:231801 PALM BEACH LAKES BOULEVARD - JCP
 PERMIT #12120636
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LIFE SAFETY PLAN SHOWING FIRE RATED WALLS,
 EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES,
 COMMON PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO EXIT ACCESS DOORS SHOWN IN THE "JOE FRESH" SPACE.
  
 THE SCOPE OF WORK SHOWN ON THE DEMOLITION PLAN AND THE
 OCCUPANCY PLAN SHEETS IS NOT VERY CLEAR. SHEETS APPEAR
 TO SHOWN THE INSTALLATION OF SEVERAL WALLS INDICATED AS
 D1 AND D2. NO DRAWINGS HAVE BEEN SUBMITTED INDICATING
 CHANGES TO THE LIFE SAFETY PLAN, FIRE SPRINKLER SYSTEM
 OR FIRE ALARM SYSTEM.
  
 DUE TO LACK OF PLAN INFORMATION AND SCOPE OF WORK
 CLARITY, A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 PERFORMED AT THIS TIME.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 10:44 Rev Time 0.00
Received By wjolin Date 2013-01-31 Time 07:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-30 Cont ID  
Sent By eschneid Date 2013-01-30 Time 14:23 Rev Time 0.00
Received By eschneid Date 2012-12-20 Time 16:17 Sent To  
Notes
2012-12-21 16:19:48B--11

Review Stop Z ZONING
Rev No 1 Status N Date 2013-01-30 Cont ID  
Sent By eschneid Date 2013-01-30 Time 14:22 Rev Time 0.25
Received By eschneid Date 2013-01-30 Time 14:22 Sent To  
Notes
2013-01-30 14:23:30NO EXTERIOR WORK. VALUE LESS THAN 50% OF STRUCTURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved