Plan Review Details - Permit 12120231
Plan Review Stops For Permit 12120231
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-24 Cont ID  
Sent By jwitmer Date 2013-05-24 Time 15:36 Rev Time 0.00
Received By jwitmer Date 2013-05-24 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-14 Cont ID  
Sent By jwitmer Date 2012-12-14 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2012-12-14 Time 08:17 Sent To  
Notes
2012-12-14 14:02:07BUILDING PLAN REVIEW
 PERMIT: 12120231
 ADD: 2623 (2615) OKEECHOBEE BLVD.
 CONT: CARRICK CONTRACTING
 TEL: (561)209-3189
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE USE THE CORRECT ADDRESS FOR THIS PROJECT. THE
 SITE ADDRESS OF 2623 SHOULD NOT BE USED, THE BASE
 BUILDING (SHELL) ADDRESS IS 2615 AND WILL BE THE
 ADDRESS THAT NEEDS TO BE CORRECTED ON BOTH THE PERMIT
 APPLICATION AND THE PERMITED SET OF PLANS THAT WILL TIE
 THE SHELL PERMIT AND TENANT BUILD OUT.
  
 2) THE CONSTRUCTION SERVICES DIVISION WILL NEED A
 LETTER FROM THE OWNER (TENANT) THAT BOTH CONTRACTORS
 WILL WORK TOGETHER TO ENABLE THIS PROJECT TO CONTINUE
 THROUGH
 TO TIME OF C.O. THE TENANT, AND BOTH CONTRACTORS, SHELL
 AND BUILD OUT CONTRACTOR WILL ALSO NEED TO SIGN THE
 NOTARIZED LETTER THEY ARE IN AGREEMENT TO WORK
 TOGETHER.
  
 3) PLEASE SEE SHEET AE 101, DOOR NUMBERS 101 B & 106A,
 PLEASE REVIEW THE 2010 FBC- ACCESSIBILITY CODE DOORS IN
 SERIES 404.2.6 & FIGURE 404.2.6.
  
 4) SHEET M-2 DETAIL # 2 INDICATES ROOF MOUNTED
 CONDENSING UNITS THAT SSIT ON PITCH PANS, PLEASE REVIEW
 THE 2010 FBC-B 1509.7 & TABLE 1509.7 FOR THE REQUIRED
 CLEARENCES BETWEEN THE ROOF SURFACE AND MECHANICAL
 UNIT.
  
 5) SHEET M-1 DEPICTS ROOF TOP PACKAGE UNITS THAT SIT ON
 ROOF TOP CURBS AND DOWNDRAFT UNITS, PLEASE DELETE THE
 DETAILS WHICH ARE NOT GOING TO BE INSTALLED ON THIS
 JOB, DISCREPANCIES. 107.2.1 ADITIONAL INFORMATION IS
 REQUIRED. IF THE ROOF TOP CURBS ARE GOING TO BE
 INSTALLED AND AS NOT PART OF THE SHELL PERMIT, PLEAS
 PROVIDE DETAILS FOR THE ATTACHMENT OF THE CURB TO THE
 ROOFING ASSEMBLY AS WELL AS THE ATTACHMENT OF THE AIR
 HANDLIER TO THE CURB. PLEASE REVIEW 1609.8.ROOF TOP
 STRUCTURES AND EQUIPMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-23 Cont ID  
Sent By dharvey Date 2013-05-23 Time 10:40 Rev Time 0.00
Received By dharvey Date 2013-05-23 Time 10:40 Sent To  
Notes
2013-05-23 10:41:045-23-13
 PREVIOUSLY APPROVED BY RL. NO CHANGES.
 VB

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-27 Cont ID  
Sent By rlecky Date 2012-12-27 Time 15:41 Rev Time 0.00
Received By rlecky Date 2012-12-27 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-22 Cont ID  
Sent By wjolin Date 2013-05-22 Time 11:15 Rev Time 0.00
Received By wjolin Date 2013-05-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-17 Cont ID  
Sent By wjolin Date 2012-12-17 Time 09:53 Rev Time 0.00
Received By wjolin Date 2012-12-17 Time 09:42 Sent To  
Notes
2012-12-17 09:53:402615 OKEECHOBEE BOULEVARD
 PERMIT #12120231
 MASTER #12060789
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL OTHER PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 13:49 Rev Time 0.00
Received By hmoser Date 2013-05-16 Time 14:05 Sent To  
Notes
2013-05-16 14:06:14INCOMING SENT TO C-09 BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-27 Cont ID  
Sent By rlecky Date 2012-12-27 Time 15:41 Rev Time 0.00
Received By rlecky Date 2012-12-07 Time 09:33 Sent To  
Notes
2012-12-13 09:33:38SENT TO B12 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-05-24 Cont ID  
Sent By jwitmer Date 2012-12-27 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2012-12-27 Time 13:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 13:42 Rev Time 0.00
Received By hmoser Date 2013-05-31 Time 11:48 Sent To  
Notes
2013-05-31 13:49:02PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL.
 2010 FLORIDA ENERGY CODE.
 REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS.
 2010 FBC (M) FAN SHUTDOWN FOR FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-17 Cont ID  
Sent By tgordon Date 2012-12-17 Time 12:49 Rev Time 0.00
Received By tgordon Date 2012-12-17 Time 12:49 Sent To  
Notes
2012-12-17 12:56:52*** MECHANICAL CORRECTIONS NEEDED ***
  
 1) PLAN M2 SHOWS DETAIL FOR ROOF MOUNTED CONDENSER
 UNIT. PER 2010 FBC 1509.7 MECHANICAL UNITS. ROOF
 MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 PLEASE COMPLY WITH TABLE 1509.7.
  
 2) PLAN M1 NOTE #6 STATES CONDENSATE FROM AHU-1 TO
 DRAIN INTO MOP SINK, THIS IS PROHIBITED PER. CODE OF
 ORDINANCES CH. 90 ARTICLE III SEC 90-126. PROHIBITIONS
 AND LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS
 SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN
 ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE
 PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY
 WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR
 INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF.
 NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED
 SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE
 FOLLOWING:
 (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By lwagner Date 2013-05-28 Time 14:17 Rev Time 0.00
Received By lwagner Date 2013-05-28 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-14 Cont ID  
Sent By lwagner Date 2012-12-14 Time 15:33 Rev Time 0.00
Received By lwagner Date 2012-12-14 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-12-18 Cont ID  
Sent By ajones Date 2012-12-18 Time 16:56 Rev Time 0.00
Received By ajones Date 2012-12-18 Time 16:56 Sent To  
Notes
***NONE***