Plan Review Details - Permit 12120425
Plan Review Stops For Permit 12120425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-15 Cont ID  
Sent By jwitmer Date 2013-01-15 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2013-01-15 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-18 Cont ID  
Sent By jwitmer Date 2012-12-18 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2012-12-18 Time 14:01 Sent To  
Notes
2012-12-18 14:09:24BUILDING PLAN REVIEW
 PERMIT: 12120425
 ADD: 1475 CENTREPARK DRIVE SUITE # 140
 CONT: CHANDLER CONSTRUCTION
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WILL REQUIRE A SEPERATE PERMIT APPLICATION FOR SUITE
 # 140 WITH BOTH THE SIGNATURE OF OWNER AND CONTRACTOR.
 105.3 APPLICATION FOR PERMIT.
  
 2) SUITE # 140 SQUARE FOOTAGE IS 6657 SQ FT OR AN
 OCCUPANT LOAD OF 67 OCCUPANTS. 2010 FBC-B 1008.1.2 DOOR
 SWING REQUIRES THE DOOR TO SWING IN THE DIRECTION OF
 EXIT TRAVEL WHEN THE OCCUPANT LOAD OF 50 OR MORE. SEE
 SHEET A-4 SINGLE INSWING DOOR.
  
 3) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2013-01-16 Cont ID  
Sent By lmartine Date 2013-01-16 Time 12:39 Rev Time 0.00
Received By lmartine Date 2013-01-16 Time 12:39 Sent To  
Notes
2013-01-16 12:39:36#140 IS VACANT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-12-31 Cont ID  
Sent By rlecky Date 2012-12-31 Time 14:44 Rev Time 0.00
Received By rlecky Date 2012-12-31 Time 14:40 Sent To  
Notes
2012-12-31 14:44:43NO ELECTRICAL PROPOSED OR SHOWN FOR SUITE 140

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-01-15 Cont ID  
Sent By wjolin Date 2013-01-15 Time 14:00 Rev Time 0.00
Received By wjolin Date 2013-01-15 Time 14:00 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-17 Cont ID  
Sent By wjolin Date 2012-12-17 Time 10:53 Rev Time 0.00
Received By wjolin Date 2012-12-17 Time 10:46 Sent To  
Notes
2012-12-17 10:53:261475 CENTREPARK DRIVE WEST - #140
 PERMIT #12120425
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WITH THE CREATION OF SUITE #135, THE EXISTING EXIT
 SIGNS, EMERGENCY LIGHTING, AND FIRE ALARM DEVICES IN
 SUITE #140 MAY REQUIRE MODIFICATION AND ADDITIONAL
 FIXTURES MAY BE NEEDED. PROVIDE A REVISED LIFE SAFETY
 PLAN FOR SUITE #140.
  
 THE EXISTING EGRESS DOOR LEADING TO THE EXIT PASSAGEWAY
 IS SWINGING AGAINST THE FLOW OF TRAFFIC. DOOR IS
 REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL FOR
 AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-15 Cont ID  
Sent By jwitmer Date 2013-01-15 Time 15:36 Rev Time 0.00
Received By jwitmer Date 2013-01-14 Time 10:35 Sent To  
Notes
2013-01-15 10:36:19SENT TO JW DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-31 Cont ID  
Sent By rlecky Date 2012-12-31 Time 14:46 Rev Time 0.00
Received By rlecky Date 2012-12-13 Time 11:07 Sent To  
Notes
2012-12-13 11:07:46B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-01-15 Cont ID  
Sent By jwitmer Date 2013-01-15 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2013-01-15 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 12:20 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 12:20 Sent To  
Notes
2012-12-19 12:25:15*** MECHANICAL PLAN REVIEW ***
  
 1) SEE BUILDING REVIEW NOTE #1. PHOTO COPY'S ARE NOT
 ACCEPTABLE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-12-14 Cont ID  
Sent By lwagner Date 2012-12-14 Time 11:13 Rev Time 0.00
Received By lwagner Date 2012-12-14 Time 11:13 Sent To  
Notes
2012-12-14 11:15:16NO PLUMBING SHOWN AT THIS TIME

Review Stop Z ZONING
Rev No 1 Status P Date 2012-12-31 Cont ID  
Sent By jroach Date 2012-12-20 Time 14:29 Rev Time 0.00
Received By rlecky Date 2012-12-20 Time 14:29 Sent To  
Notes
2012-12-18 17:17:1612/18/12