Plan Review Details - Permit 12120587
Plan Review Stops For Permit 12120587
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-12-20 Cont ID  
Sent By wjolin Date 2012-12-20 Time 12:54 Rev Time 0.00
Received By wjolin Date 2012-12-20 Time 12:49 Sent To M
Notes
2012-12-20 12:54:281401 FORUM WAY - SUITE #600
 PERMIT #12120587
 MASTER #12110592
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-20 Cont ID  
Sent By tgordon Date 2012-12-20 Time 15:38 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 16:52 Sent To  
Notes
2012-12-19 16:52:56SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-20 Cont ID  
Sent By tgordon Date 2012-12-20 Time 15:37 Rev Time 0.00
Received By tgordon Date 2012-12-20 Time 15:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved