Plan Review Details - Permit 12120418
Plan Review Stops For Permit 12120418
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-28 Cont ID  
Sent By jwitmer Date 2012-12-28 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2012-12-28 Time 13:36 Sent To  
Notes
2012-12-28 16:25:27BUILDING PLAN REVIEW
 PERMIT: 12120418
 ADD:1155 BELVEDERE RD
 CONT: TBD
 TEL: (305) 710-1118
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DEC. 28/2012
 ACTION: DENIED
 1) PLEASE BREAK UP THE PROJECT INTO A PERMIT FOR EACH
 OF THE BUILDINGS WHERE WORK IS GOING TO BE PREFORMED.
 THIS PERMIT WILL BE FOR THE EXISTING BUILDING BUILT
 UNDER THE 1201 BELVEDERE ADDRESS IN 1963. PULL THE
 VALUE OUT OF THIS PERMIT AND APPLY IT APPROPRIATELY TO
 THE OTHER BUILDINGS LABELED A, B & C.
  
 2) SHEET A0.01 INDICATES A LEVEL II ALTERATION
 OCCURING, PLEASE BREAK OUT AND IDENTIFY EACH BUILDING
 BY BUILDING TYPE AND ALTERATION LEVEL FOR EACH BUILDING
 SEPERATELY. THE 1201 BELVEDERE BUILDING WILL BE
 CONSIDERED A LEVEL III ALTERATION AS WELL AS A VERTICAL
 ADDITION. PLEASE REVIEW THE REQUIREMENTS FOUND IN 2010
 EXST BLDG CODE 807.2- 807.4.1.
  
 3) 2010 FLORIDA EXIST BLDG CODE 1001.2 CREATION OR
 EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING, OR ELECTRICAL SYSTEMS.
  
 THE PROPOSED PENTHOUSE OR ARCHITECTURAL EMBELLISHMENT
 ON THE EXISTING BUILDING ADDRESSED AT 1201 BELVEDERE RD
 WAS BUILT IN 1963 UNDER THE CODE IT WAS BUILT A BLDG
 TYPE VB, THE CURRENT 2010 FBC CODE ( BLDG TYPE IIIB) IN
 1963, WHICH ALLOWED WOOD ROOF FRAMING AND SHEATHING,
 THE PROPOSED VERTICAL ADDITION IS INDICATED TO BE A
 TYPE IB SEE SHEET A0.01. UNDER THE 2010 FBC 603.1.1
 ONLY FIRE RETARDANT TREATED WOOD CAN BE USED IN THE
 ROOF SYSTEM THE PLANS INDICATE THE EXISTING ROOF
 FRAMING TO REMAIN CREATING A NONCONFORMITY.
  
 4) SHEET A1.01 INDICATES WALL SECTIONS FOUND ON SHEET
 A3.01 AND DETAILS FOUND ON A3.02 THESE PLANS DO NOT
 PROVIDE ANY MAIN WIND FORCE RESISTING SYSTEM DETAILS,
 THESE PLANS AS DRAWN ARE CONCEPTUAL, NOT PLANS THAT CAN
 BE USED FOR CONSTRUCTION DOCUMENTS,
 EXST BLDG CODE 807.2 NEW STRUCTURAL ELEMENTS.
 NEW STRUCTURAL ELEMENTS SHALL COMPLY WITH SECTION
 707.2.
  
 EXST BLDG CODE 807.3 EXISTING STRUCTURAL ELEMENTS
 CARRYING GRAVITY LOADS.
 EXISTING STRUCTURAL ELEMENTS CARRYING GRAVITY LOADS
 SHALL COMPLY WITH SECTION 707.4.
  
 5) MISSING WIND DESIGN CRITERIA:
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6)
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, DENSE GLASS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7) SHEET A1.01 RESTROOM ENLARGED DETAIL, THE DOOR
 SWINGS IN OVER THE REQUIRED CLEAR FLOOR SPACE FOR BOTH
 THE LAV AND WATER CLOSET. 2010 ACCESSIBILITY CODE
 604.3.2 & 606.2.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-02 Cont ID  
Sent By rlecky Date 2013-01-02 Time 16:41 Rev Time 0.00
Received By rlecky Date 2013-01-02 Time 13:39 Sent To  
Notes
2013-01-02 16:46:0112120418
 1155 BELVEDERE ROAD
 COMMERCIAL RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION CODE 505.3
  
 PROVIDE GFCI PROTECTED RECEPTACLES WITHIN A 25 FEET
 RADIUS OF THE OUTSIDE CONDENSING UNITS. NEC 210.63
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 FEEDER TO PANEL ?C? APPEARS TO BE MISLABELED.
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA AND FIRE ALARM.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-12-17 Cont ID  
Sent By wjolin Date 2012-12-17 Time 13:52 Rev Time 0.00
Received By wjolin Date 2012-12-17 Time 12:58 Sent To  
Notes
2012-12-17 13:52:281155 BELVEDERE ROAD
 PERMIT #12120418
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.01: CONFIRM DOOR #02D IS FIRE RATED FOR
 90-MINUTES. FIRE DOORS SHALL BE SELF CLOSING AND
 POSITIVE LATCHING.
  
 SHEET A1.01: PER SECTION 7.2.1.9.1.3 OF NFPA 101- POWER
 OPERATED DOORS: A READILY VISIBLE, DURABLE SIGN IN
 LETTERS NOT LESS THAN 1-INCH HIGH ON A CONTRASTING
 BACKGROUND THAT READS AS FOLLOWS SHALL BE LOCATED ON
 THE EGRESS SIDE OF EACH DOOR OPENING: IN EMERGENCY,
 PUSH TO OPEN.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND/OR FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE EXTERIOR KEY SAFES TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE GATE AND INTO
 THE BUILDING DURING NON-BUSINESS HOURS. KEY SAFES CAN
 BE ORDERED FROM WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-10 Cont ID  
Sent By jwitmer Date 2013-01-10 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2012-12-14 Time 14:51 Sent To  
Notes
2012-12-14 14:51:52C01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-01-10 Cont ID  
Sent By jwitmer Date 2013-01-10 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2013-01-10 Time 13:36 Sent To  
Notes
2013-01-10 13:37:09BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-28 Cont ID  
Sent By tgordon Date 2012-12-28 Time 13:59 Rev Time 0.00
Received By tgordon Date 2012-12-28 Time 12:23 Sent To  
Notes
2012-12-28 14:20:09*** MECHANICAL CORRECTIONS NEEDED ***
  
 1) PLAN M-1.2 SHOWS A FAN CONTROLLER IN THE SPRINKLER
 ROOM BUT NO FAN, PLEASE CORRECT. SEE 2010 CITY OF WPB
 AMEND. 107.2.1.
  
 2) PLAN M-1.0, M-1.1, & M 1.2 MAIN SUPPLY AIR TRUNK
 LINES AND OUTSIDE AIR DUCTS ARE NOT SIZED. SEE 2010
 FBC/M 603.2.
  
 3) PLAN M-1.3 AHU 1 & 2 MAIN SUPPLY AIR TRUNK LINES AND
 OUTSIDE AIR DUCTS ARE NOT SIZED. SEE 2010 FBC/M 603.2.
  
 4) PROVIDE COOLING LOAD CALCULATIONS FOR THE THREE NEW
 A/C SYSTEMS IN THE OFFICE BUILDING. SEE 2010 FBC/ENERGY
 503.2.1.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-02 Cont ID  
Sent By lwagner Date 2013-01-02 Time 09:25 Rev Time 0.00
Received By lwagner Date 2013-01-02 Time 08:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-10 Cont ID  
Sent By escheide Date 2013-01-10 Time 10:44 Rev Time 3.00
Received By eschneid Date 2013-01-09 Time 15:55 Sent To  
Notes
2013-01-09 17:25:29FAILED
  
 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THIS
 PERMIT. THE APPLICATION IS FOR "INTERIOR REMIX AND
 RENOVATION" YET THE PLANS INCLUDE SITE WORK, PARKING
 AND LANDSCAPING PLANS. SEPARATE PERMITS ARE REQUIRED
 FOR THE FOLLOWING:
  
 A. PARKING LOT, TO INCLUDE THE STRIPING.
 B. LANDSCAPE WORK. NOTE ANY TREE REMOVAL OR RELOCATION
 REQUIRES A TREE ALTERATION PERMIT.
 C. SIGNAGE
 D. FENCES AND GATES.
 E. TRASH ENCLOSURES.
 F. IRRIGATION.
  
 2) THE PERMITS FOR EXTERIOR WORK WILL REQUIRE THE
 SUBMITTAL OF TWO COPIES OF A RECENT SURVEY, LESS THAN
 ONE YEAR OLD.
  
 3) THIS PROPERTY IS ZONED COMMERCIAL PLANNED
 DEVELOPMENT, SO ANY CHANGES TO THE EXTERIOR OF THE SITE
 REQUIRE A PLANNED DEVELOPMENT AMENDMENT. PLEASE CONTACT
 THE PLANNING DIVISION FOR THE APPLICATION.
  
 4) THE VALUE OF THE CONSTRUCTION ($650,000) EXCEEDS 50%
 OF THE VALUE OF THE STRUCTURES ON-SITE ($996,730 )
 ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. THE LANDSCAPE PLAN SUBMITTED WITH THE PERMIT
 VERIFIES THAT THE SITE DOES NOT CONFORM TO ARTICLE XIV;
 THEREFORE, PRIOR TO THE ZONING APPROVAL OF THIS PERMIT
 A SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL
 BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO
 CONFORMITY.
  
 5) THE PORTION OF THE PARKING LOT THAT IS BEING MILLED
 AND OVERLAYED SHALL CONFORM TO ALL LANDSCAPE
 REQUIREMENTS.
  
 6) THE PAVING AND GRADING PLAN SEEMS TO INDICATE THAT
 THERE IS A PORTION OF A PARKING SPACE BEING CONSTRUCTED
 WITHIN THE RIGHT-OF-WAY. THIS IS NOT PERMITTED.
  
 7) THE PARKING TABLE USES INCORRECT PARKING
 REQUIREMENTS. PLEASE REFER TO ARTICLE XV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.
  
 8) THE CITY REQUIRES THE USE OF SINGLE SIDED WHEEL
 STOPS.
  
 9) THE PARKING SPACE STRIPING DETAIL SHALL CALL OUT THE
 WIDTH, COLOR AND SPACING OF ALL STRIPING. IT SHALL
 COMPLY WITH THE CITY'S REQUIREMENTS. THE CURRENT SITE
 STRIPING IS NOT IN CONFORMANCE WITH CITY CODE.
  
 10) THE PLANS SEEM TO INDICATE THE REMOVAL OF
 SIGNIFICANT AMOUNTS OF LANDSCAPE, TO INCLUDE FOUNDATION
 PLANTING FOR AT LEAST ONE BUILDING. THE LANDSCAPE
 PERCENTAGE ON THE SITE MAY NOT BE REDUCED BELOW 15% AND
 THE BUILDINGS MAY NOT HAVE THEIR REQUIRED FOUNDATION
 PLANTING REDUCED.
  
 11) THE LAURAL OAK TREE PROPOSED FOR REMOVAL APPEARS TO
 BE ON THE ADJACENT PROPERTY AND THUS MAY NOT BE REMOVED
 BY THIS PROPERTY OWNER.
  
 12) THE SUBMITTED LANDSCAPE PLAN DOES NOT COVER THE
 ENTIRE SITE AND DOES NOT MEET THE MINIMUM REQUIREMENTS
 FOR A LANDSCAPE PLAN. THE LANDSCAPE PLAN WILL BE FULLY
 REVIEWED AS PART OF THE REQUIRED LANDSCAPE PERMIT.
  
 13) THE TRASH ENCLOSURES REQUIRE A 12.5 FOOT CLEAR
 OPENING.
  
 14) THE TRASH ENCLOSURE SHALL HAVE PERIMETER
 LANDSCAPING.
  
 15) NO DIMENSION LINES WERE INCLUDED ON THE ELEVATIONS
 TO VERIFY THE HEIGHT OF THE NEW TOWER.
  
 16) IS THERE ROOF MOUNTED A/C EQUIPMENT PROPOSED? IF SO
 IT SHALL BE SCREENED. PLANS SHALL SHOW THE SCREENING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2012-12-18 17:26:0412/18/12